1. Introduction
The heat exchanger (HE) is one the foremost critical engineering tools and is used in both heating and cooling processes in several domestic, industrial, and commercial applications, including the wastewater treatment, HVAC, waste heat recovery units, and pharmaceutical industries [
1]. HEs are used to fulfilling different tasks in the industry depending on the type of fluid, density, viscosity, and temperature. Waste of energy in practice is a common phenomenon that could be recovered by means of HEs and heat a different stream in the process [
1]. This can be seen as a practical way to save money and avoid employing an external energy source, which is generally expensive and harmful to the environment.
The need for heat transfer is a thorny issue in HEs and can be investigated by looking into many factors, such as structure complexity, intermediate fluid, and configuration [
1]. Precisely, different techniques are employed to reduce thermal resistance by generating turbulence in the inner running fluid or increasing the effective surface area. The heat transfer enhancement method can be generally categorized into three classes: active [
2,
3], passive [
4,
5], and compound methods [
6]. dis when some external power inputs are either imposed on the fluid or the heated surface so that the rate of heat transfer is enhanced. This issue is somewhat related to the system requirements. Since flow structure analysis is hard to access (owing to external impacts), the methods in this class are deemed complex. Passive methods, on the other hand, take advantage of the modified surfaces and/or insertion of elements, especially turbulence promotors within the flow. Therefore, there is no need to utilize any external power in order to augment the heat transfer. As a result of the alteration of the flow treatment, the coefficient of the convective heat transfer rises. Operating under specific flow and thermal conditions, such techniques come with corresponding pros and cons.
Fin-and-tube heat exchangers (FTHEs) are one of the most widely used heat exchangers for thermal energy conversion and are used in different applications, such as the automotive industry, power plants, electronic devices, process equipment, air conditioning, and refrigeration [
7]. Sadeghianjahromi and Wang [
7] presented a complete review paper on the previous studies in the field of heat transfer in FTHEs before 2020. The various techniques introduced to improve heat transfer in this type of HE were described in this review paper. Most of these techniques are in the category of passive methods. Recent research in this area is discussed in the following. Gong et al. [
8] proposed a new windward Louvered fin structure for use in the fuel cell vehicle radiator. They claimed that due to the airflow deflection, the windward Louvered fin structure significantly improved the thermal performance of the HEs. In addition, Gong et al. [
9] proposed the idea of inserting metal elbows into the airside of an FTHE to improve heat transfer in fuel cell vehicles. A comparison between the new structure and the traditional compact radiator was conducted both numerically and experimentally, and a heat transfer improvement of 22% was observed. Altwieb et al. [
10] presented a new perforated plain fin structure used for multi-tube, multi-fin heat exchangers. The new fin structure was compared with standard plain and louvered fins. They claimed that by considering both the factors of increasing heat transfer and pressure drop, their proposed fin structure performed better than plain and louvered fin structures. In order to enhance the heat transfer in traditional vehicle radiators, Luo et al. [
11] presented three novel structural designs for FTHEs based on wavy–louvered fin and vortex generators. They claimed that these new designs could be used to increase the cooling capability in proton exchange membrane fuel cells. Song et al. [
12] suggested a new fin configuration using both concave curved vortex generator pairs and wavy fins in an FTHE. The impact of the concave curved vortex generator pairs location and attack angle on HE performance were investigated numerically. The results showed that adding vortex generators could increase the Nusselt number by 30.6%. Jalil and Goudarzi [
13] suggested a nozzle- and diffuser-shaped arrangement of fins to improve the heat transfer in FTHEs. They compared the thermal performance of these two types of fin arrangements with the simple tube. The results revealed that the nozzle-shaped fin structure had a better performance than the other one.
Recently, the passive method of using nanofluids as the working fluid in FTHEs has received much attention. Enhanced heat transfer performance of car radiators is the main purpose of using these nanocoolants. The heat transfer enhancement of using hybrid nanofluids in car radiators was investigated by Li et al. [
14]. For this type of FTHE, the maximum convective heat transfer coefficient of the nanocoolant was 26% higher than that of pure ethylene glycol under identical circumstances. A new hybrid nanofluid comprising Fe
2O
3-TiO
2 (50:50) nanoparticles was introduced by Abbas et al. [
15]. The nanofluid thermal performance was tested in an aluminum tube automotive radiator for three different nanofluid concentrations. In addition, the impacts of inlet temperature and flow rate were examined. The results showed a large effect of nanoparticle volume fraction on the heat transfer performance of FTHEs. In their experiments, the maximum increase in heat transfer was 26.7%. Xian et al. [
16] examined the effect of a hybrid nanocoolant containing carboxyl-functionalized graphene nanoplatelets and titanium dioxide nanoparticles on the thermal performance of an FTHE used in a vehicle cooling system. The results showed that using a new hybrid nanocoolant led to an increase of up to 35.87% in the overall heat transfer coefficient of the HE in comparison with that using a base coolant.
As an active method, Li et al. [
17] introduced a vibration-enhanced heat transfer technology for an FTHE. The vibrations of their experiments had a frequency of 25 kHz and were in the audible range. Their simulations showed that increasing the amplitude and frequency increased the thermal performance of the HE. Furthermore, there are several review papers [
18,
19] and applied research papers [
20,
21,
22,
23] dealing with heat transfer enhancement in several types of HEs caused by applying ultrasonic excitation (UE). It should be noted that other methods, such as magnetohydrodynamics (MHD) [
24,
25], have also been introduced to increase heat transfer in thermal systems.
In this paper, the authors tried to perform a comprehensible study on the effects of UE on heat transfer enhancement of an FTHE experimentally. According to the research literature, the study of UE’s effect in this type of HEs is very rare, and much research is needed to prove the efficiency of this technology in this type of exchanger and its commercialization. In fact, most of the proposed techniques for increasing heat transfer in FTHEs have been limited to passive methods, such as modifying the geometry of the fins or substituting the HE operating fluid. Modifying the fin arrangement requires redesigning the existing HEs and in some cases can even increase the structure’s weight and pressure drop. Replacing the base fluids, such as water or ethylene glycol, with nanocoolants can also cause the continuous accumulation and sedimentation of nanoparticles in this type of HE, and therefore, its practical implementation is associated with many issues. It is expected that the power UE technology used in the present work, due to its significant effects on the propagation medium, could significantly increase the heat performance of FTHEs.
2. Non-Dimensional Numbers and Formulations
Here, some of the most important non-dimensional numbers used in this paper are presented. These dimensionless numbers are defined for the liquid flow inside the tube. First and foremost, the Reynolds (
) number is defined as:
where
stands for the kinematic viscosity of the fluid, and
is the hydraulic diameter of the tubes.
and
are dynamic viscosity and density, respectively. The Reynolds number for the liquid fluid flow inside the tube varies between 2166 and 6500. In addition, considering the hydraulic diameter of the air conditioning channel as the characteristic length, the air-side Reynolds number will be between 2000 and 9000. The Prandtl (
) number, the ratio of momentum diffusivity to thermal diffusivity (
), is defined as:
The Prandtl number for the water inside the pipes is in the range of 6.99 <
Pr < 9.95, and for the flow of air passing over the radiator, it is about 0.7. The Nusselt (
) number, which plays a critical role in convective heat transfer, is defined as:
where,
represents the coefficients of the convective heat transfer.
can also be considered the overall heat transfer coefficient, as follows:
where
is the heat transfer rate, and this can be calculated by means of the energy balance equation. The temperatures of the liquid flowing inside the tube at the inlet and outlet of the FTHE are shown via
and
, respectively.
denotes the thermal capacity of the liquid and is calculated at the bulk temperature of the liquid fluid flow.
Q is the volumetric flow rate recorded by the flow meter (
Figure 1). In addition,
A is the peripheral area of the tube that is in contact with water and can be calculated by the following equation:
where
l,
w, and
H are the length, width, and height of the tube which are shown in
Figure 2.
Moreover,
is the difference between the bulk temperature of the fluid flow inside the test section and the wall temperature (
). Using the mean temperature method,
is calculated as [
26]:
3. Methodology
Here, the experimental apparatus, setup, and methods of gathering results are presented and discussed. To study the impacts of UE on the heat transfer rate, an experimental apparatus was constructed. The schematic of the apparatus and instrumentation of the experiment are depicted in
Figure 1. This system was actually an upgraded air conditioning testing system that included an air conditioning tunnel with dimensions of 200 (cm) × 35 (cm) × 35 (cm). The air conditioning tunnel was equipped with a blower fan with remote control capability with an accuracy of 1 (RPM), which allowed testing for different air flows. Two heaters (PTFE) with a power range of 0–3500 (W) were located in the air channel to control the temperature of the air over the test section. These heaters used PID control to adjust the desired air temperature. Four temperature sensors (Maxim Integrated Co., Accuracy: ±0.5 (°C)) were used. Two of them were located at the inlet and outlet of the FTHE to measure the liquid inlet and outlet temperatures, which changed in the range of 12 (°C) to 20 (°C). The other temperature sensors were used to detect the air passing temperatures ranging between 25 (°C) to 45 (°C). An airflow meter (Testo 400, Range: 0–10 (m/s), Accuracy: ±0.04 (m/s)) was utilized to measure the air passing velocity over the FTHE, which varied between 0.1 (m/s) to 4 (m/s). A refrigerated circulator (Lauda, Alpha R8) equipped with affordable cooling thermostats and a heating unit with the ability to maintain temperatures from −25 to 100 (°C) (in the lab) was used to supply water with the desired temperature and flow rate to the entrance of the test section. A flow meter (Nixon Flow Meter LTD Co, Model: NT5, Range 1.2–10 (L/min), Accuracy: ±5%) was used to record the volumetric flow rate of the liquid flow in the radiator. In the current experimental tests, the liquid flow rate was in the range of 2 to 6 (L/min).
A radiator (250 × 130 (mm)) made of aluminum alloy was considered the FTHE. A 40 (kHz) ultrasonic transducer (Hesentec Ultrasonic Co., Model: HS-8SH-3840) was powered by an ultrasonic generator (Hesentec Ultrasonic Co., Ultrasonic PCB Driver Ultrasonic Generator) with a power level of 50 (W). Two data types were obtained for each test case, one with the presence of ultrasonic excitation and the other in the silent state (no vibration), and then the obtained data were compared. As for recording data, all sensors were connected to a handheld control unit. This unit had the ability to send all the information obtained to the computer for further analysis. Furthermore, detailed drawings of the FTHE, piezoelectric transducer, and louvered fin are presented in
Figure 2. As shown in
Figure 2, a metal belt (in red) with a width of 20 mm and a thickness of 3 mm was used to mount the piezoelectric transducer. The piezoelectric transducer was connected to this adjustable structure by several screws on the top of FTHE, and its lower surface was exactly tangential to the FTHE to ensure the transmission of UE to the radiator. The Moffat method [
27] was used to calculate the uncertainty of the experiments. Using this method, the uncertainty values of the Reynolds number, Nusselt number, and heat transfer rate were ±5%, ±3.4%, and ±2.6%, respectively. It should be noted that the assumptions of (1) constant ambient air temperature and (2) equal wall temperature between the outer surface of the radiator’s tube and its inner surface (due to very low thickness) were considered in the theoretical analysis of the present work.
4. Results and Discussions
In this section, the thermal effect of UE in the FTHEs is discussed. Then, the validity of the obtained data is checked, and at the end, the thermal findings are presented and discussed in detail.
4.1. Validation
For validation, the authors took advantage of the empirical correlation reported by Dittus-Boelter [
28]. The Dittus-Boelter correlation is expressed via the non-dimensional parameters of
and
, as follows:
where
n equals 0.4 and 0.3 for heating and cooling, respectively. The variation of the
number at different Reynolds numbers ranging from 2000 to 7000 is compared and presented in
Table 1. Additionally, the percentage differences (Errors) between the current results and those of Dittus-Boelter [
28] are mentioned in
Table 1. As can be seen, there was a close match between the trend and data and that of Dittus-Boelter [
28], which ensures the validity of the findings as well as the reliability of the facility.
4.2. The Effect of UE on the Outlet Temperature
In this section, the outlet temperature is studied in a very comprehensive way. To do so, various
numbers ranging from 2166 to 6500 for the water flowing into the test section were considered. Four different velocities (
U = 0.1, 0.5, 1, and 4
) for the air passing through the FTHE were also taken into account, and
varied from 25 (°C) to 45 (°C).
Figure 3,
Figure 4,
Figure 5 and
Figure 6, which show the variation of the outlet temperature against
number, are presented to examine the presence of the ultrasonic field. Furthermore, the variation percentage is calculated and shown in the figures. All figures are presented in the absence of vibrations (UP = 0) and the presence of ultrasonic excitation with a power level of 50 Watts (UP = 50 (W)).
Increasing the ambient temperature with constant Reynolds numbers raised the wall temperature of the radiator tube and thus increased
. As a result, the heat transfer rate to the radiator increased, and the outlet fluid temperature grew. In addition, growing the velocity of the air passing over the radiator (
U) increased the heat transfer coefficient and consequently increased the heat transfer rate. However, on the other hand, with an increasing velocity of liquid flow inside the tubes and an increasing mass flow, the rate of temperature change of the outlet liquid fluid flow was less (
Figure 3,
Figure 4,
Figure 5 and
Figure 6). In the following, we focus more on the effects of ultrasonic excitation.
As can be seen, there was a consistent trend among the data, and as expected, with an increase in the Re number, the impact of UE on the outlet temperature generally faded (in all values of air passing velocity as well as ambient temperature). Accordingly, at lower air passing velocities as well as lower ambient temperatures, the influence of the vibration was highlighted more. However, with increases in
and
, the mentioned effects decreased. The most sensible effects on the outlet temperature (with 9.14%) could be seen when
and
are equal to 0.1
and 25 (°C), respectively. This can be attributed to the formation of micro-bubbles and their collision within a liquid due to acoustic excitation [
29]. Increasing the ambient temperature (at a constant Re) raised the water temperature inside the tubes. As the water temperature increased, the solubility of the air in the water decreased [
30], resulting in a lower rate of microbubble formation. Therefore, as mentioned, the effect of ultrasound was reduced.
4.3. The Effect of UE on Heat Flow
Here, the heat convection to the fluid in the FTHE under the influence of UE is studied in detail. For this test, the ambient temperature ranged from 25 (°C) to 45 (°C), and four different velocities (U = 0.1, 0.5, 1, and 4
) for the air passing through the FTHE were considered. Additionally, the Reynolds number (Re) effect was taken into account and examined for three values: 2166, 4333, and 6500.
Figure 7,
Figure 8,
Figure 9 and
Figure 10, which show the variation in heat flow against ambient temperature, are presented to examine the presence of the acoustic field and state the variation percentage. As can be seen in the figures, there was a general increase in the heat flow in comparison to the case in which there was no acoustic vibration. As expected, apart from the influence of UE, the exchanged heat flow increased as the ambient temperature rose. This was because of the increase in the temperature difference between the medium fluid and that of the surroundings. It was also found that the impact of UE lessened as the ambient temperature increased, especially at a higher
and
. As a result of this, the amount of transferred heat flow dropped.
In the current test, considering various discussed parameters, UE had the strongest influence on heat flow (70.11%) when and . On the other hand, the lowest (9.31%) was associated with the case in which and .
4.4. The Impact of UE on Nusselt Number
As shown in
Figure 11,
Figure 12,
Figure 13,
Figure 14 and
Figure 15, the current test focused on the impact of UE on the Nusselt number, and the figures show its variation against
. The test covered the ranges of
and
, and
.
As can be seen, the number, regardless of the presence of UE, increased as increased, and this was because an enhancement in the velocity led to an increase in the coefficient of convection heat transfer. As ultrasonic was imposed on the test case, there was an overall enhancement in the variations of the Nusselt number. To be precise, the impact of UE was more dominant when the case was operating at a lower s. The most significant case was when and , and in this case, the variation percentage was 76.98%, while the least (with 10%) was when and . Furthermore, at a lower s, the vibration could significantly affect the mixture of the boundary layers on the fines.
5. Conclusions
In the current experimental study, an attempt was made to study the effects of ultrasonic excitation on the rate of convection heat transfer in a louvered FTHE. An experimental system was designed and made to help understand the influence of various engineering parameters, such as the air passing velocity, ambient temperature, Nusselt number, and Reynolds number. The findings can be expressed as follows:
It was found that enhancing the flow rate had a negative effect on the UE’s impact on heat transfer enhancement in this type of HE.
Increasing the velocity of the air passing over the HE generally increased heat transfer; however, it undermined the presence of ultrasonic excitation.
With an increase in the surrounding temperature, the temperature difference between the running water and air passing the fins increased, and this also adversely affected the ultrasonic excitation’s imposition.
In the current experimental conditions, the highest increase in heat transfer was equal to 70.11%, recorded with Re = 2166, an ambient temperature of 25 °C, and an air velocity of 0.1 m/s.
It should be noted that ultrasonic excitation, in addition to improving heat transfer, can also result in the continuous cleaning of equipment and a reduction in maintenance costs.