Experimental Investigation of Solar-Driven Hollow Fiber Membrane Liquid Dehumidification System
Abstract
:1. Introduction
2. Experimental Set-Up
2.1. Hollow Fiber Membrane Liquid Dehumidification System
2.2. Solar Water Heating System
2.3. Cooling Water System
2.4. Experimental Procedure
- (1)
- Prepare a 35% LiCl solution with LiCl powder and deionized water;
- (2)
- Fill the solution tank with 35% LiCl solution to the operating level;
- (3)
- Turn on the solar collector, adjust the hot water flow rate and run for a period of time, until the hot water temperature meets the regeneration temperature;
- (4)
- Turn on the air-cooled chiller and set the flow rate and temperature, until the chilled water temperature reaches a predefined value;
- (5)
- Turn on the dehumidification and regeneration fans and adjust the air flow rate;
- (6)
- Turn on the solution pump and adjust the solution flow rate to send the desiccant liquid from the solution tank to the dehumidifier;
- (7)
- The system starts to run, and the experiment can be performed after the system parameters meet the requirements and stability.
3. Data Processing
3.1. Data Recording
3.2. Performance Indices
3.3. Uncertainty Analysis
4. Results and Discussion
4.1. Daily and Hourly Variations in Solar Radiation and Solar Collector Performance
4.2. Hourly Variation in Dehumidification Efficiency and Cooling Capacity
4.3. Hourly Variation in Hot Water Temperature and Regeneration Capacity
4.4. Hourly Variation in the COP of the Dehumidification System and Solar Collector
5. Conclusions
- (1)
- The higher/lower hot water temperatures usually correspond to the greater/lower solar radiation. From July to September 2020 in Guilin, China, the maximum daily solar radiation was mainly in the range of 400 W/m2–1000 W/m2, while the maximum daily water temperature was between 50 °C and 80 °C. This means that the solar collectors provide sufficient energy to meet the regeneration demands of the dehumidification system and maintain the system operating continuously.
- (2)
- The dehumidification capacity, dehumidification efficiency and cooling capacity had the maximal values of 0.23 g/s, 71.3%, and 0.63 kW at 17:30, respectively. The regeneration capacity between 12:00 and 16:00 was larger than the dehumidification capacity, while the desiccant solution concentration in the system kept increasing. Therefore, the dehumidification and cooling capacity increased accordingly. This provides for the performance of the dehumidification system when the solar radiation was lower (15:30–17:50).
- (3)
- The hot water in the solar collector supplied energy for solution regeneration. The hot water temperature had a maximum value of 55.5 °C at 15:00, which lagged by about 1.5–3.5 h compared to the maximum solar radiation. The maximum regeneration capacity was 0.36 g/s, which was 0.13 g/s larger than the dehumidification capacity. The water temperature was above 48 °C after 12:00. The regeneration capacity was larger than the dehumidification capacity, which means that the regenerator performance met the system circulation demand. However, the regeneration capacity before 10:30 was less than the dehumidification capacity, which means that the dilute solution needed to be auxiliary-heated to maintain the steady operation of the system.
- (4)
- Because the heat absorption performance of solar collectors was limited, the heat not absorbed dissipated into the ambient, which decreased the COP of solar collectors with the increase in solar radiation. Further, the COP of the dehumidification system and solar collector had the opposite trend to solar radiation. Further, they showed a trend of decrease first, then stabilization for some time and then increased, in which the COP of solar collectors changed more significantly.
- (5)
- It is efficient and economical to supply regenerative energy to hollow fiber membrane liquid dehumidification systems by solar energy. The heat provided by the solar collectors can satisfy the system regeneration demands and ensure the stable operation of the system. However, the auxiliary heating of the regeneration solution is needed to provide regeneration heat when the solar radiation is lower, such as on cloudy and rainy days. In addition, the solar-driven hollow fiber membrane liquid dehumidification system performs better in regions with larger solar radiation.
Author Contributions
Funding
Institutional Review Board Statement
Data Availability Statement
Conflicts of Interest
References
- Sina Tech. China Double Carbon Big Data Index White Paper 2022. Available online: https://finance.sina.com.cn/tech/2022-02-18/doc-ikyamrna1375899.shtml (accessed on 18 February 2022).
- UN Environment Programme. 2021 Global Status Report for Buildings and Construction. Available online: https://www.unep.org/resources/report/2021-global-status-report-buildings-and-construction (accessed on 19 October 2021).
- China Association of Building Energy Efficiency. China Building Energy Consumption Research Report (2020) Results Released. Available online: http://www.cabee.org/site/content/24020.html (accessed on 4 January 2021).
- Zhang, L.Z.; Xiao, F. Simultaneous heat and moisture transfer through a composite supported liquid membrane. Int. J. Heat Mass Transf. 2008, 51, 2179–2189. [Google Scholar] [CrossRef]
- Niu, R.P.; Geng, L.Z.; Fan, Y.Y. Advance in the application of separation membranes in membrane liquid dehumidification. Mater. Rep. 2020, 34, 15069–15074. [Google Scholar]
- Isetti, C.; Nannei, E.; Magrini, A. On the application of a membrane air-liquid contactor for air dehumidification. Energy Build. 1997, 25, 185–193. [Google Scholar] [CrossRef]
- Bergero, S.; Chiari, A. Experimental and theoretical analysis of air humidification/ dehumidification processes using hydrophobic capillary contactors. Appl. Therm. Eng. 2001, 21, 1119–1135. [Google Scholar] [CrossRef]
- Bergero, S.; Chiari, A. On the performances of a hybrid air-conditioning system in different climatic conditions. Energy 2011, 36, 5261–5273. [Google Scholar] [CrossRef]
- Zhang, L.Z. Coupled heat and mass transfer in an application-scale cross-flow hollow fiber membrane module for air humidification. Int. J. Heat Mass Transf. 2012, 55, 5861–5869. [Google Scholar] [CrossRef]
- Li, N.F.; Zhong, T.; Zhou, L.; Huang, S.M.; Zeng, S.; Liang, C.H. Experimental Investigations on the Performance of a Hollow Fiber Membrane Evaporative Cooler (HFMEC) in Hot–Dry Regions. Membranes 2022, 12, 793. [Google Scholar] [CrossRef]
- Energy Efficiency & Renewable Energy. Energy Savings Potential and RD&D Opportunities for Non-Vapor-Compression HVAC Technologies. Available online: http://www.energy.gov/sites/prod/files/2014/03/f12/Non-Vapor%20Compression%20HVAC%20Report.pdf (accessed on 12 March 2014).
- Oberg, V.; Goswami, D.Y. A review of liquid desiccant cooling. Adv. Sol. Energy 1998, 12, 431–470. [Google Scholar]
- Xiao, F.; Ge, G.M.; Niu, X.F. Control performance of a dedicated outdoor air system adopting liquid desiccant dehumidification. Appl. Energy 2011, 88, 143–149. [Google Scholar] [CrossRef]
- Abdel-Salam, A.H.; Ge, G.M.; Simonson, C.J. Performance analysis of a membrane liquid desiccant air-conditioning system. Energy Build. 2013, 62, 559–569. [Google Scholar] [CrossRef]
- Zhang, L.Z.; Zhang, N. A heat pump driven and hollow fiber membrane-based liquid desiccant air dehumidification system: Modeling and experimental validation. Energy 2014, 65, 441–451. [Google Scholar] [CrossRef]
- Das, R.S.; Jain, S. Performance characteristics of cross-flow membrane contactors for liquid desiccant systems. Appl. Energy 2015, 141, 1–11. [Google Scholar] [CrossRef]
- Liu, X.L.; Qu, M.; Liu, X.B. Membrane liquid desiccant air dehumidification: A comprehensive review on materials, components, systems and performances. Renew. Sustain. Energy Rev. 2019, 110, 444–466. [Google Scholar] [CrossRef]
- Bai, H.; Zhu, J.; Chen, X. Steady-state performance evaluation and energy assessment of a complete membrane liquid desiccant dehumidification system. Appl. Energy 2020, 258, 114082. [Google Scholar] [CrossRef]
- Zhang, L.Z.; Jiang, Y. Research and Progress of Membrane Air Dehumidification. Heat. Vent. Air Cond. 1999, 29, 28–32. [Google Scholar]
- Zhang, L.Z.; Huang, S.M. Conjugate heat and mass transfer in a hollow fiber membrane module for liquid desiccant air dehumidification: A free surface model approach. Int. J. Heat Mass Transf. 2012, 55, 3789–3799. [Google Scholar] [CrossRef]
- Zhang, W.R.; Qu, K.Y.; Liu, X.H. Preliminary study of the effect of solution dehumidification methods on indoor air quality. Heat. Vent. Air Cond. 2004, 11, 114–117. [Google Scholar]
- Sahlot, M.; Riffat, S.B. Desiccant cooling systems: A review. Int. J. Low-Carbon Technol. 2016, 11, 489–505. [Google Scholar] [CrossRef] [Green Version]
- Zhang, L.Z. Fabrication of a lithium chloride solution based composite supported liquid membrane and its moisture permeation analysis. J. Membr. Sci. 2006, 276, 91–100. [Google Scholar] [CrossRef]
- Zhang, L.Z.; Wang, Y.Y.; Wang, C.L. Synthesis and characterization of a PVA/LiCl blend membrane for air dehumidification. J. Membr. Sci. 2008, 308, 198–206. [Google Scholar] [CrossRef]
- Zhang, L.Z. Coupled heat and mass transfer through asymmetric porous membranes with finger-like macrovoids structure. Int. J. Heat Mass Transf. 2009, 52, 751–759. [Google Scholar] [CrossRef]
- Huang, S.M.; Zhang, L.Z. Researches and trends in membrane liquid desiccant air dehumidification. Renew. Sustain. Energy Rev. 2013, 28, 425–440. [Google Scholar] [CrossRef]
- Keniar, K.; Ghali, K.; Ghaddar, N. Study of solar regenerated membrane desiccant system to control humidity and decrease energy consumption in office spaces. Appl. Energy 2015, 138, 121–132. [Google Scholar] [CrossRef]
- Abdel-Salam, A.; Ge, G.M.; Simonson, C.J. Thermo-economic performance of a solar membrane liquid desiccant air conditioning system. Sol. Energy 2014, 102, 56–73. [Google Scholar] [CrossRef]
- Bahaidaraha, A.H.M.; Mohamed, M.H.; Mokheimer, E.M.A. Solar-assisted liquid desiccant dehumidification using hollow-fiber and parallel-plate membrane dehumidifiers: Comparative analysis. J. Energy Resour. Technol. 2019, 141, 121201. [Google Scholar] [CrossRef]
- Zhang, N.; Yin, S.Y. Study of energy matching characteristics of solar energy driven membrane liquid desiccant system for air dehumidification. Sol. Energy 2019, 40, 957–962. [Google Scholar]
- Yukui, M.; Nanfeng, L.; Zhipeng, H.; Caihang, L.; Zhenxing, L.; Xiaoman, T. Exergy Analysis of Solar Powered Hollow Fiber Membrane Liquid Dehumidification System. J. Sol. Energy 2022, 43, 261–267. [Google Scholar]
- Gurubalan, A.; Maiya, M.P.; Tiwari, S. A Novel Solar-assisted Membrane-based Liquid Desiccant Air Conditioning System for Hot and Humid Climatic Conditions. In Proceedings of the International Refrigeration and Air Conditioning Conference, West Lafayette, IN, USA, 9–12 July 2018; p. 1920. [Google Scholar]
Geometry Structures | Values | Unit | Membrane Properties | Values | Unit |
---|---|---|---|---|---|
Module length | 280 | mm | Outer diameter | 1.7 | mm |
Module width | 150 | mm | Inner diameter | 1.5 | mm |
Module height | 100 | mm | Water contact angle | 72 (outer) | ° |
105 (inner) | |||||
Tube pitch | 3.5 | mm | Pore size | 0.10 | μm |
Packing Fraction | 0.251 | - | Diffusivity | 9 × 10−7 | m2/s |
Number of total fibers | 1660 | - | Thermal conductivity | 0.17 | W/(m·K) |
Dehumidifier Module | Values | Unit | Regenerator Module | Values | Unit |
---|---|---|---|---|---|
Air flow rate | 60 | m3/h | Air flow rate | 60 | m3/h |
Inlet air temperature | 26.8–33.7 | °C | Inlet air temperature | 24.8–28.9 | °C |
Inlet air humidity ratio | 19.2–21.5 | g/kg | Inlet air humidity ratio | 12.8–14.3 | g/kg |
Cooling water flow rate | 120 | L/h | Hot water flow rate | 120 | L/h |
Cooling water temperature | 22 | °C | Solution flow rate | 120 | L/h |
Parameter | Model | Accuracy | Measurement Range |
---|---|---|---|
Air velocity | Testo 425 | ±0.03 m/s | 0–20 m/s |
Water flow rate | LZB-10 | ±4 L/h | 16–160 L/h |
Solution temperature | PT-100 | ±0.15 °C | −20–250 °C |
Air temperature | Siemens QFM 2160 | ±3.00% | 0–100% |
Relative humidity | Siemens QFM 2160 | ±1 °C | −35–50 °C |
Data acquisition | Agilent 34970A | ±0.15% | - |
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2023 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/).
Share and Cite
Liang, C.-H.; Hu, J.-L.; Li, N.-F.; He, Z.-P.; Mo, C.; Zeng, S. Experimental Investigation of Solar-Driven Hollow Fiber Membrane Liquid Dehumidification System. Membranes 2023, 13, 383. https://doi.org/10.3390/membranes13040383
Liang C-H, Hu J-L, Li N-F, He Z-P, Mo C, Zeng S. Experimental Investigation of Solar-Driven Hollow Fiber Membrane Liquid Dehumidification System. Membranes. 2023; 13(4):383. https://doi.org/10.3390/membranes13040383
Chicago/Turabian StyleLiang, Cai-Hang, Jia-Li Hu, Nan-Feng Li, Zhi-Peng He, Chou Mo, and Si Zeng. 2023. "Experimental Investigation of Solar-Driven Hollow Fiber Membrane Liquid Dehumidification System" Membranes 13, no. 4: 383. https://doi.org/10.3390/membranes13040383
APA StyleLiang, C. -H., Hu, J. -L., Li, N. -F., He, Z. -P., Mo, C., & Zeng, S. (2023). Experimental Investigation of Solar-Driven Hollow Fiber Membrane Liquid Dehumidification System. Membranes, 13(4), 383. https://doi.org/10.3390/membranes13040383