The hourly monitored data used for the base case (BC) were collected from the building automation system (BAS), supplemented by information from the equipment suppliers, the Central Weather Bureau of Taiwan and also the local power company for the year 2012.
2.2.1. Energy Analysis
The cooling capacity
(kW) of a chiller can be calculated as:
In Equation (1),
is the chilled water flowrate.
and
are the chilled water temperatures flowing in and out through the evaporator, respectively. The specific heat capacity of water
= 4.186 kJ·kg
−1·K
−1.
Figure 2 shows that there is more than one chiller for each system. The average coefficient of performance
of the chillers for either the general or the 24-h systems can be calculated using Equation (2):
In Equation (2), k is the number of chillers, and j is each of the operating hour in a year. is the compressor of the acting chiller in the hour. In times of lower cooling demand, only one chiller would be operating.
The operating power (kW) of a pump, either for a chilled water pump or a condensing water pump, can be calculated by using Equation (3):
where
is the volume flow rate m
3·s
−1 and
is the pressure jump (Pa) though the pump. The total power consumption of an air-conditioning system can be calculated as in Equation (4):
In Equation (4),
,
,
,
and
are respectively the power load of chilled water pumps, condensing water pumps, air handling units (AHU) or fan coils (FC), chillers and cooling towers. In this study, a system performance factor (SPF) for the entire system can be expressed as Equation (5):
is the cooling capacity of the air-conditioning system.
2.2.2. Exergy Analysis
Kummel [
36] relates the second law to economics. Exergy can be taken as the flow availability of a system that performs the maximum reversible work. Regarding the scope of this study, the kinetic and the potential work can be neglected. Hence, exergy can be expressed as H − H
0 − T
0(S − S
0), where H is the enthalpy and S is the entropy of the respective states. T
0(S − S
0) is the entropy generation term or exergy destruction against the dead state. Sayyaadi and Neiatolahi [
19] stated that a more convenient form of the exergy of a flowing system consists of a temperature component and a pressure component Ex = Ex
△T + Ex
△P. In this study the pressure component is neglected. The exergy of an air-conditioning system can be defined to be the maximum useful work attainable from a heat transfer process. Lu and Wu [
6] mentioned that in differential form, exergy can be expressed as in Equation (6):
Integrating from the given state (
) to the dead state (
), which is the ambient condition in this study, a general equation for calculating exergy rate
is obtained as in Equation (7):
In Equation (7),
is the refrigeration effect (kW),
T0 is the outdoor temperature (the reference environment temperature),
Tei is inlet chiller water temperature and
Teo is the outlet chiller water temperature. The thermodynamic second law efficiency (exergy efficiency) can be expressed as Equation (8):
In this study, the total exergy destruction rate is the sum of the general and the 24-h systems, as expressed in Equation (9):
where
and
.
,
and
are the exergy destruction rate for the total, the 24-h system and the general air-conditioning system, respectively.
2.2.3. Thermoeconomic Analysis
The thermoeconomic analysis has to consider the construction cost, amortization, maintenance and electricity consumption. In this study, the total revenue requirement levelization (TRRL) method was applied. In this study, the TRRL method takes into account the estimated total carrying charge, along with assumptions for economic, financial and market input parameters calculated on a yearly basis. Moreover, the non-uniform annual monetary values of the carrying charges, maintenance cost and electricity cost are levelized and converted to an equivalent series of constant payments (annuities) [
37].
TRRL can be computed as in Equation (10):
In Equation (10), CRF is the capital recovery factor.
is the total revenue requirement in the
j-th year of system operation, and
is the interest rate (%). In applying Equation (10), each monetary transaction is assumed to occur at year end. The capital recovery factor
is calculated by Equation (11):
In Equation (11), n is the economic lifetime in years. The series of payments of the annual electrical cost
can be calculated using Equation (12):
In Equation (12),
is the constant escalation. The levelized value
can then be determined multiplying the first year electricity cost
(NT) by the constant escalation levelization factor (CELF) as Equation (13):
In Equation (13),
. The terms
and
are respectively the annual escalation rate of electricity cost and the capital recovery factor.
can be computed by Equation (14):
In Equation (14), Celect is the electricity price per kWh in Taiwan taken as 3.1 NT/kWh. The total annual electric consumption (kWh) includes that of the chiller water pump (Epu, ch), condensing water pumps (Epu, cd), air side equipment (EAHU, FC), such as air handling units (AHU) and fan coils (FC), water chillers (Ech) and cooling towers (ECT).
The levelized annual operating and maintenance costs OMC
L are given in Equation (15):
where
, and the term
is a constant representing the nominal escalation rate for the operating and maintenance costs.
The economic operating lifetime of the system is taken to be 15 years. Therefore, the magnitude of the economic constant, such as , and are taken to be 0.02, 0.03 and 0.03, respectively, in the analysis.
For the air-conditioning system, the annual total revenue requirement levelization (TRRL) is equal to the sum of the carrying charge levelization (CCL), electricity costs levelization (ECL) and operating and maintenance cost levelization (OML), as shown in Equation (16):
The levelized cost rate of the total revenue requirement can be calculated by Equation (17):
In Equation (17), is the hourly cost of the total revenue requirement levelization. The hourly rates of CCL and ECL are to be calculated separately for the general and the 24-h systems. The annual operating hours of the 24-h and the general systems, and , are 8784 h and 4870 h, respectively, according to the actual operation of the train station.
In this study, the reduction of carbon dioxide (CO
2) emissions due to energy saving was estimated. The emission of carbon dioxide per kWh of electricity used given by Taipower [
38] for the year of 2012 was 0.522 kg/kWh.
2.2.4. Empirically-Based Performance Models of Equipment
The energy performance models of chillers refer to Lee
et al. [
29] and Jiang and Reddy [
30]. The regression models of the chillers and pumps are fitted using data provided by equipment suppliers. These models are used in thermoeconomic and exergy analysis in this study. Prediction of chiller COP refers to the modified Gordon-Ng universal model proposed by Jiang and Reddy [
30]. The model considers the refrigerant flow rate that may change the internal entropy production in the compressor. The independent variables of chiller COP are then the cooling load ratio
, evaporator outlet temperature
and condenser inlet water temperature
. The functional form of the model is shown in Equation (18):
In Equation (18), the regression constants β1–β4 are determined by regressing the performance data provided by equipment suppliers.
Similarly, the power consumption of chilled water pumps and condensing water pumps
can be expressed in regression form, as shown in Equation (19):
The independent variable is only the volumetric flow rate , whether of the chilled water or the condensing water. The regression constants α1–α3 are determined by regressing the performance data provided by equipment suppliers.
2.2.5. Multi-Objective Optimization
The two objective functions studied are the economic and thermodynamic objective functions shown in Equation (20) and Equation (21):
The multi-objective optimization refers to the method of the Pareto optimal frontier [
39]. In Equations (20) and (21),
and
are the minimum and maximum values of
in the Pareto frontier, similarly for
and
.
=
and
=
correspond to the limits of economic and thermodynamic optimization. When Equations (20) and (21) are separately used in single objective optimization,
and
would lies between 0 and 1.
In this study, the decision variables of selecting chillers are:
- (1)
Using screw or centrifugal compressors, constant or variable speed drive.
- (2)
The operating refrigeration capacity.
- (3)
The coefficient of performance (COP).
- (4)
Inlet/outlet chilled water and condensing water temperatures.
- (5)
The cost of chillers.
Similarly, the decision variables of selecting pumps are:
- (1)
Pumps with constant speed drive or variable speed drive.
- (2)
The efficiency of pumps.
- (3)
The pump pressure and water volumetric flow rate (m−3·s−1).
- (4)
The cost of pumps.
Three optimization cases are compared to the base case, with the operating parameters described in
Table 1 and
Table 2. The three cases are namely cost consideration (CC), thermodynamic efficiency (TE) and multiple objectives of efficiency and cost (MO). The operation constraints of the 24-h and the general air-conditioning systems are listed in
Table 1 and
Table 2. Constraints of these decision variables are partly the limitations emanating from the technical data of equipment suppliers. For the general system, the total chilled water flow rate is 4032 kg/min (equivalent to liters per minute (lpm) for water) and is 1210 kg/min for the 24-h system. It is noted that the variable frequency drive (VFD) is applied to the chillers and pumps in Case TE and Case MO. VFD systems general cost more, but it would better match the cooling demand and the overall operation of the system.