1. Introduction
Depletion of traditional carbon-based energy sources, as well as the rapid increase in power demand all over the world and environmental pollution concerns, has increased the popularity of renewable energy sources [
1]. Solar energy demand is constantly rising due to wide accessibility and reducing cost of photovoltaic panel installation, leading to increased integration of high-scale PV farms into the electrical grid [
2,
3]. Despite the significant advantages associated with integrating PV power sources into the grid, it increases systems’ sensitivity to grid faults. Grid-connected PV sources can affect the voltage profile depending on several factors such as the amount of PV penetration level, load fluctuations, and effects of the PV system transients caused by clouds. Therefore, the power inverters must have excess power capability to absorb or generate reactive power to allow additional voltage regulation [
4]. The transient faults cause an imbalance of generated power by the PV system, a rapid increase of the DC-link voltage, and overcurrent. The power imbalance adds additional stress on the components and has the potential to damage them permanently [
5].
Large-scale penetration of PV power sources into the grid leads to enhanced short-circuit currents. Therefore, it is crucial to maintain the stability of the power system, continuous power flow, and its optimal operation point during transient fault events.
The duration of a fault in a power system is significantly influenced by the nature and location of the fault. The fault that is located closer to the power source will cause higher fault currents. Moreover, three-phase faults tend to be more severe than single-phase faults, resulting in longer durations and more complex recovery processes [
6]. The design and complexity of the power system, especially with the integration of distributed energy resources like PV and wind, can lead to more prolonged and complicated fault and recovery periods due to the need for coordinated responses [
7]. Additionally, the characteristics of system components, such as circuit breakers’ response times and the dynamic behavior of power electronic devices like inverters, also play a critical role in determining fault duration.
Traditional circuit breakers have a relatively long response time during which severe damage can be caused to the components of the power system. Furthermore, the excessive dynamic stress endured during severe faults can result in circuit breaker failures, leading to cascading power outages that can persist for an extended period [
8]. Applying fault current limiters (FCLs) in power grids overcomes the limitations of traditional circuit breakers. This protection approach offers fast response and flexible protection, enhancing safety, reliability, and overall power quality [
9]. Moreover, the FCLs allow the operation of the faulted power line during the faults without opening it. This prevents undesired transient processes in the feeding power sources (e.g., inverter of PV power source) and their faster recovery when the fault ends.
The most common approaches for FCL development can be categorized into three main groups: superconducting FCL (SFCL), solid-state FCL (SSFCL), and hybrid FCL (HFCL). The main element in the SFCL is the superconductor material. This type of FCL is characterized by near-zero operational power losses and good fault-limiting properties [
10]. However, superconductivity requires a thermal management system and has a higher footprint leading to additional operational costs. The most popular types of SFCL are resistive-type SFCL [
11,
12], inductive-type SFCL [
13,
14], and flux-locked-type SFCL [
15].
The SSFCL is a power electronics-based device designed to operate seamlessly within the existing power system, effectively addressing issues arising from short-circuit faults. The SSFCL continuously monitors system parameters like line current and voltage and dynamically introduces additional impedance into the line when a fault occurs. Recent advancements in semiconductor technology have resulted in fast-responding switching components with higher voltage and current ratings, enabling SSFCLs to integrate into medium- and high-voltage systems and making them economically viable. SSFCLs offer various advantages, including modularity, a flexible structure, and significantly reduced costs compared to SFCLs. Nevertheless, there are several drawbacks. One of the primary drawbacks of FCLs, especially SFCLs, is their high cost [
16]. This includes the initial investment and ongoing costs associated with advanced materials, cooling requirements, and power losses associated with the internal resistance of the components for the non-superconducting FCLs [
17]. Moreover, FCLs can add significant complexity to power systems.
The common types of SSFCLs are switched impedance SSFCL [
18], resonance type SSFCL [
19], and bridge type SSFCL [
20].
The series dynamic braking resistor (SDBR) FCL shown in
Figure 1a represents one of the most widely adopted and straightforward topologies. The SDBR-FCL is comprises a series resistor with a parallel AC switch, implemented by a pair of IGBT transistors [
21]. Under normal operation conditions, the AC switch is activated to bypass the resistor allowing lossless operation. During fault occurrence, the bypass switch is deactivated, forcing the fault current through the limiting resistor. The increased resistance suppresses the rise of fault current and reduces the peak to a maintainable level. SDBR has several advantages such as straightforward design with simple control, high cost-efficiency, and no power losses during normal operation.
Another prevalent topology is the bridge-type FCL (B-FCL) [
22,
23,
24]. The common structure has four diodes forming a bridge-like configuration, creating a rectified voltage at the center, as shown in
Figure 1b. The simplified topology of the bridge-type FCL uses four diodes, and a reactor is placed inside the bridge [
20]. During both operation periods, the current flows through the reactor in the same direction through the entire cycle. As a fault occurs, a rapid increase in fault current is suppressed by the reactor. The advantage is the simple structure combined with the passive current limitation that provides a practical solution. However, the main drawback of this topology is its relatively low current limitation capability, as the fault current will be limited only to several cycles of the fault current until the reactor is fully charged. Moreover, this topology has power losses associated with the reactor’s internal resistance during normal operation. Extended variations of this topology include additional components connected to the bridge part such as reactors and/or resistors, forming a high-impedance path during fault operation of the system [
23,
24,
25].
The resonant FCLs can be divided into three main topologies: series resonance [
26,
27], parallel resonance [
28,
29], and series–parallel resonance FCLs [
30]. The conventional series resonance-based FCL topology is shown in
Figure 1c. This topology has a series resonance between the inductive and capacitive components at the grid’s frequency resulting in almost zero impedance for the series path during normal operation of the system. It allows current to flow through this path without restriction and power losses. In the event of a fault, the operation of the resonance circuit is interrupted when the controller bypasses the capacitor, causing an increase in the total impedance and providing enhanced fault current limitation. The major advantage of the series resonance topology is the simplicity of construction and low price. However, the main disadvantage of the series resonance topology is the current limitation capability only until the reactor is fully charged.
The parallel resonance FCL (PR-FCL) is another approach used to enhance the performance of the B-FCL. This involves introducing a parallel resonance branch, as referenced in [
28]. The standard PR-FCL topology, depicted in
Figure 1d, consists of a bridge-type FCL supplemented with a parallel branch. This branch includes a parallel LC circuit that operates in resonance at the network frequency, creating a path with very high impedance [
29]. During normal operation, the IGBT switch is ON, allowing current to flow through the bridge charging reactor. During a fault condition, the switch is turned OFF to divert the current flow away from the reactor, enabling the current to be shared between the series and parallel branches. This flexibility enables the PR-FCL to adapt to different fault scenarios. However, this approach has several disadvantages. The first drawback is the large oscillations between the inductor and capacitor during transient states, which may affect system stability under fault conditions. Another drawback is that integrating a parallel branch requires additional components to achieve higher current limitation capability.
This paper presents a new improved resonant FCL topology. The main contributions of the proposed LC resonance-based FCL are:
It provides better transient stability than other studied FCLs.
It allows improved fault current suppression and DC-link voltage stabilization.
It reduces the amount of injected power by the PV system during the fault.
It has fewer components compared to standard B-FCL.
It reduces power losses by maintaining near-zero impedance during normal operation.
It provides a passive current limitation, quickly limiting fault current even during the FCL’s response period, eliminating the uncontrolled rise of fault current, and enhancing safety.
Despite all the above-mentioned advantages, the proposed FCL also has a tradeoff: to ensure zero power losses during normal operation, the resonant inductor and capacitor must have precise values that may not be available from the components’ manufacturers.
The rest of the paper is organized as follows:
Section 2 presents the proposed FCL,
Section 3 describes the tested power system,
Section 4 presents the simulation results and their analysis,
Section 5 presents the experimental results, and
Section 6 presents the conclusions and future research.
2. The Proposed FCL Topology and Its Control
The improved configuration of series LC resonance-based FCL is illustrated in
Figure 2. The reactor
is connected in series to the capacitor
and the AC switch, and the limiting resistor
is connected between the reactor and capacitor, in parallel to the capacitor and AC switch. The values of the components were selected to create a series LC resonance at the network frequency as shown in Equation (1). To reduce power losses, the value of the limiting resistor (
) should have a relatively high resistance.
During normal operation of the system, the AC switch is set to conduct to allow the resonance state. Consequently, the impedance and power losses in the inductor–capacitor branch approach zero. The relatively high resistance of the parallel resistor constrains the current flow to the resonance branch.
Figure 3 presents the equivalent circuit of the power system with FCL protection. The impedance of the power line during normal operation is given by
while the load impedance is expressed as
The sinusoidal voltage source is given by
).
The total impedance of the power system during normal operation is given by
while the modulus and the angle are
The KVL equation of the power system is given by
where
denotes voltage drop across IGBTs.
Solving (5) leads to the line current calculation
where
denotes the initial condition of the line current and
the initial condition of the time.
In the event of a fault, the current rises rapidly, quickly reaching hazardous levels, which threaten the system. To prevent damage to components, the control system of the FCL must promptly detect the fault development and execute the transition to the current limitation mode. The threshold should be set near the value of the nominal line current as the limited current is targeted to stay at the pre-fault level.
The control unit is continuously monitoring the PCC voltage. In the event of a fault, a sudden voltage drop is caused by a short circuit with low impedance. The controller recognizes the voltage drop exceeding the permitted threshold, forcing the AC switch to open which causes a swift increase in the FCL’s impedance that restricts the rise of fault current. Nevertheless, both the fault detection and the switch have a response time, during which the power system is potentially vulnerable to damage. Throughout this response period, the rise of the fault current is suppressed only by the reactor until the controller activates the AC switch.
Implementing fast and accurate fault detection and classification algorithms, such as artificial neural networks and machine learning models, may reduce detection time [
31,
32]. However, large-scale deployment of these solutions is challenging due to data requirements, computational complexity, and cost. Another solution is using new gallium nitride (GaN) and silicon carbide (SiC) MOSFET technologies which are now available, with ultrafast switch response times of around 25–30 ns, allowing further reduction in response time [
33,
34]. In the experimental setup, we used silicon carbide (SiC) MOSFETs with ultrafast (22 ns) response time. This response time is so fast that the fault current cannot gain high values—the fault current rising rate is not high enough.
Following the activation of the AC switch, the flow of the fault current is redirected to the high-impedance pathway composed of and , restricting the fault current with better efficiency.
The FCL impedance in fault operation is given by
where
The KVL equation of the studied power system during fault operation is
Consequently, the fault current can be calculated by
where
and
are initial conditions of the fault current and time, respectively.
Figure 4 depicts the block diagram of the fault detection method and control scheme of the FCLs. The control unit transforms the three-phase values of the PCC voltage into the dq reference frame. The threshold voltage
value is set to 0.9 pu. Following this,
is subtracted from
, resulting in a positive value during normal system operation and a negative value during a fault. This signal serves as the gate control signal for the IGBT-based AC switch within the control unit. Employing the
dq0 transformation results in better tracking and stable fault detection than the direct monitoring of the three-phase voltage [
35,
36].
4. Simulation Results
The transient stability of the PV farm was evaluated based on DC-link voltage fluctuations, fault current magnitude, PCC voltage sags, and the amount of injected active and reactive power. In this simulation, two fault scenarios were considered. In the first scenario, the fault resistance (Rf) was set at 7.5 Ω, in the second scenario, it was set at 5 Ω. In all simulated cases, a three-phase to-ground fault was applied. The fault was located between the PCC and the circuit breaker of a load branch, as shown in
Figure 5. The transient stability analysis was performed for the fault operation period, starting at 2.5 s and ending when the circuit breaker tripped at 2.56 s for all studied cases. Therefore, the fault period is defined as
. The duration of the return-to-normal operation is defined as the period it takes for the power system parameters to return to pre-fault values. Therefore, the return-to-normal period is defined as
.
The simulation results for the tested fault scenarios with all examined parameters are displayed in
Figure 5,
Figure 6,
Figure 7,
Figure 8 and
Figure 9. The evaluated stability index values for all studied cases are summarized in
Table 2 and
Table 3. The evaluated parameters are represented in the per-unit system to normalize these quantities.
Table 2 shows the evaluated stability index values for all studied cases with a three-phase to-ground fault with a resistance of 7.5 Ω.
The simulation results of DC-link voltages for all studied cases are presented in
Figure 6. Throughout the fault period, there is a rise in the DC-link voltage. The proposed FCL, SDBR-FCL, and B-FCLs had the most effective limitation of the voltage rise, suppressing it to 1.04 pu and quickly stabilizing at the pre-fault level. The PR-FCL limited the voltage spike to 1.09 pu, while the SR-FCL was slightly worse, restricting the spike to 1.10 pu. Both SR- and PR-FCLs struggled to maintain the voltage at the pre-fault level. Furthermore, the proposed FCL, SDBR-, and B-FCLs operated with the best transient stability index of 0.07. The PR-FCL performed significantly worse with a transient stability index of 0.35. The worst result of 0.41 was obtained with SR-FCL (see
Table 2). For reference, the non-protected system had the highest index of 0.48 indicating the lowest stability.
Regarding the return-to-normal period, the proposed FCL showed superior performance compared to other FCLs, having a voltage sag of only 0.98 pu with minimal fluctuations and a stability index of 0.06. The SDBR- and B-FCLs showed nearly identical performance, with the voltage sag down to 0.97 pu and stability indexes of 0.08. The three FCLs reached stabilization near the 2.61 s time point. Oppositely, the PR-FCL and SR-FCL demonstrated worse performance with stability indexes of 0.53 and 0.42, and voltage sags dropping to 0.82 pu and 0.79 pu, respectively. Notably, substantial fluctuations persisted throughout the period, ultimately stabilizing later at 2.68 s. The system without FCL experienced a voltage spike up to 1.12 pu during the fault period and for the recovery period sagged as deep as 0.78 pu and stabilized at the 2.7 s time point, with a stability index of 0.61.
The fault currents for all cases are shown in
Figure 7. During the fault period, the proposed FCL restricts the fault current spike to 1.5 pu, stabilizing at 1.28 pu, performing similarly to SDBR-FCL and B-FCL, which is the most effective performance among the compared FCLs. In contrast, PR- and SR-FCLs performed significantly worse, struggling to limit the initial fault current spike, peaking at 1.64 pu and 1.63 pu, only slightly lower than the system without FCL, which peaked at 1.64 pu. The examination of stability indexes draws a similar picture, as the SDBR-FCL and the B-FCL excelled with a stability index of 1.86, while the proposed FCL showed an insignificant difference and achieved an index of 1.87. The PR-FCL and SR-FCL were the least effective with stability indexes of 2.91 and 2.93, respectively, while the stability index of the system without FCL was 2.99.
During the return period starting at 2.56 s, the current fluctuates before stabilizing at the pre-fault levels. The proposed FCL shows superior performance among the tested FCLs, reaching a peak current of 1.33 pu and a dip of 0.94 pu and quickly stabilizing at time 2.62 s to pre-fault level, achieving a stability index of 1.07. The SDBR-FCL and B-FCL performed less effectively, peaking at 1.43 pu for the SDBR-FCL and 1.44 pu for the B-FCL, followed by sagging to 0.93 pu with worse stability indexes of 1.28 and 1.26, respectively. The PR- and SR-FCLs had the weakest performance, peaking at 1.35 pu and 1.4 pu, sagging to 0.69 pu and 0.62 pu, and stabilizing at 2.63 s and 2.64 s, with stability indexes of 2.11 and 2.42, respectively. The unprotected system had the deepest sag among the tested cases, down to 0.61 pu, and a stability index of 2.62.
The active power simulations are shown in
Figure 8. During the fault period, the proposed FCL, B-FCL, and SDBR-FCL effectively limit the drop in active power to 0.93 pu. Considering the stability indexes, the proposed FCL outperforms the other FCLs, providing a slight advantage with an index of 0.19 compared to the identical stability index of 0.20 for the other two cases. The SR-FCL performed slightly worse, allowing a larger drop in power to 0.79 pu, leading to an increased stability index value of 0.35. The PR-FCL provided the least effective performance due to a large power drop of 0.77 pu, leading to the worst stability index of 0.36. At the same time, the system without FCL experienced a power drop of 0.74 pu and a stability index of 0.55. During the return period, the proposed FCL offers superior transient stability in terms of active power with an index of 0.17, peaking at 1.07 pu and the lowest sag at 0.96 pu, minimal fluctuations, and quick stabilization to the pre-fault level at 2.62 s. The SDBR-FCL and B-FCL performance was slightly worse with indexes of 0.28 and 0.25, peaking at 1.10 pu and 1.09 pu, and dipping down to 0.94 pu and 0.95 pu, respectively. Both FCLs stabilized at the pre-fault level at the 2.625 s time point. Once more, the PR- and SR-FCLs demonstrate poor performance, with significant fluctuations during the entire period, peaking at 1.24 pu and 1.23 pu, which is worse than the system without an FCL with a peak of 1.2 pu. Similarly, both cases show deep sags of 0.68 pu and 0.61 pu, stabilizing relatively late at 2.64 s and 2.65 s, resulting in stability indexes of 0.91 and 1.19, respectively. The stability index of the system without FCL is 1.17.
Reactive power simulation results are detailed in
Figure 9. During the fault period, the proposed FCL limited the sag in reactive power to −4.2 pu, achieving the best stability index of 10.95 among the tested FCLs. The PR-FCL and SR-FCL showed slightly inferior performance, limiting the drop to −4.5 pu with a stability index of 11.78 and 11.81, respectively. The worst outcomes were observed with the SDBR- and B-FCLs, which allowed a deeper drop in reactive power to −4.6 pu contributing to the worst stability indexes of 11.86 and 11.87. The system without an FCL experienced the deepest drop to −4.9 pu with a stability index of 13.07.
During the return period, the proposed FCL performed best in terms of limiting the reactive power spike to 8.4 pu. The SR-FCL and PR-FCL have a slightly worse performance due to higher peaks of 9.0 pu and 8.9 pu but stabilize quickly. The worst performance is observed with the SDBR- and B-FCLs, which limit the peak of reactive power to 9.5 pu and 9.6 pu, respectively. The examination of stability indexes confirmed the superior performance of the proposed FCL with a stability index of 29.81, followed closely by the SR-FCL at 29.91. The PR-FCL, B-FCL, and SDBR-FCL had worse performance, with stability indexes of 31.28, 32.75, and 33.02, respectively, marking the SDBR as the worst case. Without an FCL, the system peaked at 9.8 pu with a stability index of 31.85. The stabilization for all examined cases occurred nearly simultaneously, at the time point of 2.68 s.
The behavior of PCC voltage during fault and recovery periods is depicted in
Figure 10. The SDBR-FCL and B-FCL exhibit the most effective performance, limiting the voltage dip to 0.72 pu and stabilizing at 0.77 pu, with transient stability indexes of 1.29 for the SDBR-FCL and 1.28 for the B-FCL. The system equipped with the proposed FCL had a slightly less effective performance; the voltage sag is limited to 0.71 pu and recovers gradually to 0.77 pu, resulting in a stability index of 1.33. For systems with PR-FCL and SR-FCL, the voltage sag worsens to 0.57 pu, the poorest result among the cases compared; however, they gradually recover to 0.65 pu and 0.64 pu for PR-FCL and SR-FCL, respectively, with stability indexes of 1.93 and 2.00.
During the return period, the proposed FCL performed similarly to the SDBR-FCL and B-FCL, demonstrating the most effective performance with the quickest recovery, achieving a stability index of 0.41. The PR-FCL and SR-FCL displayed significant performance declines, each securing a stability index of 0.54, with the SR-FCL being the least effective FCL, particularly in voltage stability. For comparison, the system without any FCL achieved a transient stability index of 0.61 for this period.
Compared to the SDBR-FCL, during the first fault scenario, the proposed FCL outperformed and showed significantly better results for all tested parameters during the return period, with the most significant advantages observed for DC-link voltage, current, active power, and reactive power parameters. During the fault period, the proposed FCL achieved better transient stability indexes for active power and reactive power. Moreover, both proposed and SDBR-FCLs showed the best performance in DC-link voltage recovery. However, the SDBR-FCL had insignificantly better performance in only one test: the PCC voltage drop during the fault period.
Similar outcomes were observed when compared to the B-FCL. In the first fault scenario, the proposed FCL outperformed the B-FCL, showing significantly better results for all tested parameters during the return period, with notable advantages in DC-link voltage, current, active power, and reactive power. During the fault period, the proposed FCL achieved better transient stability indexes for active power and reactive power parameters. Both FCLs excelled in DC-link voltage recovery. However, the B-FCL had a marginally better performance in one test: the PCC voltage drop during the fault period.
A comparison of the proposed FCL to the SR-FCL and PR-FCL shows that the proposed FCL offers enhanced transient stability of the power system, due to a major performance advantage in every tested parameter in both fault and return periods.
The simulation results for the second tested fault scenario, with a three-phase to-ground fault resistance of 5 Ω, are displayed in
Figure 11,
Figure 12,
Figure 13,
Figure 14 and
Figure 15. The evaluated stability index values for all studied cases for fault resistance of 5 Ω are summarized in
Table 3.
Figure 11 presents the simulation results of DC-link voltages for all studied cases. Throughout the fault period, there was a rise in DC-link voltage. The proposed FCL, SDBR-FCL, and B-FCL effectively limited the voltage rise to 1.08 pu and quickly stabilized it at the pre-fault level. In contrast, the PR-FCL performed significantly worse, limiting the voltage spike to 1.22 pu, while the SR-FCL performed the worst, restricting the spike to 1.24 pu. Both SR- and PR-FCLs struggled to maintain the voltage at the pre-fault level. The proposed FCL, SDBR-FCL, and B-FCL achieved the best transient stability index of 0.27. The PR-FCL had a significantly worse index of 0.92, and the SR-FCL had the worst result with an index of 1.01 (see
Table 3). For reference, the non-protected system had the highest index of 1.03, indicating the lowest transient stability.
Regarding the return to normal period, the proposed FCL and SDBR-FCL demonstrated superior performance compared to other FCLs, showing a voltage sag of only 0.82 pu with minimal fluctuations and the lowest stability index of 0.41. The B-FCL performed similarly, with a voltage sag of 0.83 pu and a transient stability index of 0.44. These three FCLs reached stabilization around the 2.62 s time point. In contrast, the PR-FCL and SR-FCL showed worse performance, with stability indexes of 1.13 and 1.25, and voltage sags dropping to 0.77 pu and 0.76 pu, respectively. Notably, substantial fluctuations persisted throughout the period for both cases, ultimately stabilizing later at 2.71 s. The system without FCL experienced a voltage spike up to 1.12 pu during the fault period and, during the recovery period, sagged as low as 0.76 pu, stabilizing at the 2.72 s time point with a stability index of 1.26.
Figure 12 shows the fault currents for all cases. During the fault period, the proposed FCL restricts the fault current spike to 1.62 pu, performing similarly to the SDBR-FCL and B-FCL, which is the most effective performance among the compared FCLs. In contrast, the PR-FCL and SR-FCL performed significantly worse, struggling to limit the initial fault current spike and peaking at 1.6 pu, only slightly lower than the system without an FCL, which peaked at 1.71 pu. The examination of stability indexes paints a similar picture: the proposed FCL, SDBR-FCL, and B-FCL excelled with a transient stability index of 2.85. The PR-FCL and SR-FCL were the least effective, with stability indexes of 3.14 and 3.15, respectively, while the stability index of the system without an FCL was 3.26.
During the return period, the proposed FCL shows superior performance among the tested FCLs, reaching a peak current of 1.49 pu and a dip of 0.69 pu, and quickly stabilizing at 2.64 s to the pre-fault level, achieving a stability index of 2.37. Despite a smoother recovery at the beginning of the return period, the PR-FCL and SR-FCL performed less effectively, with significant fluctuations and deeper sags of 0.66 pu and 0.67 pu, respectively, resulting in worse stability indexes of 2.42 and 2.48. The SDBR-FCL and B-FCL had the weakest performance, both peaking at 1.59 pu, sagging to 0.69 pu and 0.62 pu, and stabilizing at 2.63 s and 2.64 s, with stability indexes of 2.55 and 2.59, respectively. The unprotected system had the deepest sag among the tested cases, down to 0.67 pu, with a stability index of 2.55.
The active power simulations are shown in
Figure 13. During the fault period, the proposed FCL, B-FCL, and SDBR-FCL effectively limit the drop in active power to 0.82 pu. Considering the stability indexes, the proposed FCL outperforms the other FCLs, providing a slight advantage with an index of 0.29 compared to the identical stability index of 0.31 for the other two cases. The PR-FCL performed significantly worse, allowing a larger drop in power to 0.57 pu, leading to an increased transient stability index of 1.38. The SR-FCL provided the least effective performance due to a large power drop to 0.59 pu, resulting in the worst stability index of 1.39. At the same time, the system without an FCL experienced a power drop to 0.55 pu and a stability index of 1.61.
During the return period, the proposed FCL, the SDBR-FCL, and B-FCLs offer superior transient stability in terms of active power, with a slight advantage to the proposed FCL, which has an index of 1.08 compared to 1.09 for the SDBR-FCL and 1.13 for the B-FCL. Throughout the entire period, all three cases performed similarly and recovered to the pre-fault value at 2.64 s, with the proposed FCL having a minor advantage in terms of peak reduction. The PR- and SR-FCLs demonstrated poor performance, with significant fluctuations throughout the entire period and extended recovery near 2.69 s, resulting in transient stability indexes of 1.93 and 1.98, respectively. The stability index of the system without an FCL is 2.18.
Reactive power simulation results are detailed in
Figure 14. During the fault period, the proposed FCL limited the sag in reactive power to −4.3 pu, achieving the best stability index of 12.67 among the tested FCLs. The PR-FCL and SR-FCL showed slightly inferior performance, limiting the drop to −4.4 pu, with transient stability indexes of 12.99 and 13.22, respectively. The worst outcomes were observed with the SDBR- and B-FCLs, which allowed a deeper drop in reactive power to −4.8 pu, contributing to the worst stability indexes of 13.96 and 13.93, respectively. The system without an FCL experienced the deepest drop to −4.82 pu, with a transient stability index of 14.59.
During the return period, the proposed FCL performed best in terms of transient stability, with a peak of 10.85 pu and a smooth recovery curve, resulting in a transient stability index of 36.03. The SDBR- and B-FCLs performed closely behind, with peaks of 11.92 pu and transient stability indexes of 38.86 and 38.71, respectively. All three cases recovered to the pre-fault level at 2.69 s. Despite having significantly lower peaks of 9.6 pu, the SR-FCL and PR-FCL recovered relatively late at 2.75 s with fluctuations, resulting in higher transient stability indexes of 43.26 for the PR-FCL and 47.18 for the SR-FCL. For comparison, the system without any FCL showed even more fluctuations and received a transient stability index of 51.25.
Figure 15 depicts the PCC voltage during fault and recovery periods. The SDBR-FCL and B-FCL exhibit the most effective performance, limiting the voltage dip to 0.61 pu and stabilizing at 0.66 pu, with transient stability indexes of 1.85 for the SDBR-FCL and 1.84 for the B-FCL. The system equipped with the proposed FCL had slightly less effective performance; the voltage sag was limited to 0.59 pu and gradually recovered to 0.66 pu, resulting in an increased transient stability index of 1.90. For systems protected with PR-FCL and SR-FCL, the voltage sag worsened to 0.45 pu, like the non-protected system, achieving the poorest results among the cases compared. However, they gradually recovered to 0.52 pu and 0.50 pu for PR-FCL and SR-FCL, respectively, with stability indexes of 2.68 and 2.69. The non-protected system achieved an index of 2.77.
During the return period, the proposed FCL performed similarly to the B-FCL, both demonstrating the most effective performance with the quickest recovery, achieving a stability index of 0.53. The SDBR-FCL showed very close performance, achieving a transient stability index of 0.54. The PR-FCL and SR-FCL displayed significant performance declines with longer recovery times, securing transient stability indexes of 0.72 and 0.74, respectively, with the SR-FCL being the least effective. For comparison, the system without any FCL achieved a transient stability index of 0.80 for this period.
In the second fault scenario, the same tendency was observed as in the first fault scenario: during the return period, the proposed FCL had a performance advantage over the SDBR-FCL in current, active power, reactive power, and PCC voltage recovery. For the rest of the parameters, both FCLs had nearly identical performance in current and DC-link voltage parameters. The SDBR-FCL had no advantages over the proposed FCL during the return period. Regarding the fault period, the proposed FCL had a significant performance advantage in the active power and reactive power parameters. Both the SDBR-FCL and the proposed FCL achieved the best performance for the current and DC-link parameters during this period. However, the SDBR-FCL had a slight advantage over the proposed FCL in terms of PCC voltage recovery.
The proposed FCL demonstrated a performance advantage over the B-FCL, during the return period, in DC-link voltage, current, active power, and reactive power. Both FCLs performed identically in current and PCC voltage, showing the best transient stability in these tests. The B-FCL had no advantages over the proposed FCL during the recovery period. Considering the fault period, the proposed FCL had a significant performance advantage in active power and reactive power parameters. Both FCLs performed best in current and DC-link parameters during this period. However, the B-FCL had a slight advantage over the proposed FCL in the PCC voltage parameter.
Similarly to the first fault scenario, the proposed FCL offers enhanced transient stability compared to the SR-FCL and PR-FCL, demonstrating a major performance advantage in every tested parameter for both fault and return periods.