Impact of Electric Vehicles on Energy Efficiency with Energy Boosters in Coordination for Sustainable Energy in Smart Cities
Abstract
:1. Introduction
2. Mathematical Formulations for Energy Efficiency
2.1. Problem Formulation
- a.
- Active and reactive power limit: The algebraic sum of all the generations, power demands, and power losses should be zero, and it is defined as:
- b.
- Voltage limit: The PEBs and AEBs are responsible for improving the system voltage profile. However, PEBs can improve up to a certain extent, whereas AEBs can improve the voltage profile even beyond 1.0 pu. Therefore, voltage limit restrains the overcompensation due to AEBs, and it is defined in (4):
- c.
- Capacity limit: In power distribution, the lines have their capacity to transfer power and, hence, the loadability. The line capacity is usually evaluated with current limits, and the maximum load that can be connected at a particular node is defined with kVA loading. These limits are described in (5).
- d.
- Network radiality limit: A distribution system is generally operated as radial to coordinate protecting devices. The branches are arranged in a downward stream. In a set of branches, the index value kij is equal to ‘1′ for all connected branches between the ‘ith’ and ‘jth’ nodes; otherwise, it is zero if that branch is considered as a tie-line in the configuration. In a radial network,
- e.
- State of charge limit: An energy storage system (ESS) in electrical power distribution can work as a load, as well as an energy resource, depending on its state of charge during operation. ESS below its lower limit of SOC tends to work as load, whereas it can meet load demand under peak loading conditions when SOC is above the prescribed limit.
- f.
- AEB’s limit: The external DGs are the source of AEBs. If AEBs are operated below their minimum prescribed limit, they become uneconomical. The lower limit is taken as 0.3 times of its full capacity in this work. Therefore, the following limits are imposed for AEBs for the energy-efficient operation of the power system.
2.2. Energy Efficiency Analysis
2.3. Load Representation and Modeling
- Load model-1 (LM-1): In LM-1, the load at each node is considered to be a constant power type and represented as
- b.
- Load model-2 (LM-2): In LM-2, the loads are considered as the combinations of various load types, such as constant power, constant current, and constant impedance loads, and it is represented as
- c.
- Load model-3 (LM-3): In LM-3, the loads are considered as the combinations of various load classes, such as residential, commercial, and industrial loads, and it is represented as
2.4. Probabilistic Loading Patterns (λ) and Cases of Study
2.5. Representation of Energy Storage System
2.6. Margin of Reliability
3. Harmony Search Algorithm
- Initialization of harmony memory
- Improvisation of harmony memory
- Updating the harmony memory
3.1. Harmony Improvisations
3.2. Solution Vector for PEBs
3.3. Solution Vector for AEBs
3.4. Solution Vector for PEBs and AEBs in Coordination
4. Proposed Algorithm and Flowchart
- Step-1:
- Read the line and load data.
- Step-2:
- Set LMs, PLPs, and cases of study
- Step-3:
- Run the load flow for initial configuration and save the result as reference.
- Step-4:
- Read the HSA parameters and generate HM, as per the solution vector described in Section 3.
- Step-5:
- Set iteration counts = 1.
- Step-6:
- Calculate the solution after each iteration and apply HSA rules for HM improvisation.
- Step-7:
- If the new HM is better than the old, update HM, or else set counts = count + 1.
- Step-8:
- In case-1, consider the following:
- a.
- run the load flow for LM-1, LM-2, and LM-3 under light, normal, and overloading scenario and find optimal configuration.
- b.
- run the load flow for LM-1, LM-2, and LM-3 with 1DG, 2DG, and 3DG allocation in base configuration.
- c.
- run the load flow for LM-1, LM-2, and LM-3 with 1DG, 2DG, and 3DG allocation in optimal configuration, which is obtained in (a).
- Step-9:
- In case-2, consider the following:
- a.
- run the load flow for LM-1 under normal loading scenario for 0%, 25%, and 50% SOC, with 1EV, 2EV, 3EV, and 4EVs as a load and find optimal configuration.
- b.
- run the load flow individually for LM-2 and 3 under normal loading scenario for PLP-1, PLP-2, and PLP-3, with 1EV, 2EV, 3EV, and 4EVs as a load and find optimal configuration.
- Step-10:
- In case-3, consider the following;
- a.
- run the load flow for LM-1 under normal loading scenario for 0%, 25%, and 50% SOC, with 1EV, 2EV, 3EV, and 4EVs as a source and find optimal configuration.
- b.
- run the load flow individually for LM-2 and 3 under normal loading scenario for PLP-1, PLP-2, and PLP-3, with 1EV, 2EV, 3EV, and 4EVs as a source and find optimal configuration.
- Step-11:
- In case-4, consider the following;
- a.
- run the load flow for LM-1 under normal loading scenario for 0%, 25%, and 50% SOC, with 1EV, 2EV, 3EV, and 4EVs as a load, at the most occurred location obtained in case 2 and 3, and find optimal configuration and DG allocation in coordination.
- b.
- run the load flow individually for LM-2 and 3 under normal loading scenario for PLP-1, PLP-2, and PLP-3, with 1EV, 2EV, 3EV, and 4EVs as a load, at the most occurred location obtained in case 2 and 3, and find optimal configuration and DG allocation in coordination.
- Step-12:
- In case-5, consider the following;
- a.
- run the load flow for LM-1 under normal loading scenario for 0%, 25%, and 50% SOC, with 1EV, 2EV, 3EV, and 4EVs as a source, at the most occurred location obtained in case 2 and 3, and find optimal configuration and DG allocation in coordination.
- b.
- run the load flow individually for LM-2 and 3 under normal loading scenario for PLP-1, PLP-2, and PLP-3, with 1EV, 2EV, 3EV, and 4EVs as a source, at the most occurred location obtained in case 2 and 3, and find optimal configuration and DG allocation in coordination.
- Step-13:
- Print the EEP under different LMs for different SOC, PLP, EVs, and DG allocations, as the case may be, of energy efficient configuration.
5. Test System, Assumptions and Cases of Study
5.1. Test System
5.2. Assumptions
- (a)
- The substation can meet the power demand of the system
- (b)
- The maximum voltage at the substation is 1.0 pu.
- (c)
- The minimum and maximum voltage, at respective nodes, are 0.90 pu and 1.05 pu.
- (d)
- The maximum capacity of a single AEB is 1 MW at one location.
- (e)
- The switching loss is negligible.
- (f)
- The appropriate size of AEBs is available at the optimal location and can operate at their maximum capacity.
5.3. Energy Efficiency Analysis under Different Cases of Study
6. Test Results and Discussions
6.1. Case-1: EEP Realization in Original and Reconfigured Topology (without ESS)
6.2. Case-2: EEP Realization with PEBs (ESS Works as a Load)
6.3. Case-3: EEP Realization with PEBs (ESS Works as a Source)
6.4. Case-4: EEP Realization with PEBs and AEBs in Coordination (ESS Works as a Load)
6.5. Case-5: EEP Realization with PEBs and AEBs in Coordination (ESS Works as Source)
6.6. Comparative Analysis of EEP with PEBs and AEBs across All the Cases
7. Conclusions
Author Contributions
Funding
Institutional Review Board Statement
Informed Consent Statement
Data Availability Statement
Conflicts of Interest
References
- Kumar, P.; Thanki, D.V.; Singh, S.; Nikolovski, S. A new framework for intensification of energy efficiency in commercial and residential use by imposing social, technical and environmental constraints. Sustain. Cities Soc. 2020, 62, 102400. [Google Scholar] [CrossRef]
- Ali, I.; Thomas, M.S.; Kumar, P. Energy efficient reconfiguration for practical load combinations in distribution systems. IET Gener. Transm. Distrib. 2015, 9, 1051–1060. [Google Scholar] [CrossRef]
- Kumar, P.; Ali, I.; Thomas, M.S.; Singh, S. Imposing voltage security and network radiality for reconfiguration of distribution systems using efficient heuristic and meta-heuristic approach. IET Gener. Transm. Distrib. 2017, 11, 2457–2467. [Google Scholar] [CrossRef]
- Kumar, P.; Ali, I.; Thomas, M.S.; Singh, S. A coordinated framework of dg allocation and operating strategy in distribution system for configuration management under varying loading patterns. Electr. Power Compon. Syst. 2020, 48, 12–29. [Google Scholar] [CrossRef]
- Wang, K.; Li, H.; Maharjan, S.; Zhang, Y.; Guo, S. Green energy scheduling for demand side management in the smart grid. IEEE Trans. Green Commun. Netw. 2018, 2, 596–611. [Google Scholar] [CrossRef]
- Haseeb, M.; Kazmi, S.A.; Malik, M.M.; Ali, S.; Bukhari, S.B.; Shin, D.R. Multi objective based framework for energy management of smart micro-grid. IEEE Access 2020, 8, 220302–220319. [Google Scholar] [CrossRef]
- Kumar, P.; Singh, S.; Ali, I.; Ustun, T.S. Handbook of Research on Power and Energy System Optimization. In 2018 IGI Global, Engineering Science Reference; IGI Global: Hershey, PA, USA, 2018. [Google Scholar]
- Cao, B.; Dong, W.; Lv, Z.; Gu, Y.; Singh, S.; Kumar, P. Hybrid microgrid many-objective sizing optimization with fuzzy decision. IEEE Trans. Fuzzy Syst. 2020, 28, 2702–2710. [Google Scholar] [CrossRef]
- Zhang, K.; Yu, J.; Ren, Y. Demand side management of energy consumption in a photovoltaic integrated greenhouse. Int. J. Electr. Power Energy Syst. 2022, 134, 107433. [Google Scholar] [CrossRef]
- Kumar, P.; Brar, G.S.; Singh, S.; Nikolovski, S.; Baghaee, H.R.; Balkić, Z. Perspectives and intensification of energy efficiency in commercial and residential buildings using strategic auditing and demand-side management. Energies 2019, 12, 4539. [Google Scholar] [CrossRef]
- Asrari, A.; Wu, T.; Lotfifard, S. The impacts of distributed energy sources on distribution network reconfiguration. IEEE Trans. Energy Convers. 2016, 31, 606–613. [Google Scholar] [CrossRef]
- Dorostkar, G.M.R.; Fotuhi, F.M.; Lehtonen, M.; Safdarian, A. Value of distribution network reconfiguration in presence of renewable energy resources. IEEE Trans. Power Syst. 2015, 31, 1879–1888. [Google Scholar] [CrossRef]
- Kavousi, F.A.; Rostami, M.A.; Niknam, T. Reliability-oriented reconfiguration of vehicle-to-grid networks. IEEE Trans. Ind. Inform. 2015, 11, 682–691. [Google Scholar] [CrossRef]
- Xing, H.; Sun, X. Distributed generation locating and sizing in active distribution network considering network reconfiguration. IEEE Access 2017, 5, 14768–14774. [Google Scholar] [CrossRef]
- Fu, Y.Y.; Chiang, H.D. Toward optimal multiperiod network reconfiguration for increasing the hosting capacity of distribution networks. IEEE Trans Power Deliv. 2018, 33, 2294–2304. [Google Scholar] [CrossRef]
- Azizivahed, A.; Arefi, A.; Ghavidel, S.; Shafie, K.M.; Li, L.; Zhang, J.; Catalão, J.P. Energy management strategy in dynamic distribution network reconfiguration considering renewable energy resources and storage. IEEE Trans. Sustain. Energy 2019, 11, 662–673. [Google Scholar] [CrossRef]
- Liu, Y.; Li, J.; Wu, L. Coordinated optimal network reconfiguration and voltage regulator/DER control for unbalanced distribution systems. IEEE Trans. Smart Grid 2018, 10, 2912–2922. [Google Scholar] [CrossRef]
- Song, Y.; Zheng, Y.; Liu, T.; Lei, S.; Hill, D.J. A new formulation of distribution network reconfiguration for reducing the voltage volatility induced by distributed generation. IEEE Trans. Power Syst. 2019, 35, 496–507. [Google Scholar] [CrossRef]
- Nick, M.; Cherkaoui, R.; Paolone, M. Optimal planning of distributed energy storage systems in active distribution networks embedding grid reconfiguration. IEEE Trans. Power Syst. 2017, 33, 1577–1590. [Google Scholar] [CrossRef]
- Naguib, M.; Omran, W.A.; Talaat, H.E. Performance Enhancement of Distribution Systems via Distribution Network Reconfiguration and Distributed Generator Allocation Considering Uncertain Environment. J. Mod. Power Syst. Clean Energy 2021, 10, 647–655. [Google Scholar] [CrossRef]
- Cattani, I.B.; Chaparro, E.; Barán, B. Distribution system operation and expansion planning using network reconfiguration. IEEE Lat. Am. Trans. 2020, 18, 845–852. [Google Scholar] [CrossRef]
- Ahmed, H.M.; Salama, M.M. Energy management of AC–DC hybrid distribution systems considering network reconfiguration. IEEE Trans. Power Syst. 2019, 34, 4583–4594. [Google Scholar] [CrossRef]
- Takenobu, Y.; Yasuda, N.; Kawano, S.; Minato, S.I.; Hayashi, Y. Evaluation of annual energy loss reduction based on reconfiguration scheduling. IEEE Trans. Smart Grid 2016, 9, 1986–1996. [Google Scholar] [CrossRef]
- Asrari, A.; Ansari, M.; Khazaei, J.; Fajri, P.; Amini, M.H.; Ramos, B. The impacts of a decision making framework on distribution network reconfiguration. IEEE Trans. Sustain. Energy 2020, 12, 634–645. [Google Scholar] [CrossRef]
- Huang, W.; Zheng, W.; Hill, D.J. Distribution network reconfiguration for short-term voltage stability enhancement: An efficient deep learning approach. IEEE Trans. Smart Grid 2021, 12, 5385–5395. [Google Scholar] [CrossRef]
- Zhan, J.; Liu, W.; Chung, C.Y.; Yang, J. Switch opening and exchange method for stochastic distribution network reconfiguration. IEEE Trans. Smart Grid 2020, 11, 2995–3007. [Google Scholar] [CrossRef]
- Gao, H.; Ma, W.; Xiang, Y.; Tang, Z.; Xu, X.; Pan, H.; Zhang, F.; Liu, J. Multi-Objective Dynamic Reconfiguration for Urban Distribution Network Considering Multi-Level Switching Modes. J. Mod. Power Syst. Clean Energy 2021, 1–14. [Google Scholar] [CrossRef]
- Rawat, M.S.; Vadhera, S. Heuristic optimization techniques for voltage stability enhancement of radial distribution network with simultaneous consideration of network reconfiguration and DG sizing and allocations. Turk. J. Electr. Eng. Comput. Sci. 2019, 27, 330–345. [Google Scholar] [CrossRef]
- Rao, R.S.; Ravindra, K.; Satish, K.; Narasimham, S.V. Power loss minimization in distribution system using network reconfiguration in the presence of distributed generation. IEEE Trans. Power Syst. 2012, 28, 317–325. [Google Scholar] [CrossRef]
- Esmaeilian, H.R.; Fadaeinedjad, R. Energy loss minimization in distribution systems utilizing an enhanced reconfiguration method integrating distributed generation. IEEE Syst. J. 2014, 9, 1430–1439. [Google Scholar] [CrossRef]
- Wang, B.; Zhang, C.; Dong, Z.Y. Interval optimization based coordination of demand response and battery energy storage system considering SoC management in a microgrid. IEEE Trans. Sustain. Energy 2020, 11, 2922–2931. [Google Scholar] [CrossRef]
- Diab, A.A.; Sultan, H.M.; Mohamed, I.S.; Kuznetsov, O.N.; Do, T.D. Application of different optimization algorithms for optimal sizing of PV/wind/diesel/battery storage stand-alone hybrid microgrid. IEEE Access 2019, 7, 119223–119245. [Google Scholar] [CrossRef]
- Islam, M.M.; Nagrial, M.; Rizk, J.; Hellany, A. Dual stage microgrid energy resource optimization strategy considering renewable and battery storage systems. Int. J. Energy Res. 2021, 45, 21340–21364. [Google Scholar] [CrossRef]
- Faisal, M.; Hannan, M.A.; Ker, P.J.; Hussain, A.; Mansor, M.B.; Blaabjerg, F. Review of energy storage system technologies in microgrid applications: Issues and challenges. IEEE Access 2018, 6, 35143–35164. [Google Scholar] [CrossRef]
- Kumar, P.; Ali, I.; Thomas, M.S. Energy efficiency analysis of reconfigured distribution system for practical loads. Perspect. Sci. 2016, 8, 498–501. [Google Scholar] [CrossRef]
- Geem, Z.W.; Kim, J.H.; Loganathan, G.V. A new heuristic optimization algorithm: Harmony search. Simulation 2001, 76, 60–68. [Google Scholar] [CrossRef]
- Dubey, M.; Kumar, V.; Kaur, M.; Dao, T.P. A systematic review on harmony search algorithm: Theory, literature, and applications. Math. Probl. Eng. 2021, 2021, 5594267. [Google Scholar] [CrossRef]
- Ala’a, A.; Alsewari, A.A.; Alamri, H.S.; Zamli, K.Z. Comprehensive review of the development of the harmony search algorithm and its applications. IEEE Access 2019, 7, 14233–14245. [Google Scholar]
S. No. | Parameters | Significance in EEP |
---|---|---|
1 | kW demand (Psi) | The integration of PEBs and AEBs improves the voltage profile, altering the loading pattern. |
2 | kVAr demand (Qsi) | The reactive power flow in the system directly affects the voltage profile. The higher the reactive power lower will be the voltage and hence the poor energy efficiency. |
3 | kVA demand (Ssi) | The number of customers to be supplied depends upon the kVA rating of transformer at load point. |
4 | Node voltage profile (Vi) | The loads are voltage-dependent, and hence, the voltage profile can alter the loading pattern and the operating efficiency of the connected loads. |
5 | Loadability index (fsi) | Loadability margin limits the maximum number of customers supplied at a particular node. |
6 | Power loss (PL) | PEBs and AEBs reduce the power loss by improving voltage profile and local generation. |
7 | Margin of Reliability (MR) | The reliability of supplying power is influenced by the possible number of consumers, voltage limit, and thermal limit. The PEBs and AEBs improve these aspects and hence the reliability. |
Load Type | Voltage Exponents | Load Class | Voltage Exponents | ||
---|---|---|---|---|---|
α | β | α | β | ||
Constant power | 0 | 0 | Industrial | 0.18 | 6.0 |
Constant current | 1 | 1 | Commercial | 0.99 | 3.5 |
Constant impedance | 2 | 2 | Residential | 1.2 | 2.9 |
LP | LM-2 | LM-3 |
---|---|---|
PLP-1 | ||
PLP-2 | ||
PLP-3 |
Cases | HAS Parameter | Objective Function as Power Loss (kW) | ||
---|---|---|---|---|
HMCR | PAR | HMS | ||
1 | 0.90 | 0.25 | 12 | 147.63 |
0.70 | 0.25 | 12 | 143.44 | |
0.45 | 0.25 | 12 | 144.35 | |
0.35 | 0.25 | 12 | 155.73 | |
2 | 0.85 | 0.35 | 12 | 139.55 |
0.85 | 0.45 | 12 | 140.02 | |
0.85 | 0.55 | 12 | 139.97 | |
0.85 | 0.65 | 12 | 140.65 | |
3 | 0.80 | 0.40 | 5 | 159.81 |
0.80 | 0.40 | 20 | 147.90 | |
0.80 | 0.40 | 25 | 162.68 | |
0.80 | 0.40 | 35 | 163.82 |
Cases | Description | Remarks |
---|---|---|
Case-1 | EEP evaluation of new configuration with PEBs and AEBs exclusively | This allows the EEP evaluation of reconfigured network and AEBs allocation in the original network and reconfigured network under different LMs without ESS. |
Case-2 | EEP evaluation with PEBs | This allows the change in a network topology for single/multi objectives and the EEP evaluation of the resulting configuration under different LMs with ESS as a LOAD. |
Case-3 | EEP evaluation with PEBs | This allows the change in a network topology for single/multi objectives and the EEP evaluation of the resulting configuration under different LMs with ESS as a SOURCE. |
Case-4 | EEP evaluation with PEBs and AEBs in coordination | This allows EEP evaluation in the coordination of PEBs and AEBs for energy-efficient operation under different LMs with ESS as a LOAD. |
Case-5 | EEP evaluation with PEBs and AEBs in coordination | This allows EEP evaluation in the coordination of PEBs and AEBs for energy-efficient operation under different LMs with ESS as a SOURCE. |
A. EEP analysis of reconfigured network | |||||||||
EEP evaluation under LM-1 | EEP evaluation under LM-2 | EEP evaluation under LM-3 | |||||||
Loading scenario | Light | Normal | Over | Light | Normal | Over | Light | Normal | Over |
Optimal Conf | 7, 14, 9, 32, 37 | 7, 14, 9, 32, 37 | 7, 14, 9, 32, 28 | 7, 14, 9, 32, 28 | 7, 14, 9, 32, 37 | 7, 14, 9, 32, 37 | 7, 14, 9, 32, 37 | 7, 14, 9, 32, 37 | 7, 14, 9, 32, 37 |
Vmin | 0.9508 | 0.9378 | 0.9287 | 0.9553 | 0.9410 | 0.9292 | 0.9512 | 0.9384 | 0.9254 |
Fsi,min | 18.53 | 14.73 | 12.20 | 19.11 | 15.32 | 12.80 | 18.63 | 14.84 | 12.31 |
PL, (kW) | 87.59 | 139.55 | 205.62 | 81.86 | 127.47 | 183.59 | 86.43 | 137.20 | 200.80 |
%MR | 1.2812 | 1.2812 | 2.3501 | 2.2355 | 1.1569 | 1.1302 | 1.2622 | 1.2566 | 1.2505 |
B. EEP analysis of original network with DG allocations | |||||||||
EEP evaluation under LM-1 | EEP evaluation under LM-2 | EEP evaluation under LM-3 | |||||||
AEBs scenario | 1DG | 2DG | 3DG | 1DG | 2DG | 3DG | 1DG | 2DG | 3DG |
OriginalConf | 33, 34, 35, 36, 37 | 33, 34, 35, 36, 37 | 33, 34, 35, 36, 37 | 33, 34, 35, 36, 37 | 33, 34, 35, 36, 37 | 33, 34, 35, 36, 37 | 33, 34, 35, 36, 37 | 33, 34, 35, 36, 37 | 33, 34, 35, 36, 37 |
DG size (Node) | 1975 (7) | 1078 (11) 1032 (30) | 945 (30) 796 (25) 716 (14) | 1976 (7) | 1304 (30) 780 (13) | 882 (10) 943 (30) 868 (24) | 2190 (7) | 1138 (29) 779 (14) | 765 (25) 726 (14) 952 (30) |
Vmin | 0.9450 | 0.9673 | 0.9629 | 0.9472 | 0.9708 | 0.9620 | 0.9515 | 0.9659 | 0.9658 |
Fsi,min | 22.13 | 29.29 | 25.26 | 22.83 | 29.36 | 27.03 | 23.35 | 29.08 | 26.87 |
PL, (kW) | 108.31 | 86.24 | 73.49 | 102.50 | 85.51 | 72.87 | 97.88 | 81.11 | 68.50 |
%MR | -- | -- | -- | −0.0420 | −0.0302 | −0.0178 | −0.0765 | −0.1250 | −0.1327 |
C. EEP analysis of reconfigured network with DG allocations | |||||||||
EEP evaluation under LM-1 | EEP evaluation under LM-2 | EEP evaluation under LM-3 | |||||||
AEBs scenario | 1DG | 2DG | 3DG | 1DG | 2DG | 3DG | 1DG | 2DG | 3DG |
Optimal Conf | 7, 14, 9, 32, 37 | 7, 14, 9, 32, 37 | 7, 14, 9, 32, 28 | 7, 14, 9, 32, 28 | 7, 14, 9, 32, 37 | 7, 14, 9, 32, 37 | 7, 14, 9, 32, 37 | 7, 14, 9, 32, 37 | 7, 14, 9, 32, 37 |
DG size (Node) | 1030 (30) | 881 (9) 1080 (29) | 944 (30) 963 (8) 855 (24) | 1571(25) | 1693 (25) 865 (8) | 861 (9) 792 (30) 879 (24) | 1570 (25) | 907 (8) 1372 (25) | 903 (24) 759 (30) 811 (8) |
Vmin | 0.9478 | 0.9707 | 0.9732 | 0.9489 | 0.9725 | 0.9732 | 0.9507 | 0.9694 | 0.9720 |
Fsi,min | 14.75 | 30.08 | 32.53 | 14.94 | 30.13 | 29.64 | 15.42 | 32.24 | 29.43 |
PL, (kW) | 98.19 | 73.54 | 59.46 | 85.70 | 61.86 | 59.28 | 81.58 | 60.06 | 56.45 |
%MR | −0.8123 | −0.8123 | −0.8123 | −0.7195 | −0.7468 | −0.7103 | −0.7716 | −0.8404 | −0.8292 |
A. EEP evaluation under LM-1 | ||||||||||||
With SOC | With 1EV Station | With 2EV Station | With 3EV Station | With 4EV Station | ||||||||
0% | 25% | 50% | 0% | 25% | 50% | 0% | 25% | 50% | 0% | 25% | 50% | |
Optimal EVS (Location) | 24 | 2 | 5 | 5, 2 | 27, 2 | 10, 19 | 23, 5, 2 | 30, 6, 2 | 24, 2, 19 | 18, 5, 19, 2 | 19, 4, 28, 13 | 13, 23, 2, 28 |
Optimal Conf | 7, 14, 10, 32, 37 | 7, 13, 9, 36, 28 | 7, 14, 9, 32, 37 | 7, 14, 10, 32, 28 | 7, 13, 9, 32, 28 | 7, 14, 9, 32, 28 | 6, 14, 10, 36, 37 | 7, 14, 10, 36,28 | 7, 14, 9, 36, 37 | 7, 34, 10, 17, 28 | 7, 14, 10, 36, 28 | 7, 34, 10, 36, 28 |
Vmin | 0.9370 | 0.9377 | 0.9369 | 0.9403 | 0.9402 | 0.9411 | 0.9336 | 0.9327 | 0.9330 | 0.9226 | 0.9354 | 0.9360 |
Fsi,min | 14.72 | 15.58 | 14.73 | 14.71 | 14.68 | 13.83 | 13.19 | 15.26 | 15.62 | 14.24 | 13.80 | 14.54 |
PL, (kW) | 148.10 | 145.29 | 143.01 | 147.77 | 149.81 | 147.01 | 162.97 | 164.78 | 148.31 | 183.94 | 174.35 | 163.09 |
%MR | −1.0526 | −0.6973 | −0.8123 | −0.9409 | −0.7283 | −0.6982 | −1.5227 | −0.9105 | −0.7816 | −0.5477 | −0.9105 | −0.7326 |
B. EEP evaluation under LM-2 | ||||||||||||
With SOC (60–100%) | With 1EV Station | With 2EV Station | With 3EV Station | With 4EV Station | ||||||||
PLP = 1 | PLP = 2 | PLP = 3 | PLP = 1 | PLP = 2 | PLP = 3 | PLP = 1 | PLP = 2 | PLP = 3 | PLP = 1 | PLP = 2 | PLP = 3 | |
Optimal EVS (Location) | 18 | 33 | 32 | 18, 32 | 32, 15 | 15, 31 | 10, 33, 15 | 31, 15, 18 | 16, 15, 18 | 15, 30, 32, 31 | 16, 32, 18, 14 | 32, 30, 18, 14 |
Optimal Conf | 7, 14, 9, 32, 37 | 7, 14, 10, 32, 28 | 7, 14, 9, 31, 28 | 7, 13, 9, 31, 28 | 7, 14, 9, 31, 37 | 7, 14, 9, 30, 37 | 6, 14, 9, 31, 37 | 6, 14, 9, 31, 37 | 7, 13, 10, 30, 37 | 7, 34, 10, 31, 27 | 7, 14, 10, 30, 37 | 7, 13, 9, 30, 37 |
Vmin | 0.9396 | 0.9442 | 0.9460 | 0.9526 | 0.9524 | 0.9446 | 0.9559 | 0.9500 | 0.9440 | 0.9512 | 0.9601 | 0.9553 |
Fsi,min | 16.48 | 17.05 | 17.35 | 17.35 | 16.92 | 15.82 | 17.07 | 17.16 | 17.74 | 17.41 | 20.51 | 18.96 |
PL, (kW) | 124.17 | 118.33 | 104.40 | 103.07 | 100.24 | 92.91 | 87.19 | 91.43 | 87.19 | 82.25 | 80.21 | 74.88 |
%MR | −0.8491 | −1.0015 | −0.7938 | −0.7784 | −0.9003 | −0.6252 | −1.4383 | −1.4025 | −0.9168 | −0.7571 | −0.8689 | −0.6699 |
C. EEP evaluation under LM-3 | ||||||||||||
With SOC (60–100%) | With 1EV Station | With 2EV Station | With 3EV Station | With 4EV Station | ||||||||
PLP = 1 | PLP = 2 | PLP = 3 | PLP = 1 | PLP = 2 | PLP = 3 | PLP = 1 | PLP = 2 | PLP = 3 | PLP = 1 | PLP = 2 | PLP = 3 | |
Optimal EVS (Location) | 31 | 16 | 16 | 30,32 | 29,18 | 15,32 | 18,29,15 | 8,31,33 | 32,30,14 | 30,29, 17,31 | 32,31, 33,25 | 32,30, 16,18 |
Optimal Conf | 7, 14, 9, 36, 37 | 7, 14, 9, 31, 37 | 7, 14, 9, 31, 37 | 7, 14, 9, 31, 28 | 7, 14, 10, 31, 37 | 7, 14, 10, 31, 28 | 7, 14, 9, 31, 37 | 7, 14, 10, 31, 28 | 7, 13, 9, 31, 37 | 7, 14, 9, 30, 28 | 7, 14, 10, 31, 28 | 6, 13, 9, 31, 37 |
Vmin | 0.9441 | 0.9388 | 0.9337 | 0.9437 | 0.9446 | 0.9507 | 0.9542 | 0.9568 | 0.9469 | 0.9479 | 0.9639 | 0.9528 |
Fsi,min | 16.27 | 14.64 | 13.75 | 14.82 | 15.27 | 16.36 | 17.61 | 18.28 | 17.27 | 15.86 | 18.27 | 16.06 |
PL, (kW) | 116.19 | 114.33 | 124.65 | 103.44 | 102.09 | 105.97 | 85.70 | 83.18 | 89.70 | 80.11 | 74.13 | 84.53 |
%MR | −0.8572 | −0.8825 | −0.8515 | −0.7700 | −1.1233 | −0.9918 | −0.9064 | −1.0288 | −0.9881 | −0.4787 | −1.0305 | −1.3883 |
A. EEP evaluation under LM-1 | ||||||||||||
With SOC | With 1EV Station | With 2EV Station | With 3EV Station | With 4EV Station | ||||||||
0% | 25% | 50% | 0% | 25% | 50% | 0% | 25% | 50% | 0% | 25% | 50% | |
Optimal EVS(Location) | 31 | 32 | 33 | 31, 17 | 9, 18 | 29, 32 | 8, 18, 31 | 16, 30, 31 | 17, 31, 32 | 16, 24, 31, 32 | 8, 15, 27, 33 | 17, 18, 28, 33 |
Optimal Conf | 7, 9, 14, 23, 37 | 7, 9, 14, 23, 37 | 7, 9, 14, 23, 37 | 7, 9, 14, 23, 37 | 7, 9, 14, 23, 37 | 7, 9, 14, 32, 37 | 7, 14, 10, 32, 37 | 7, 9, 14, 32, 37 | 7, 9, 14, 28, 32 | 7, 9, 14, 32, 37 | 7, 9, 14, 32, 37 | 7, 9, 14, 32, 37 |
Vmin | 0.9386 | 0.9386 | 0.9378 | 0.9387 | 0.9378 | 0.9390 | 0.9391 | 0.9398 | 0.9429 | 0.9405 | 0.9384 | 0.9385 |
Fsi,min | 14.73 | 14.73 | 14.89 | 15.04 | 15.21 | 14.77 | 15.33 | 15.02 | 15.02 | 14.98 | 15.46 | 15.40 |
PL, (kW) | 137.87 | 138.03 | 138.24 | 135.55 | 136.19 | 136.97 | 133.44 | 133.24 | 133.97 | 131.70 | 133.11 | 133.02 |
%MR | −0.8123 | −0.8123 | −0.8123 | −0.8123 | −0.8123 | −0.8123 | −1.0526 | −0.8123 | −0.6982 | −0.8123 | −0.8123 | −0.8123 |
B. EEP evaluation under LM-2 | ||||||||||||
With SOC (60–100%) | With 1EV Station | With 2EV Station | With 3EV Station | With 4EV Station | ||||||||
PLP = 1 | PLP = 2 | PLP = 3 | PLP = 1 | PLP = 2 | PLP = 3 | PLP = 1 | PLP = 2 | PLP = 3 | PLP = 1 | PLP = 2 | PLP = 3 | |
Optimal EVS (Location) | 12 | 27 | 9 | 15, 31 | 8, 33 | 9, 32 | 15, 17, 32 | 15, 16, 33 | 14, 30, 31 | 8, 10, 29, 32 | 7, 17, 32, 15 | 14, 12, 15, 32 |
Optimal Conf | 7, 9, 14, 32, 37 | 7, 9, 14, 32, 37 | 7, 9, 14, 32, 37 | 7, 9, 14, 32, 37 | 7, 9, 14, 28, 32 | 7, 9, 14, 32, 37 | 7, 9, 14, 32, 37 | 7, 9, 14, 28, 32 | 7, 10, 14, 32, 37 | 7, 9, 14, 32, 37 | 7, 14, 10, 32, 37 | 7, 9, 14, 28, 32 |
Vmin | 0.9386 | 0.9413 | 0.9433 | 0.9394 | 0.9441 | 0.9429 | 0.9396 | 0.9442 | 0.9454 | 0.9416 | 0.9428 | 0.9470 |
Fsi,min | 15.06 | 15.32 | 15.91 | 14.99 | 15.76 | 15.75 | 15.20 | 16.16 | 15.95 | 15.48 | 15.72 | 16.53 |
PL, (kW) | 135.47 | 126.77 | 118.73 | 134.25 | 125.25 | 120.93 | 132.47 | 122.71 | 115.13 | 126.48 | 121.93 | 114.41 |
%MR | −0.8274 | −0.8707 | −0.9091 | −0.8226 | −0.7482 | −0.8912 | −0.8217 | −0.7523 | −1.1480 | −0.8474 | −1.1124 | −0.7822 |
C. EEP evaluation under LM-3 | ||||||||||||
With SOC (60–100%) | With 1EV Station | With 2EV Station | With 3EV Station | With 4EV Station | ||||||||
PLP = 1 | PLP = 2 | PLP = 3 | PLP = 1 | PLP = 2 | PLP = 3 | PLP = 1 | PLP = 2 | PLP = 3 | PLP = 1 | PLP = 2 | PLP = 3 | |
Optimal EVS(Location) | 18 | 32 | 33 | 18,30 | 24,31 | 15,31 | 12,28,29 | 18,30, 33 | 14,31,33 | 16,17, 30, 33 | 30,31, 27,18 | 18,31, 32,33 |
Optimal Conf | 7, 9, 14, 32, 37 | 7, 9, 14, 32, 37 | 7, 9, 14, 32, 37 | 7, 9, 14, 32, 37 | 7, 9, 14, 28, 32 | 7, 9, 14, 28, 32 | 7, 9, 14, 32, 37 | 7, 14, 10, 32, 37 | 7, 9, 14, 32, 37 | 7, 9, 14, 32, 37 | 7, 9, 14, 32, 37 | 7, 14, 10, 32, 37 |
Vmin | 0.9410 | 0.9413 | 0.9393 | 0.9417 | 0.9449 | 0.9427 | 0.9431 | 0.9415 | 0.9397 | 0.9424 | 0.9433 | 0.9405 |
Fsi,min | 15.46 | 15.26 | 15.19 | 15.64 | 15.26 | 15.13 | 15.54 | 15.72 | 15.34 | 16.06 | 15.46 | 15.54 |
PL, (kW) | 126.65 | 127.53 | 132.50 | 123.84 | 126.60 | 133.29 | 121.60 | 124.39 | 131.37 | 119.77 | 121.85 | 128.37 |
%MR | −0.8722 | −0.8660 | −0.8409 | −0.8781 | −0.7413 | −0.7141 | −0.8767 | −1.1081 | −0.8270 | −0.8865 | −0.8723 | −1.0800 |
A. EEP evaluation under LM-1 | ||||||||||||
With SOC | With 1EV Station | With 2EV Station | With 3EV Station | With 4EV Station | ||||||||
0% | 25% | 50% | 0% | 25% | 50% | 0% | 25% | 50% | 0% | 25% | 50% | |
Optimal Conf | 7, 14, 10, 28, 31 | 9, 28, 31, 33, 34 | 7, 9, 13, 28, 31 | 9, 26, 30, 33, 34 | 7, 10, 28, 30, 34 | 7, 9, 13, 28, 36 | 7, 9, 14, 28, 30 | 7, 12, 28, 31, 35 | 7, 13, 28, 32, 35 | 6, 9, 13, 27, 30 | 10, 28, 31, 33, 34 | 10, 14, 28, 31, 33 |
Optimal EVS (Location) | 18 | 18 | 18 | 2, 19 | 2, 19 | 2, 19 | 2, 19, 23 | 2, 19, 23 | 2, 19, 23 | 2, 19, 23, 30 | 2, 19, 23, 30 | 2, 19, 23, 30 |
DG | 691 (33) 428 (12) 877 (25) | 933 (15) 885 (7) 990 (30) | 952 (29) 548 (8) 615 (17) | 890 (17) 568 (7) 923 (25) | 820 (21) 693 (17) 932 (25) | 773 (32) 836 (25) 709 (15) | 612 (13) 795 (33) 867 (25) | 696 (18) 996 (29) 568 (8) | 662 (29) 977 (25) 775 (16) | 778 (18) 975 (29) 797 (7) | 755 (33) 954 (25) 721 (26) | 837 (30) 688 (15) 784 (7) |
Vmin | 0.9684 | 0.9656 | 0.9710 | 0.9599 | 0.9553 | 0.9785 | 0.9732 | 0.9721 | 0.9728 | 0.9681 | 0.9703 | 0.9712 |
Fsi,min | 27.16 | 31.73 | 28.19 | 26.07 | 24.58 | 28.47 | 28.04 | 30.81 | 27.31 | 24.46 | 30.78 | 28.96 |
PL, (kW) | 59.71 | 55.39 | 59.04 | 57.86 | 58.97 | 59.77 | 57.64 | 59.87 | 61.60 | 59.53 | 56.42 | 61.55 |
%MR | −0.9553 | 0.0017 | −0.7455 | 0.2208 | −0.4815 | −0.6964 | −0.4128 | −0.4004 | −0.6657 | −0.9202 | −0.2524 | −0.4389 |
B. EEP evaluation under LM-2 | ||||||||||||
With SOC (60–100%) | With 1EV Station | With 2EV Station | With 3EV Station | With 4EV Station | ||||||||
PLP = 1 | PLP = 2 | PLP = 3 | PLP = 1 | PLP = 2 | PLP = 3 | PLP = 1 | PLP = 2 | PLP = 3 | PLP = 1 | PLP = 2 | PLP = 3 | |
Optimal Conf | 7, 10, 13, 28, 32 | 7, 9, 28, 32, 34 | 9, 14, 28, 30, 33 | 10, 14, 27, 30, 33 | 6, 13, 16, 35,37 | 10, 14, 28, 30, 33 | 9, 14, 28, 30, 33 | 9, 28, 31, 33, 34 | 7, 10, 13, 28, 31 | 7, 9, 13, 32, 37 | 10, 13, 28, 30, 33 | 6, 9, 26, 31, 34 |
Optimal EVS (Location) | 18 | 18 | 18 | 2, 19 | 2, 19 | 2, 19 | 2, 19, 23 | 2, 19, 23 | 2, 19, 23 | 2, 19, 23, 30 | 2, 19, 23, 30 | 2, 19, 23, 30 |
DG | 785 (31) 746 (14) 996 (24) | 662 (31) 816 (24) 826 (14) | 977 (25) 699 (17) 930 (7) | 670 (25) 655 (33) 931 (8) | 963 (30) 996 (8) 955 (24) | 610 (25) 921 (7) 626 (32) | 946 (7) 812 (29) 753 (33) | 890 (4) 914 (30) 787 (17) | 683 (24) 771 (16) 693 (30) | 863 (25) 852 (30) 691 (15) | 625 (18) 925 (29) 601 (8) | 947 (29) 612 (8) 793 (15) |
Vmin | 0.9757 | 0.9745 | 0.9739 | 0.9714 | 0.9660 | 0.9728 | 0.9728 | 0.9722 | 9632 | 0.9699 | 0.9631 | 0.9633 |
Fsi,min | 26.71 | 29.64 | 29.46 | 29.58 | 35.42 | 31.21 | 28.58 | 30.79 | 22.60 | 25.72 | 34.77 | 28.27 |
PL, (kW) | 58.39 | 56.11 | 53.37 | 58.68 | 57.02 | 53.96 | 57.57 | 56.57 | 55.16 | 58.09 | 57.52 | 55.30 |
%MR | −0.9806 | −0.6383 | −0.0501 | −0.1342 | −1.0598 | −0.3125 | 0.1254 | −0.1120 | −1.1570 | −0.8885 | −0.2734 | −1.3336 |
C. EEP evaluation under LM-3 | ||||||||||||
With SOC (60–100%) | With 1EV Station | With 2EV Station | With 3EV Station | With 4EV Station | ||||||||
PLP = 1 | PLP = 2 | PLP = 3 | PLP = 1 | PLP = 2 | PLP = 3 | PLP = 1 | PLP = 2 | PLP = 3 | PLP = 1 | PLP = 2 | PLP = 3 | |
Optimal Conf | 6, 10, 13, 28, 30 | 9, 27, 30, 33, 34 | 7, 13, 26, 32, 35 | 7, 9, 14, 28,30 | 7, 9, 13, 27,30 | 7, 9, 13, 28, 32 | 7,8,28, 32, 34 | 7, 9, 13, 28, 32 | 7, 10, 14, 28,30 | 7,9,12, 28, 31 | 10, 27, 30, 33, 34 | 7, 12, 28, 32, 35 |
Optimal EVS (Location) | 18 | 18 | 18 | 2, 19 | 2, 19 | 2, 19 | 2, 19, 23 | 2, 19, 23 | 2, 19, 23 | 2, 19, 23, 30 | 2, 19, 23, 30 | 2, 19, 23, 30 |
DG | 632 (9) 947 (25) 610 (33) | 957 (25) 920 (8) 741 (18) | 831 (29) 856 (15) 860 (25) | 667 (11) 827 (30) 641 (31) | 735 (12) 797 (32) 984 (25) | 666 (25) 733 (15) 979 (29) | 664 (14) 922 (24) 750 (29) | 745 (9) 848 (24) 807 (29) | 934 (29) 942 (8) 482 (31) | 985 (25) 613 (23) 834 (18) | 984 (18) 749 (25) 889 (7) | 935 (30) 886 (24) 883 (15) |
Vmin | 0.9614 | 0.9579 | 0.9741 | 0.9680 | 0.9717 | 0.9760 | 0.9692 | 0.9687 | 0.9701 | 0.9702 | 0.9732 | 0.9760 |
Fsi,min | 21.05 | 24.21 | 30.09 | 27.42 | 25.60 | 26.51 | 25.80 | 27.51 | 28.95 | 22.80 | 31.06 | 30.57 |
PL (kW) | 55.32 | 54.99 | 58.58 | 57.33 | 56.81 | 59.58 | 56.29 | 57.65 | 57.23 | 57.56 | 54.64 | 56.64 |
%MR | −1.3101 | 0.2732 | −0.8319 | −0.5304 | −0.5192 | −0.7529 | −0.6434 | −0.8319 | −0.7244 | −0.5743 | −0.0033 | −0.4092 |
A. EEP evaluation under LM-1 | ||||||||||||
With SOC | With 1EV Station | With 2EV Station | With 3EV Station | With 4EV Station | ||||||||
0% | 25% | 50% | 0% | 25% | 50% | 0% | 25% | 50% | 0% | 25% | 50% | |
Optimal Conf | 10, 27, 30, 33, 34 | 7, 8, 12, 26, 31 | 7, 10, 14, 28, 30 | 10, 28, 31, 33, 34 | 10, 13, 28, 30, 33 | 6, 9, 13, 28, 30 | 10, 14, 28, 30, 33 | 10, 14, 28, 30, 33 | 6, 9, 12, 17, 28 | 10, 27, 31, 33, 34 | 10, 13, 26, 30, 33 | 7, 12, 10, 27, 32 |
Optimal EVS(Location) | 32 | 32 | 32 | 18, 32 | 18, 32 | 18, 32 | 18, 32, 17 | 18, 32, 17 | 18, 32, 17 | 18, 32, 17, 30 | 18, 32, 17, 30 | 18, 32, 17, 30 |
DG | 904 (18) 767 (7) 833 (29) | 857 (16) 838 (24) 942 (29) | 964 (25) 549 (13) 883 (33) | 630 (15) 734 (25) 908 (7) | 782 (33) 834 (7) 889 (25) | 766 (18) 925 (29) 832 (8) | 816 (7) 650 (32) 902 (30) | 915 (26) 808 (25) 764 (31) | 574 (25) 862 (9) 755 (32) | 800 (26) 824 (16) 713 (29) | 842 (8) 731 (33) 944 (25) | 906 (29) 804 (15) 882 (24) |
Vmin | 0.9692 | 0.9593 | 0.9765 | 0.9582 | 0.9752 | 0.9703 | 0.9754 | 0.9754 | 0.9721 | 0.9687 | 0.9748 | 0.9728 |
Fsi,min | 29.01 | 22.50 | 28.78 | 27.84 | 34.39 | 25.27 | 31.39 | 31.39 | 27.97 | 26.74 | 32.45 | 29.58 |
PL, (kW) | 54.94 | 59.78 | 56.97 | 58.66 | 55.49 | 57.58 | 56.77 | 57.69 | 61.11 | 58.56 | 57.07 | 56.25 |
%MR | −0.1137 | −0.5635 | −0.6639 | −0.2555 | −0.1613 | −0.9775 | −0.1322 | −0.1320 | −0.8058 | −0.2126 | −0.2690 | −0.6587 |
B. EEP evaluation under LM-2 | ||||||||||||
With SOC (60–100%) | With 1EV Station | With 2EV Station | With 3EV Station | With 4EV Station | ||||||||
PLP = 1 | PLP = 2 | PLP = 3 | PLP = 1 | PLP = 2 | PLP = 3 | PLP = 1 | PLP = 2 | PLP = 3 | PLP = 1 | PLP = 2 | PLP = 3 | |
Optimal Conf | 11, 14, 28, 30, 33 | 7, 10, 14, 28, 30 | 7, 12, 10, 32, 37 | 7, 8, 32, 34, 37 | 7, 13, 28, 30, 35 | 9, 13, 26, 30, 33 | 7, 9, 14, 28, 30 | 9, 26, 31, 33, 34 | 6, 9, 13, 31, 37 | 7, 9, 14, 28, 30 | 7, 9, 13, 28, 30 | 7, 10, 27, 31, 34 |
Optimal EVS (Location) | 32 | 32 | 32 | 18, 32 | 18, 32 | 18, 32 | 18, 32, 17 | 18, 32, 17 | 18, 32, 17 | 18, 32, 17, 30 | 18, 32, 17, 30 | 18, 32, 17, 30 |
DG | 880 (25) 877 (5) 790 (32) | 594 (32) 831 (22) 985 (25) | 790 (30) 856 (15) 755 (25) | 806 (25) 874 (12) 965 (28) | 628 (33) 886 (25) 736 (8) | 830 (29) 561 (18) 812 (6) | 858 (18) 756 (7) 967 (25) | 966 (30) 557 (8) 871 (15) | 531 (29) 876 (15) 810 (24) | 915 (25) 556 (32) 437 (22) | 613 (31) 966 (24) 778 (20) | 472 (18) 555 (8) 950 (29) |
Vmin | 0.9755 | 0.9668 | 0.9714 | 0.9662 | 0.9659 | 0.9664 | 0.9672 | 0.9706 | 0.9625 | 0.9603 | 0.9643 | 0.9664 |
Fsi,min | 34.26 | 24.37 | 31.39 | 30.87 | 28.84 | 32.12 | 19.94 | 29.57 | 20.58 | 21.88 | 22.95 | 29.62 |
PL, (kW) | 57.81 | 53.02 | 53.14 | 60.50 | 55.49 | 54.80 | 57.38 | 55.35 | 55.63 | 58.36 | 57.58 | 53.67 |
%MR | −0.0852 | −0.7734 | −1.0477 | −0.6443 | −0.4915 | −0.1927 | −0.4482 | −0.2100 | −1.5506 | −0.4392 | −0.5456 | −0.9368 |
C. EEP evaluation under LM-3 | ||||||||||||
With SOC (60–100%) | With 1EV Station | With 2EV Station | With 3EV Station | With 4EV Station | ||||||||
PLP = 1 | PLP = 2 | PLP = 3 | PLP = 1 | PLP = 2 | PLP = 3 | PLP = 1 | PLP = 2 | PLP = 3 | PLP = 1 | PLP = 2 | PLP = 3 | |
Optimal Conf | 10, 28, 31, 33, 34 | 7, 8, 32, 34, 37 | 10, 14, 28, 31, 33 | 7, 11, 14, 31, 37 | 7, 8, 28, 32, 34 | 7, 9, 12, 27, 30 | 7, 12, 27, 31, 35 | 10, 13, 28, 31, 33 | 7, 9, 25, 32, 34 | 7, 9, 26, 30, 34 | 6, 8, 13, 27, 31 | 6, 9, 12, 16, 28 |
Optimal EVS (Location) | 32 | 32 | 32 | 18, 32 | 18.32 | 18, 32 | 18, 32, 17 | 18, 32, 17 | 18, 32, 17 | 18, 32, 17, 30 | 18, 32, 17, 30 | 18, 32, 17, 30 |
DG | 878 (16) 979 (6) 714 (31) | 848 (25) 678 (12) 889 (30) | 610 (26) 653 (18) 946 (29) | 854 (16) 834 (24) 941 (29) | 793 (15) 663 (31) 820 (25) | 851 (25) 839 (17) 673 (22) | 908 (24) 866 (15) 918 (30) | 912 (25) 815 (8) 607 (33) | 680 (15) 813 (24) 977 (29) | 807 (33) 648 (8) 914 (29) | 690 (8) 670 (17) 870 (25) | 843 (24) 871 (32) 893 (8) |
Vmin | 0.9738 | 0.9610 | 0.9740 | 0.9724 | 0.9788 | 0.9644 | 0.9605 | 0.9712 | 0.9708 | 0.9719 | 0.9672 | 0.9748 |
Fsi,min | 28.55 | 26.02 | 31.41 | 23.79 | 29.41 | 24.11 | 24.89 | 31.48 | 26.77 | 28.59 | 27.79 | 31.51 |
PL, (kW) | 55.88 | 58.51 | 57.06 | 56.58 | 56.30 | 58.77 | 56.99 | 55.51 | 57.33 | 57.18 | 57.64 | 57.01 |
%MR | −0.3905 | −0.7449 | −0.4915 | −1.1597 | −0.6402 | −0.1447 | −0.4603 | −0.5888 | −0.6973 | −0.4448 | −1.3562 | −0.7979 |
Case/Methods | Configuration | EV | Power Loss (kW) | DG Size | DG Location |
---|---|---|---|---|---|
Location | |||||
Base Configuration | 33, 34, 35, 36, 37 | -- | 202.67 | -- | -- |
Optimal configuration | 7, 9, 14, 32, 37 | -- | 139.5 | -- | -- |
DG allocation in base Configuration under, | -- | ||||
LM-1 | |||||
LM-2 | 78.25 | 652, 999, 656 | 14, 26, 32 | ||
LM-3 | 33, 34, 35, 36, 37 | 76.78 | 781, 991, 407 | 32, 7, 18 | |
69.72 | 970, 542, 505 | 29, 9, 14 | |||
DG allocation in optimal configuration under, | |||||
LM-1 | |||||
LM-2 | 7, 9, 14, 32, 37 | -- | 72.19 | 968, 780, 997 | 23, 16, 27 |
LM-3 | 75.05 | 419, 408, 653 | 6, 18, 28 | ||
65.07 | 680, 828, 622 | 12, 7, 30 | |||
DG allocation and Reconfiguration under, | |||||
LM-1 | |||||
LM-2 | 7, 13, 11, 36, 27 | -- | 58.10 | 890, 856, 792 | 25, 9, 31 |
LM-3 | 7, 12, 10, 32, 25 | 56.39 | 984, 811, 754 | 25, 15, 31 | |
7, 12, 10, 31, 27 | 52.18 | 892, 967, 780 | 29, 9, 16 | ||
DG allocation and Reconfiguration with EVs as a load | |||||
LM-1 | |||||
LM-2 | |||||
LM-3 | 9, 28, 31, 33, 34 | 18 | 55.64 | 933, 885, 990 | 15, 7, 30 |
9, 14, 28, 30, 33 | 18 | 53.37 | 977, 699, 930 | 25, 17, 7 | |
9, 27, 30, 33, 34 | 18 | 54.99 | 957, 920, 741 | 25, 8, 18 | |
DG allocation and Reconfiguration with EVs as a source | |||||
LM-1 | |||||
LM-2 | |||||
LM-3 | 10, 27, 30, 33, 34 | 32 | 54.94 | 904, 767, 833 | 18, 7, 29 |
7, 10, 14, 28, 30 | 32 | 53.02 | 594, 831, 985 | 32, 22, 25 | |
10, 28, 31, 33, 34 | 32 | 55.88 | 878, 979, 714 | 16, 6, 31 | |
Ref. [28] | |||||
IPSO | 33, 34, 9, 32, 28 | -- | 59.63 | 557, 922, 931 | 18, 7, 30 |
TLBO | 6,14, 10, 32, 37 | 58.08 | 1329, 1172, 726 | 8, 24, 31 | |
PSO | 7, 13, 11, 32, 27 | 59.37 | 1732, 809, 550 | 29, 16, 7 | |
Jaya | 33, 13, 9, 28, 30 | 58.49 | 801, 1215, 745 | 18, 25, 9 | |
Ref. [29] | 7, 14, 10, 31, 28 | -- | 73.05 | 526, 559, 584 | 28, 31, 33 |
Ref. [30] | 7, 9, 14, 17, 37 | -- | 92.98 | 55, 151, 103 | 18, 31, 32 |
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations. |
© 2022 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/).
Share and Cite
Kumar, P.; Nikolovski, S.; Ali, I.; Thomas, M.S.; Ahuja, H. Impact of Electric Vehicles on Energy Efficiency with Energy Boosters in Coordination for Sustainable Energy in Smart Cities. Processes 2022, 10, 1593. https://doi.org/10.3390/pr10081593
Kumar P, Nikolovski S, Ali I, Thomas MS, Ahuja H. Impact of Electric Vehicles on Energy Efficiency with Energy Boosters in Coordination for Sustainable Energy in Smart Cities. Processes. 2022; 10(8):1593. https://doi.org/10.3390/pr10081593
Chicago/Turabian StyleKumar, Pawan, Srete Nikolovski, Ikbal Ali, Mini S. Thomas, and Hemant Ahuja. 2022. "Impact of Electric Vehicles on Energy Efficiency with Energy Boosters in Coordination for Sustainable Energy in Smart Cities" Processes 10, no. 8: 1593. https://doi.org/10.3390/pr10081593
APA StyleKumar, P., Nikolovski, S., Ali, I., Thomas, M. S., & Ahuja, H. (2022). Impact of Electric Vehicles on Energy Efficiency with Energy Boosters in Coordination for Sustainable Energy in Smart Cities. Processes, 10(8), 1593. https://doi.org/10.3390/pr10081593