Assessment of the Visual Impact of Existing High-Voltage Lines in Urban Areas
Abstract
:1. Introduction
2. Environmental Impact of Overhead Power Lines
3. Methodology to Evaluate the Visual Impact of Overhead Power Lines
3.1. The Overall Aesthetic Impact Value
3.2. Quality of the Landscape
3.3. Visual Impact
Visibility Indicator
3.4. Color Indicator
3.5. Climatology Coefficient
3.6. Fragility Indicator
4. Impact of the Observation Angle on the Visibility Index
5. Application Case and Comparison with Previous Results
- the 110 kV transmission line Can Jardí-Collblanc (R1), located at the Avinguda Pep Ventura;
- the 220 kV transmission line Can Jardí-Sant Andreu-Canyet (R2), located at the turnaround Avinguda Electricitat and Passeig de les Torres; and
- the 220 kV transmission line Foix-Mas Figueres (R3), located in the zone Can Fatjó.
6. Conclusions
Author Contributions
Funding
Institutional Review Board Statement
Informed Consent Statement
Data Availability Statement
Conflicts of Interest
References
- Sumper, A.; Boix-Aragonés, O.; Villafáfila-Robles, R.; Ramírez-Pisco, R. Methodology for the assessment of the impact of existing high voltage lines. Energy Policy 2010, 38, 6036–6644. [Google Scholar] [CrossRef]
- Sumper, A.; Ferreira, P. A New Open Access Journal. Electricity 2020, 1, 4. [Google Scholar] [CrossRef]
- Franken, M.; Schrief, A.B.; Barrios, H.; Puffer, R.; Moser, A. Co-optimization of multi-stage transmission expansion planning and grid operation. Electr. Power Syst. Res. 2020, 189, 106686. [Google Scholar] [CrossRef]
- Horst, D.V.d. NIMBY or not? Exploring the relevance of location and the politics of voiced opinions in renewable energy siting controversies. Energy Policy 2007, 35, 2705–2714. [Google Scholar] [CrossRef] [Green Version]
- Vajjhala, S.P.; Fischbeck, P.S. Quantifying siting difficulty: A case study of US transmission line siting. Energy Policy 2007, 35, 650–671. [Google Scholar] [CrossRef]
- Marshall, R.; Baxter, R. Strategic Routeing and Environmental Impact Assessment for Overhead Electrical Transmission Lines. J. Environ. Plan. Manag. 2002, 45, 747–764. [Google Scholar] [CrossRef]
- Rahman, K.A. Mediation and Mediator Skills: A Critical Appraisal. Available online: https://ssrn.com/abstract=3231684 (accessed on 1 February 2012).
- Cloquell-Ballester, V.-A.; Cloquell-Ballester, V.-A.; Monterde-Díaz, R.; San-tamarina-Siurana, M.-C. Indicators validation for the improvement of environmental and social impact quantitative assessment. Environ. Impact Assess. Rev. 2006, 26, 79–105. [Google Scholar] [CrossRef]
- Salci, S. A framework for assessing economic and environmental benefits from transmission line rehabilitation investments. Electr. J. 2018, 31, 75–81. [Google Scholar] [CrossRef]
- Bickel, P.; Friedrich, R. ExternE: Externalities of energy. Eur. Commun. 2005. Available online: https://op.europa.eu/en/publication-detail/-/publication/b2b86b52-4f18-4b4e-a134-b1c81ad8a1b2 (accessed on 29 July 2021).
- Doukas, H.; Karakosta, C.; Flamos, A.; Psarras, J. Electric Power Transmission: An overview of associated burdens. Int. J. Energy Res. 2011, 11, 970–988. [Google Scholar] [CrossRef]
- Nassauer, J.I. Landscape as medium and method for synthesis in urban ecological design. Landsc. Urban Plan. 2012, 106, 221–229. [Google Scholar] [CrossRef] [Green Version]
- Torres-Sibille, A.D.C.; Cloquell-Ballester, V.-A.; Cloquell-Ballester, V.-A.; Ramírez, M.Á.A. Aesthetic impact assessment of solar power plants: An objective and a subjective approach. Renew. Sustain. Energy Rev. 2009, 13, 986–999. [Google Scholar] [CrossRef]
- Torres-Sibille, A.D.C.; Coloquel-Ballester, V.-A.; Coloquell-Ballester, V.-A.; Darton, R. Development and validation of a multicriteria indicator for the assessment of objective aesthetic impact of wind farms. Renew. Sustain. Energy Rev. 2009, 13, 40–66. [Google Scholar] [CrossRef]
- Hadrian, D.R.; Bishop, I.D.; Mitcheltree, R. Automated Mapping of visual impacts in utility corridors. Landsc. Urbaaestheticng 1988, 16, 261–282. [Google Scholar] [CrossRef]
- Luken, J.O.; Hinton, A.C.; Baker, D.G. Forest edges associated with power-line corridors and implications for corridor siting. Landsc. Urban Plan. 1991, 20, 315–324. [Google Scholar] [CrossRef]
- Tempesta, T.; Vecchiato, D.; Girardi, P. The Landscape benefits of the burial of high voltage power lines: A study in rural areas of Italy. Landsc. Urban Plan. 2014, 126, 53–64. [Google Scholar] [CrossRef]
- Frontuto, V.; Corsi, A.; Novelli, S.; Gullino, P.; Larcher, F. The visual impact of agricultural sheds on rural landscapes: The willingness to pay for mitigation solutions and treatment effects. Land Use Policy 2020, 91, 104337. [Google Scholar] [CrossRef]
- Wagner, J. Methodology of Environmental Impact Assessment for Evaluating Existing Overhead Lines. Master’s Thesis, Universitat Politècnica de Catalunya, Barcelona, Spain, 2011. [Google Scholar]
- Antrop, M. Why landscapes of the past are important for the future. Landsc. Urban Plan. 2005, 70, 21–34. [Google Scholar] [CrossRef]
- Senetra, A.; Wasilewicz-Pszczółkowska, M.; Grzelak-Kostulska, E. The European landscape convention as a Tool for the protection, management and planning of landscapes. Barom. Reg. 2015, 3, 81–88. [Google Scholar]
- Schripke, U.; Zoderer, B.M.; Tappeiner, U.; Tasser, E. Effects of past landscape changes on aesthetic landscape values in the European Alps. Landsc. Urban Plan. 2021, 212, 104109. [Google Scholar] [CrossRef]
- Sevenant, M.; Antrop, M. Cognitive attributes and aesthetic preferences in assessment and differentiation of landscapes. J. Environ. Manag. 2008, 90, 2889–2899. [Google Scholar] [CrossRef] [PubMed]
- Amat, J. Metodologia d’avaluació de l’impacte Visual de les línies d’alta Tensió Existents. Master’s Thesis, Univeristat Politècnica de Catalunya, Barcelona, Spain, 2014. [Google Scholar]
- CITCEA-UPC. Estudi Sobre l’impacte de les Linies de Tensió Superior o Igual a 66 kV en les àrees Urbanes de Rubí; CITCEA-UPC: Barcelona, Spain, 2004. [Google Scholar]
Strength of the Impact | Indicator Value |
---|---|
Strong impact | 1 |
Medium impact | 0.75 |
Light impact | 0.25 |
No impact | 0 |
Climatology | Climatology Value mi |
---|---|
Clear day | 1 |
Cloudy day | 0.75 |
Precipitation | 0.5 |
Fog | 0.25 |
Strength of the Impact | Indicator Value |
---|---|
Strong impact | 1 |
Medium impact | 0.75 |
Light impact | 0.25 |
No impact | 0 |
Num. of Pixels | −45° | 0° | |||||
Photograph | Pylon | Cables | Photograph | Pylon | Cables | ||
HORIZONTAL | 1 h | 13,996,800 | 718,094 | 3,701,337 | 13,996,800 | 907,989 | 1,648,112 |
1.5 h | 13,996,800 | 340,411 | 2,520,078 | 13,996,800 | 451,266 | 1,822,646 | |
2 h | 13,996,800 | 196,106 | 1,781,716 | 13,996,800 | 260,529 | 1,863,753 | |
2.5 h | 13,996,800 | 133,522 | 1,229,322 | 13,996,800 | 168,982 | 1,881,785 | |
Num. of Pixels | −45° | 0° | |||||
Photograph | Pylon | Cables | Photograph | Pylon | Cables | ||
VERTICAL | 1 h | 13,996,800 | 684,329 | 2,838,625 | 13,996,800 | 928,726 | 3,168,071 |
1.5 h | 13,996,800 | 337,139 | 2,006,036 | 13,996,800 | 488,690 | 3,649,559 | |
2 h | 13,996,800 | 201,857 | 1,446,967 | 13,996,800 | 278,209 | 3,264,157 | |
2.5 h | 13,996,800 | 140,260 | 1,045,124 | 13,996,800 | 185,107 | 3,002,302 |
% | −45° | 0° | 45° | 90° | |||||
Pylon | Cables | Pylon | Cables | Pylon | Cables | Pylon | Cables | ||
HORIZONTAL | 1 h | 5.130 | 26.444 | 6.487 | 11.775 | 5.759 | 21.194 | 2.796 | 28.922 |
1.5 h | 2.432 | 18.005 | 3.224 | 13.022 | 2.860 | 18.780 | 1.296 | 20.636 | |
2 h | 1.401 | 12.729 | 1.861 | 13.316 | 1.718 | 15.475 | 0.762 | 16.130 | |
2.5 h | 0.954 | 8.783 | 1.207 | 13.444 | 1.145 | 11.981 | 0.528 | 13.023 | |
% | −45° | 0° | 45° | 90° | |||||
Pylon | Cables | Pylon | Cables | Pylon | Cables | Pylon | Cables | ||
VERTICAL | 1 h | 4.889 | 20.281 | 6.635 | 22.634 | 5.932 | 19.387 | 2.800 | 21.557 |
1.5 h | 2.409 | 14.332 | 3.491 | 26.074 | 2.800 | 13.991 | 1.186 | 15.414 | |
2 h | 1.442 | 10.338 | 1.988 | 23.321 | 1.744 | 10.523 | 0.756 | 12.000 | |
2.5 h | 1.002 | 7.467 | 1.322 | 21.450 | 1.147 | 8.290 | 0.533 | 9.857 |
−45° | 0° | 45° | 90° | ||||||
---|---|---|---|---|---|---|---|---|---|
Pylon | Cables | Pylon | Cables | Pylon | Cables | Pylon | Cables | ||
H vs. V | 1 h | 3.64 | −3.33 | −1.66 | −2.31 | −2.24 | 0.00 | −0.11 | 0.00 |
1.5 h | 0.75 | 0.00 | −6.48 | 0.00 | 1.64 | 0.00 | 6.05 | 0.00 | |
2 h | −2.12 | 9.11 | −5.12 | 0.00 | −1.16 | 8.16 | 0.46 | 1.30 | |
2.5 h | −3.32 | 10.46 | −6.65 | 0.00 | −0.11 | 19.91 | −0.51 | 11.68 |
Differences to 0° in % | |||||||
0° and −45° | 0° and 45° | 0° and 90° | |||||
Pylon | Cables | Pylon | Cables | Pylon | Cables | ||
HORIZONTAL | 1 h | 16.16 | 0.99 | 8.47 | −2.31 | 47.87 | −2.31 |
1.5 h | 19.84 | 0.00 | 9.01 | 0.00 | 49.99 | 0.00 | |
2 h | 18.97 | −1.60 | 5.87 | 0.00 | 46.15 | 0.00 | |
2.5 h | 14.78 | 17.92 | 3.62 | 1.38 | 40.12 | 0.00 | |
Differences to 0° in % | |||||||
0° and −45° | 0° and 45° | 0° and 90° | |||||
Pylon | Cables | Pylon | Cables | Pylon | Cables | ||
VERTICAL | 1 h | 20.54 | 0.00 | 7.95 | 0.00 | 48.67 | 0.00 |
1.5 h | 25.28 | 0.00 | 15.94 | 0.00 | 55.87 | 0.00 | |
2 h | 21.29 | 9.11 | 9.42 | 8.16 | 49.01 | 1.30 | |
2.5 h | 17.45 | 26.50 | 9.54 | 21.01 | 43.57 | 11.68 |
Differences to −45° in % | ||||
45° and −45° | 90° and −45° | |||
Pylon | Cables | Pylon | Cables | |
HORIZONTAL | −9.18 | −3.33 | 37.82 | −3.33 |
−13.51 | 0.00 | 37.61 | 11.58 | |
−16.18 | 0.00 | 33.54 | 1.58 | |
−13.10 | −20.15 | 29.73 | −21.83 | |
Differences to −45° in % | ||||
45° and −45° | 45° and −45° | |||
Pylon | Cables | Pylon | Cables | |
VERTICAL | −15.84 | 0.00 | 35.41 | 0.00 |
−12.50 | 0.00 | 40.94 | 0.00 | |
−15.08 | −1.04 | 35.22 | −8.59 | |
−9.59 | −7.47 | 31.64 | −20.17 |
Differences to 45° in % | ||||
45° and −45° | 45° and 90° | |||
Pylon | Cables | Pylon | Cables | |
HORIZONTAL | 8.41 | 3.22 | 43.05 | 0.00 |
11.90 | 0.00 | 45.04 | 0.00 | |
13.92 | 0.00 | 42.80 | 0.00 | |
11.58 | 16.77 | 37.87 | −1.40 | |
Differences to 45° in % | ||||
45° and −45° | 45° and 90° | |||
Pylon | Cables | Pylon | Cables | |
VERTICAL | 13.67 | 0.00 | 44.24 | 0.00 |
11.11 | 0.00 | 47.50 | 0.00 | |
13.11 | 1.03 | 43.71 | −7.47 | |
8.75 | 6.95 | 37.62 | −11.81 |
(I vis) Pep Ventura R1 | |||
---|---|---|---|
Angle | Distance | Pylons | Cables |
0° | 1.5 h | 0.512 | 0.908 |
(I vis) Av. Electricitat R2 | |||
---|---|---|---|
Angle | Distance | Pylons | Cables |
0° | 1.5 h | 1.000 | 1.000 |
(I vis) Can Fatjó R3 | |||
---|---|---|---|
Angle | Distance | Pylons | Cables |
0° | 1.5 h | 0.607 | 1.000 |
Indicator | 27 OAIV 1 | ||||||
---|---|---|---|---|---|---|---|
Index | β | Color | Visibility of Pylons | Visibility of Wires | Quality | Fragility | Total |
R1 | 0.827 | 0.02 | 0.512 | 0.908 | 0.50 | 0.611 | 6.283 |
R2 | 0.827 | 0.02 | 1.000 | 1.000 | 0.25 | 0.792 | 5.616 |
R3 | 0.827 | 0.02 | 0.607 | 1.000 | 1.00 | 0.639 | 14.480 |
The Methodology Used in [1] | Proposed Methodology | |||
---|---|---|---|---|
Index | Result | Ranking | Result | Ranking |
R1 | 6.24 | 2 | 6.283 | 2 |
R2 | 6.24 | 2 | 5.616 | 3 |
R3 | 18.72 | 1 | 14.480 | 1 |
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations. |
© 2021 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/).
Share and Cite
Sumper, A.; Boix-Aragones, O.; Rull-Duran, J.; Amat-Algaba, J.; Wagner, J. Assessment of the Visual Impact of Existing High-Voltage Lines in Urban Areas. Electricity 2021, 2, 285-299. https://doi.org/10.3390/electricity2030017
Sumper A, Boix-Aragones O, Rull-Duran J, Amat-Algaba J, Wagner J. Assessment of the Visual Impact of Existing High-Voltage Lines in Urban Areas. Electricity. 2021; 2(3):285-299. https://doi.org/10.3390/electricity2030017
Chicago/Turabian StyleSumper, Andreas, Oriol Boix-Aragones, Joan Rull-Duran, Joan Amat-Algaba, and Joachim Wagner. 2021. "Assessment of the Visual Impact of Existing High-Voltage Lines in Urban Areas" Electricity 2, no. 3: 285-299. https://doi.org/10.3390/electricity2030017
APA StyleSumper, A., Boix-Aragones, O., Rull-Duran, J., Amat-Algaba, J., & Wagner, J. (2021). Assessment of the Visual Impact of Existing High-Voltage Lines in Urban Areas. Electricity, 2(3), 285-299. https://doi.org/10.3390/electricity2030017