1. Introduction
Heat exchangers facilitate the efficient transfer of heat from one medium to another. Shell and tube H.Xs are being used broadly in most industrial applications, including energy conversion, evaporators, condensers, heating, cooling, ventilation, and power utility systems. A number of goals have been pursued by researchers, including increasing fuel and energy efficiency, decreasing heat transmission times, lowering the size, weight, and cost of heat exchangers, and eliminating energy losses. A heat exchanger’s performance may be increased by a number of techniques, including the use of microchannels and fins. The ability to transport heat can also be improved by making the working fluid more thermally conductive [
1]. When comparisons are made to the thermal conductivity (k) of solids, the fluids that used to be used for the transmission of heat such as water, motor oil, vegetable oil, paraffin oil, propylene glycol, ethylene glycol, etc., have poor thermal conductivities [
2]. A base fluid’s k can be raised through the mixing of some highly thermally conductive solid particles. Recently, modifying the heat transmission characteristics of suspensions by the use of nano-sized particles has drawn interest. Nanofluids are stable suspensions of particles in traditional heat transmission fluids that are less than 100 nm in size. When compared to other suspensions, nanofluids exhibit superior stability, a very high k level, and no additional pressure loss, making them a viable option for engineering applications. Research has been conducted on the k of nanofluids, as it is one of the most crucial factors for improving heat transmission. Every experiment’s outcome has shown that the inclusion of nanoparticles increases heat conductivity [
3].
Li and Xuan conducted multiple experimental studies on the heat transmission and flow properties of cupric oxide nanofluids. The trials were conducted in a linear conduit with a consistent thermal boundary condition. Several researchers conducted their studies under two separate flow regimes, namely laminar and turbulent flow conditions [
4,
5]. A comprehensive investigation by R. Subramanian et al. revealed that a heat transmission increase of 5–25% was obtained using the nanofluids of TiO
2 nanoparticles, respectively. The results of the study demonstrated a significant connection between heat transmission enhancement, mass flow rate, and nanofluid volume concentration. Because the surface area was increased by the nanoparticles, the heat transfer rates improved [
6]. Farajollahi et al. performed an experimental assessment of heat transmission in a shell and tube H.X by dispersing CO
2 nanoparticles and Al
2O
3 nanoparticles in water. The examination revealed that the h of the nanofluids containing Al
2O
3-water and TiO
2-water rose by 19 to 56% and 18 to 56%, respectively, at 0.3 to 2% concentrations [
7,
8]. The impact of the concentration and proportion of nanoparticles on heat transmission performance was examined in S. Anitha’s research employing a shell and tube H.X and Al
2O
3-Cu hybrid nanofluids dispersed in water. The results concluded that the h and the Nusselt number (Nu) increased steadily as the concentration was raised; there was a noteworthy 139% increase in h when compared to water and a 25% increase when compared to Cu/water nanofluids [
9].
An extensive literature [
4,
5,
6,
7,
8,
9] exists regarding heart transfer assessments for various heat exchangers using different working fluids with various concentrations of nanoparticles. There is no research article available for finding U, Reynolds number (Re), h, and k using the LMTD method for a shell and tube H.X using water-based Al
2O
3-γ nanofluids with concentrations of 0.11%, 0.22%, and 0.34% for counter flow. Therefore, the purpose of this study is to determine the thermal performance of a shell and tube H.X using an Al
2O
3-γ nanofluid with different concentrations in counter flow configuration. Nano-particles of 12 nm of size and 99% purity are used in this study.
By examining the performance of nanofluids in a shell and tube H.X under novel operating circumstances and of low-concentration Al2O3-γ nanoparticles distributed in water, this work aims to close the knowledge gap identified in earlier studies.
3. Results and Discussion
The thermal behavior of water and water-based nanofluids at various concentrations and flow rates was investigated. The findings showed that a higher k of the alumina oxide nanoparticles led to increases in the K of 26%, 44%, and 58% at nanoparticle concentrations of 0.11%, 0.22%, and 0.34%, respectively. The higher density of the nanoparticles added mass without significantly changing volume, and this increased the viscosity by 16%, 33%, and 44% at the same concentrations. The increased K of nanofluids requires less heat energy for a given temperature, and this resulted in a decrement of heat capacity of 24%, 67%, and 107%. The relation of U and concentrations is shown in
Figure 3.
The U showed that different nanoparticle concentrations significantly improved heat transmission efficiency. Due to enhanced k and fluid dynamics, at a 0.11% nanofluid concentration, U increased by almost 16% when compared to water. U increased by over 33.33% at a concentration of 0.22%, indicating the ideal trade-off between fluid characteristics and nanoparticle dispersion to maximize heat transmission. Nevertheless, U only increased by 10% at a concentration of 0.34%, indicating diminishing returns brought on by rising fluid viscosity. The relation between convective h and concentrations is shown in
Figure 4.
Nanoparticle loading increased the heat exchanger convective heat transfer by 24.6% and 48% at 0.11% and 0.22% concentrations. The improvement was only approximately 14%, though, at 0.34% due to the increased viscosity, which adversely affects both heat transfer efficiency and fluid dynamics.
There were similar trends in the heat transfer rate as heat transmission increased by around 16% and 30%, respectively, at the 0.11% and 0.22% nanofluid concentrations as compared to water. At a 0.22% concentration, the nanoparticles were most uniformly dispersed throughout the base fluid, providing the highest surface area for heat transmission. The nanofluid’s stability was probably at its peak around 0.22%, which maintains the fluid’s consistent thermal characteristics and inhibits particle settling. Improved k results from this optimum dispersion also improved the interaction between the fluid and the nanoparticles. For experimental (U) and theoretical (h) values, the deviation of the volumetric concentration of 0.22% and water was noted as 38.81% and 22%, respectively. Alumina oxide nanoparticle addition resulted in improved heat transfer performance, as seen by the rising trends in both U and h with the nanofluid concentration. The relationship between the U and the flow rate at various concentrations and water is seen in
Figure 5.
Figure 5 illustrates the effect of the alumina oxide nanoparticles’ volume percentage and the flow rate on the total h. It shows a notable improvement in the h between a 6 and 10 L/min flow rate; for 6 L/min, there was a 14.2% increase at 0.11%, a 33.57% increase at 0.22%, and at 0.34% the increase was only 5.7%. Similarly, at 8 L/min and 0.11% the increase was 19%, at 0.22 the increase was 36%, at a 10 L/min flow rate the increase was 14.2% at 0.11,% and at 0.22% it was 23.8%. When compared to water, the Al
2O
3–H
2O nanofluid demonstrated about a 33% increase in U at the best concentration of 0.22%. The improved performance is attributed to the nanofluid’s higher thermophysical properties compared to water, and also the high conductivity and stability of the fluid. The relation between the LMTD and the Reynold number at various volumes and water is shown in
Figure 6a.
Figure 6a revealed that as the Re number decreased with higher nanoparticle concentrations, the LMTD tended to increase. This is evident from the LMTD values as shown in
Figure 6a; the observed decrease in the Re number with increasing nanoparticle concentration in nanofluids was influenced by changes in fluid viscosity, altered flow characteristics, and the transition towards laminar flow regimes. An inverse relationship between the LMTD and the Reynolds number was observed and the results are aligned with the study [
13]. Similarly, from
Figure 6b it is observed that the Nu numbers tended to increase as the Re numbers increased, which represents the enhanced h due to the thinning of the thermal boundary layer and the increased flow rate of the fluid which incremented the Re number and increased the k. The hydrodynamic boundary layer developed on low flow rates or low Reynolds numbers, and the region was equal to 2/3 of the tube length. Similarly, the thermal boundary layer thicknesses at concentrations of 0.11% were 0.32 mm, 0.275 mm, and 0.24 mm, respectively, at flow rates of 6, 8, and 10 LPM. This indicates that increased turbulence and mixing caused the thicknesses of the boundary layer to drop with the flow rate. The comparable thicknesses for a concentration of 0.22% were 0.37 mm, 0.323 mm, and 0.2875 mm, which continued the pattern of decreasing thickness as flow rates increased. The thicknesses were 0.438 mm, 0.375 mm, and 0.334 mm at the maximum concentration of 0.34%. These values decreased with the flow rate, but they were still greater than at lower concentrations because of the increased viscosity that hindered heat transmission and fluid movement. Distilled water consistently had lower boundary layer thicknesses than nanofluids, measuring 0.274 mm, 0.268 mm, and 0.209 mm at the same flow rates. This indicates that nanofluids have greater heat transmission capacities even if their viscosity is higher. Increasing the flow velocity generally results in a thinner thermal boundary layer and improves heat transfer. However, increased concentrations of nanoparticles thickened the boundary layer by increasing viscosity and boosting K simultaneously. As the concentrations increased, it led to a decrease in the Prandtl number due to a decrease in the heat capacity and an increase in the k, as the Prandtl number is dependent on the k. As the Prandtl number increased, it lead to the thinning of the boundary layer, and when the Prandtl number decreased, the boundary layer became thick. These trends are in line with these studies [
15,
16]. It was discovered that 0.22% was the best concentration for maximizing heat transfer, balancing increased thermal characteristics with controllable viscosity.
4. Conclusions
This study was conducted to evaluate the thermal behavior of a shell and tube H.X using water and nanoparticles at different concentrations, and it was noted that every property of the nanofluids provided better thermal conductivity (k) than distilled water. The k was improved by 26%, 44%, and 58% with nanoparticle concentrations of 0.11%, 0.22%, and 0.34%. The viscosity increased with the nanoparticle concentration but offset the thermal benefits at the highest concentration of 0.34%. It was noted that the U reached its maximum enhancement when the nanoparticle concentration was at its highest at 0.22%, where the U increased by over 33.33%, and at a 0.22% concentration, the h was 48% higher than the distilled water concentration. These findings show that nanoparticle loading enhances H.X convective heat transfer by 0.22%. Similarly, the also had the same characteristics enhanced with the highest value at a 0.22% concentration. By using up to this concentration of nanofluids, the was raised to about 30% when compared to the use of water, implying the effectiveness of dilated heat transmission with the help of nanofluids. The results showed that the U and h were most improved at 8 and 10 L/min flow rates, respectively, when the flow rate was increased. It was observed that the LMTD values were higher with higher concentrations of nanoparticles because as the Re number decreased, it resulted in laminar flow due to the viscosity of the fluid demonstrating being enhanced. The thermal boundary layer thicknesses at a concentration of 0.11% were 0.32 mm, 0.275 mm, and 0.24 mm, respectively, at flow rates of 6, 8, and 10 LPM. This indicates that increased turbulence and mixing caused the thicknesses of the boundary layer to drop with the flow rate. The comparable thicknesses for a concentration of 0.22% were 0.37 mm, 0.323 mm, and 0.2875 mm, which continued the pattern of decreasing thickness as flow rates increased.