1. Introduction
Energy-efficiency strategies are presently integrated into the design process of a building. The façade may play an important role in the reduction of the system’s energy demand by significantly decreasing solar radiation and increasing the inhabitants’ living comfort. Permeable double skins are an example of high-efficiency façades where the building envelope consists of two façades (or skins): the inner one is usually made of glass panels and the outer skin is characterized by a porous metallic screen. The first goal of this kind of cladding is to protect the building from direct sunlight, with the external skin acts as a louvre, allowing a nearly unobstructed view of the outside.
As far as interaction with wind is concerned, the presence of an outer permeable skin is expected to alter the distribution of wind-induced pressure on the inner façade and, thus, the design cladding loads. In addition, strong wind effects are expected on the external mesh, as it is the first layer exposed to wind action. The porous layer may act as a sheltering device for the inner façade, implying a potential reduction of the design pressure for the latter. When predicting the wind effects on a building envelope of this type, a typical multi-scale problem must be addressed—the relevant effects due to the building’s geometry being immersed in the atmospheric boundary layer must be considered along with those related to the small-scale details of the porous components’ geometry. Both scales simultaneously affect the building-wind interaction.
Despite the popularity of this cladding system in recent architectural trends, the structural design of permeable cladding in terms of wind effects has been sparsely studied in current literature [
1]. The effects of wind-loading conditions on a porous façade have been studied by Gerhardt and Janser [
2], who investigated the pressure distribution on a rainscreen installed over a closed façade. They highlighted the reduction of the wind-induced pressure on the inner skin, compared to a single-layer façade, and the net load expected on the permeable elements. However, these results refer to a very low value of porosity (in the order of 1%) compared to typical values applied for the PDSF (20–50%). More recently, Kemper et al. [
3] proposed different wind-load recommendations for rectangular-shaped buildings with single porous cladding and a porous double skin façade. For the latter, the porous cladding elements are made using stainless steel wire mesh with 20% porosity. Both full-scale measurements and wind tunnel tests on a scale model were performed to address the aerodynamic behaviour of the porous skin and corresponding wind loads. Pomaranzi et al. [
4,
5] and Lo et al. [
6] quantified the reduction of the wind-induced pressure experienced by the inner sealed façade when an outer porous screen was installed, by proposing a comparative study between the single façade case and the PDSF. The aforementioned studies propose a purely experimental approach essentially aimed at estimating the wind pressure on the inner skin of a PDSF. However, this kind of approach exhibits limitations if the net load on the permeable layer is to be measured, since it could be hard to position pressure sensors on that skin if the model’s dimensions are small. In addition to this, a quantification of the expected flow rate through the permeable skin is not quantifiable or, at best, some spot measurements can be performed. In practice, cases exist in which this information could become of great relevance for addressing potential aero-acoustic problems that may arise when porous elements are exposed to wind [
7], as the tonal noise emission is usually associated with a through velocity threshold.
These limitations can be overcome by a Computational Fluid Dynamic approach that is able to provide a continuous representation of velocity and pressure fields. Within the CFD framework, literature offers several studies focused on the fluid interaction of porous elements and they propose essentially two alternatives for modelling fluid interaction with porous elements [
8]. The first one deals with explicit modelling of the geometry of the permeable element. However, this option is computationally unaffordable, especially if the porous element is part of a more complex system, as in the case of a PDSF. The other possibility is to rely on a porous-media approach by representing the porous element by means of a surface with zero-thickness or with a 3D volume, where a pressure jump or momentum source/sink term is used to account for the porosity effects. When the thin surface is used, the approach is usually referred to as a porous baffle: the porous element is modelled as a continuous surface in the computational domain and, at the cell faces of that surface, the pressure jump condition is realized by means of a resistance source in the Navier–Stokes momentum equation, as a function of the velocity component normal to the surface itself. Xu et al. [
9] discussed the performances of the pressure jump approach on a perforated rectangular cylinder, and concluded that, if compared to explicit modelling, some local discrepancies exist but good agreement is found for the mean pressure and velocity fields. A porous baffle model is also used in many other application fields, such as modelling the air flow through perforated tiles at data centres [
10], or simulating the presence of actuator disks [
11] to mention a few. The main limitation of the pressure jump approach is that its validity holds for thin structures only. When more complex porous structures are to be considered (i.e., with anisotropic characteristics), the so-called porous media approach is more suitable than the porous baffles one. It consists of representing the porous elements by means of a 3D volume in the computational domain, where the momentum resistance is applied to the cells of that volume. This approach was used by Feichtner et al. [
12,
13] to model the wave interaction with perforated sheets and cylinders. Given that the PDSF may be formed with different types of outer skin, including louvres, perforated or expanded metal and wire meshes, the porous media approach will be considered here to be the most appropriate tool for achieving numerical modelling of the porous façade.
This paper proposes a new methodology for addressing the design of a PDSF in terms of the wind effects: experimental tests and CFD simulations with porous media models will play complementary roles, to address the computation of the design pressures on both façade layers and to estimate the flow rate through the permeable skin.
This method is presented in the form of a case study, namely the ENI Head Office building complex.
The Case Study
The
ENI Head Office case study is a building complex made up of three interconnected buildings, as shown in
Figure 1. The complex covers 65,000 m
and the height of the structures reaches 45 m. The buildings are designed with a permeable double skin façade system: the inner glazed skin is covered by perforated metal in such a way that a gap flow can develop in the cavity between the two skins. Specifically, the ICO and SKG buildings are covered by a so-called Orange Skin, made up of stainless steel perforated metal with circular holes 6mm in diameter, spaced 8 mm apart (porosity equal to 50%). The ICO and the LMK buildings are connected by a bridge, that has only the Orange Skin with no inner façade as cladding. Lastly, the LMK building’s porous layer is characterized by the Blue Skin, horizontal louvres made uyp of metal sheets perforated by circular holes 6.35 mm in diameter, spaced 8 mm apart (porosity equal to 55%).
Since the outer skin is made up of perforated metal sheets, air passing through the holes can generate undesired tonal noise [
14].
There are two main problems to be addressed for this case study: the definition of the wind-induced pressure on both layers of the cladding system, and the estimation of the flow rate expected across the porous skin. The latter can subsequently be combined with a wind climate study of the buildings’ area, in order to quantify the risk of exceeding of the threshold velocity associated with tonal noise emission by the perforated metal sheets.
2. Methodology
Addressing the assessment of wind effects on a permeable double skin façade implies facing a typical multi-scale problem. The relevant effects due to immersion of the building in the Atmospheric Boundary Layer must be considered together with the local phenomena that develop at the level of the porous façade’s openings. Local flow will be characterized by scales expected to have dimensions comparable to those of the openings themselves (usually in the order of cm), and will be affected by the boundary layer that develops locally.
An experimental-based approach, typically consisting of wind tunnel tests on a rigid scale model, is one of the most commonly adopted tools for addressing estimation of cladding loads on buildings. However, when dealing with a PDSF, reproducing the porous layer properly in the scale model may represent an issue, given the already small (at full scale) dimensions of the façade’s details. This is particularly concerning when the geometry of the permeable layer is characterized by a 3D geometry that will induce flow deflection. Additionally, as previously pointed out, quantification of the expected flow rate through the PDSF, that may be relevant for design purposes, is hard to assess using a purely experimental approach. These limitations make it necessary to consider a CFD model as a complementary tool for addressing the wind interaction issue for the PDSF. Within the numerical framework, the porous media approach can be applied to reproduce the effects due to the porous façade without explicitly modelling it in the computational domain, as already introduced in
Section 1.
A new methodology based on a combined experimental-numerical approach is proposed and the two methods play complementary roles. Specifically, the experimental part consists of wind tunnel tests on a rigid scale model, where the porous façade is reproduced physically, essentially aimed at estimating the cladding loads for the PDSF. The numerical part, on the other hand, is based on a dedicated CFD model, referred to here as the CFD reduced order model, able to model the PDSF, thereby overcoming the multi-scale nature of the problem. The latter will address estimation of the flow rate through the porous layer, after it has been validated against experimental data.
The methodology, based on experimental tests and numerical simulations, was specifically designed to allow a quantitative approach to assessing the wind effects for the porous double skin façade. It is essentially made up the following steps:
Aerodynamic characterization of the porous elements by means of the pressure loss coefficient.
Wind tunnel tests on a rigid scale model of the building complex, on which the double skin cladding system is reproduced.
Computation Fluid Dynamics simulations, where a dedicated reduced-order model is used to include the effects due to the PDSF.
2.1. First Stage—Aerodynamic Characterization of the Porous Layer
When dealing with porous elements, their loading condition due to wind is mainly affected by their resistance to the flow, which depends on the pattern of the openings and the wind attack angle [
15]. When the air flows through a porous element, there is an interaction between the fluid and the structural elements which is related to the aerodynamic properties of the medium and the characteristics of the fluid. A pressure drop in the fluid occurs when the flow passes through the permeable element. The pressure loss coefficient
k, that synthetically describes the resistance to through flow, is proportional to this pressure drop and is defined as:
where
is the pressure drop between the windward and the leeward side of the porous screen,
is the air density and
U is the mean wind speed. According to the state of the art, the pressure loss coefficient can be used to synthetically describe the aerodynamic behaviour of porous elements, especially when they are characterized by planar geometries, like perforated metals or wire meshes.
Within this case study, the pressure loss coefficient
k is measured experimentally in an open-circuit wind tunnel. A schematic representation is shown in
Figure 2: the porous screen is placed in the measurement section, orthogonally to the incoming flow. Two Pitot tubes, upstream and downstream, are used to measure the pressure drop.
2.2. Second Stage—Wind Tunnel Tests
The experimental part of the proposed methodology consists of wind tunnel tests on rigid scale models. From this stage, cladding loads on the PDSF can be assessed and data for subsequent validation of the CFD model is provided. Below, the experimental setup and model are described in relation to the ENI Head Office case study.
Wind tunnel tests were done at the Politecnico di Milano Wind Tunnel, a 1.5 MW closed circuit wind tunnel. The boundary layer test section was 4 m high, 14 m wide and 36 m long. The large dimension of the test section makes it possible to adopt a large geometric scale
(
) with low blockage ratio, equal to 3% for this test. The geometric scale is chosen to be 1:75 thereby guaranteeing a gap between the two skins large enough to let the gap flow develop (equal to 2 cm on the scale model); geometric scaling was applied to the overall structure excluding the porous elements. For these elements, the kinematic similitude of the flow condition between the full and model scales is ensured by means of the pressure loss coefficient
k, that must be maintained [
5]. Hence, the same perforated metals as in the full scale case are used in the model, as the hole diameters are compatible with the overall model’s dimensions.
The wind speed for the tests is 8.90 m/s in the experimental tests, that implies a velocity scale
equal to 1:3.09, assuming a full scale reference wind speed of 27.5 m/s. The time scale
, equal to the ratio between the length and velocity scales, is equal to 1:24.3.
Table 1 summarizes the reference lengths and velocities as well as the sampling time and frequency at model and full scale. The reference velocity for the tests was measured by a Pitot Tube placed 7 m upstream of the model, 0.60 m above the ground.
2.2.1. Model Description and Instrumentation
The buildings in the test section are shown in
Figure 3. The model was fitted with 400 pressure taps: of these, 198 were distributed on the inner sealed façade and the remaining 202 were used to measure the differential net pressure on the porous layer. The large scale of the model made it possible to position sensors on the porous layer, in an attempt to minimize the distortions due to the presence of the tubes with the gap between the two façades:
Figure 4 shows a detailed view of how the pressure taps were arranged on the model’s surface. Pressure measurements were taken using high-speed Initium pressure scanning equipment(with a sampling frequency equal to 500 Hz) and miniature pressure scanners PSI ESP-32 HD, each of which have 32 pressure channels.
Figure 5 shows the wind directions convention adopted in the wind tunnel tests: 36 exposures, at 10° spacing, were considered.
Multi-hole cobra probes were used to measure the three-components of the velocity vector in the gap in the PDSF. These sensors were installed in the gap between the perforated metal and the inner skin as well as in front of the external side of the porous façade. To achieve a reliable estimation of the gap flow, cobra probes were mounted pointing towards the expected direction of the flow.
2.2.2. Flow Configuration
Passive turbulence generators together with roughness elements were used to generate a representative wind field for the case at hand.
Figure 6 shows the mean velocity (left), turbulence intensities (centre) and integral length scales (right), measured at the centre of the turntable, compared to those proposed by Eurocode, category III, assumed as a target. The
z coordinate used in the plots is in model scale. The mean velocity profile is normalized in relation to the reference velocity
, where
is the maximum building height. Profiles compare well with the target ones, especially when focusing on
z lower than 1 m. Lastly,
Figure 7 shows the streamwise velocity spectrum, measured at a height of 1 m. It was normalized by the measured integral length scale and showed good agreement with both the Von-Karman and the Eurocode spectra.
2.3. CFD Reduced Order Model of the PDSF
To estimate the velocity flow field and to quantify the flow rate across the porous façade, a dedicated Computational Fluid Dynamic model was developed. It relies on a porous media model and will be referred to as
reduced order model, as it is able to avoid explicit modelling of the porous geometry, thereby reducing the computational complexity of the numerical simulations. It is based on the Darcy-Forchheimer model for porous media: the porous façade of the PDSF is not explicitly modelled in the computational domain, but it is reproduced by means of a “porous” slab and for each cell in that volume, a momentum resistance term is applied according to the Darcy-Forchheimer model [
16].
Figure 8 presents a schematic view of how the PDSF is modelled in the computational domain: the external porous façade in the physical system corresponds to a special set of cells in the computational domain, responsible for the momentum defect.
Since a steady-state approach was considered, the equations solved for the incompressible flow were:
where
is the velocity vector,
the fluid density,
the dynamic viscosity and
p the pressure. The momentum sink term
for modelling the porosity effects is written as:
where
represents the porosity effects proportional to viscosity and
accounts for the total pressure loss proportional to the incoming flow’s dynamic pressure. The dimensions are
and
respectively. The source term
S, which has a force per unit volume dimension or, equivalently, a pressure gradient dimension, will be responsible for the actual pressure gradient through the porous slab, associated with the cross-flow. As the porous elements considered here are characterized by a low viscosity level and high pressure contribution, the proposed model focuses on the pressure intake (tensor
F), neglecting the viscous supply, represented by
D.
According to the state of the art, the perforated metal sheets represent the simplest case, as the momentum sink term is computed by means of a diagonal tensor with only one term different from zero, i.e., the one associated with the flow component orthogonal to the porous slab. This assumption implies assuming that the other velocity components make no contribution to the source term
S and so, neglecting any flow deflection due to the permeable layer, which is expected to be of no relevance in the case of perforated metals. Hence, assuming a Cartesian reference system in which the porous slab is lying in the
plane, Equation (
3) becomes:
where the
F coefficient is computed as the pressure loss coefficient
k (experimentally computed) divided by the thickness of the
porous slab in the computational domain.
The numerical solver used for this analysis is the open-source software, OpenFOAM: the flow is calculated by means of a finite volume approach, solving the steady-state incompressible Reynolds-Averaged Navier-Stokes (RANS) equations, using adapted turbulence modelling to achieve closure and suitable boundary conditions, as will be detailed in the next sections.
2.3.1. CFD Mesh
The building’s geometry is reproduced in the computational domain, assuming a length scale of 1:75, hence with a maximum height of 0.60 m. The mesh was formed within a domain 14 m × 15 m × 6.5 m, as sketched in
Figure 9. The mesh is realized by means of a top-bottom strategy, using the OpenFOAM mesh generator, SnappyHexMesh. A background mesh is formed using a structured grid 0.5 m in size, then a successive refinement in the porous slabs area is performed, up to a final mesh size on the porous surface of 4 × 10
m with a total number of 8.7 million cells. To check the quality of the mesh and the refinement level, the
yPlus parameter was calculated and checked to be higher than 30 to allow the application of the wall functions.
Figure 10 and
Figure 11 show a detailed view of the mesh: the former shows an horizontal section of the computational domain, the latter focuses on the porous slab representing the perforated metal sheets for the SKG building.
Each numerical simulation is run on an HPC facility using 3 nodes with 8 cores each.
2.3.2. Numerical Setup and Boundary Conditions
The numerical model is a steady state incompressible RANS standard, with a
turbulence model, that is suitable for modelling the atmospheric boundary layer and flow around buildings [
17]. All the schemes were selected as second order, upwind-biased and a SIMPLE algorithm was used for the pressure-velocity coupling. The atmospheric wind profile corresponding to the wind tunnel testing profile was imposed at the inlet.
Boundary conditions are defined as follows:
INLET: atmBoundaryLayer with reference wind speed U = 10 m/s and specified wind direction, zeroGradient for pressure
OUTLET: InletOulet for velocity, fixedValue pressure
SOLID WALL: zero velocity with standard wall functions
BACK and FRONT: U symmetry, p symmetry.
Simulations were run for 24 different wind directions, i.e., from 0° to 360°, at 15° intervals, in relation to the convection shown in
Figure 5.
Figure 12 describes the boundary conditions in the case of the incoming wind direction being equal to +90°.
4. Conclusions
The ENI Head Office case study represented an opportunity to develop and apply a new methodology for assessing the wind effects on a PDSF. The proposed method takes advantage of a combined numerical—experimental approach, where the former is dedicated to estimating the flow rate and the latter focuses on the assessing the cladding load. First, characterization of the aerodynamic properties of the perforated metal sheets, by means of the pressure loss coefficient, was carried out. Then, during the wind tunnel tests on rigid scale models, the pressure was measured on both layers of the PDSF: an analysis of the recorded time histories highlighted a strong correlation between upwind and downwind sides of the porous layer, especially in the Bridge area, qualitatively highlighting a certain flow rate through the porous façade. Then, quantification of the pressure load on the cladding was proposed by means of envelope pressure maps: for the inner façade, the strongest suctions, up to , are found close to the buildings’ edges while the porous layer is affected by thrusts in the area of the Bridge, where the façade presents only the perforated metal sheets. Additionally, spot velocity measurements were taken out on the wind tunnel scale model to quantify the flow rate through the perforated metal sheets, highlighting the presence of a non-negligible gap flow, with local velocities up to 70% of the reference value. A more detailed estimation of the flow rate through the porous layer was provided by the CFD reduced order model: a porous media approach was applied to overcome the multi-scale nature of the problem, making it possible to properly model buildings with a PDSF within the computational domain. According to the Darcy-Forchheimer model, a tensorial formulation was used to describe the momentum sink due to the permeable element. Specifically, the perforated metal sheets were treated as isotropic material with diagonal terms of the inertial tensor proportional to the experimentally computed pressure loss coefficient. Results from the CFD reduced order model compare well to the experimental velocities measures, showing that building edges and the Bridge are the areas most affected by the highest flow rate. Combining the numerical estimation of the through velocities with a local wind climate analysis, makes it possible to quantify the risk of exceeding the threshold velocity associated with the generation of tonal noise, ascribable to the perforated metal.
Further developments of the proposed methodology will evolve towards considering more complex geometries for the outer porous façade, where the tensorial formulation can be fully exploited to describe more complex interaction between the flow and the permeable elements. For example, when dealing with an expanded metal sheet, the CFD reduced order model must be able to describe the flow deviation that occurs and to do so the Darcy-Forchheimer model must rely on a full tensor, where 9 input parameters are to be identified.