5.1. Verification of the Analytical Models
To verify the analytical models proposed in
Section 2 and
Section 3, an experiment was carried out on a 30 kA CT sample, whose parameters are shown in
Table 5. A four-meter-long primary bus-bar was passed through the center of the CT ring. The returning conductor of the primary bus-bar was utilized as an interfering adjacent bus-bar, and the adjacent distance c was set to 1.2 m. The shielding coil position
β was set to 0°. The secondary winding of the CT was shorted out by an ampere meter.
The main difficulties of the experiment are:
Implementing a large sinusoidal current in the bus-bar;
Powering the high-power circuit;
Sustaining the large current for a few minutes.
To realize a large current, a six-turn bus-bar was used, as presented in
Figure 9a. Therefore, the current in each copper bar is reduced to one-sixth of the total bus-bar current.
To lower the capacity requirement of the power source, reactive compensation was applied by connecting a 0.053 μF capacitor in series with the bus-bar. The whole circuit was connected to the secondary winding of a 380:8 transformer, and the primary winding of the transformer was powered by a 150 kVA, 0–220 V voltage regulator.
The sinusoidal flux in the CT core can be measured by enwinding a coil onto the CT and detecting the terminal voltage of the coil. However, as the voltage regulator cannot work under heavy-load conditions for long, the measurement should be taken quickly. To improve the measuring efficiency, a total of 30 uniformly distributed coils were enwound on the CT beforehand, as shown in
Figure 9b. Every end of the coils was connected to a six-meter long wire, so the measurement of the coil voltage could be taken at a distance, preventing the strong magnetic field from influencing the voltmeters.
The first step of the experiment was to verify the coil leakage flux model. At this step, the shielding coil 3–3’ (wound from
θ = 180° to
θ = 270°) was selected as an interfering coil and was provided with a 0.1 A AC current. Meanwhile, the other shielding coils and the bus-bar were not electrified. At this moment, the dominant flux in the core was the leakage flux produced by the shielding coil 3–3’. The flux measured in the experiment, along with the FEM simulation result and the analytical result of the coil leakage flux, are plotted together in
Figure 10. It can be seen that the analytical curve coincides with the experimental curve, proving that the proposed coil leakage flux model defined by Equations (8) and (9) can accurately describe the leakage flux produced by a coil.
The next step was to verify the improved stray flux model. The bus-bar was powered with a 6000 ampere-turn AC current (1000 A for each copper bar), while all of the shielding coils were disconnected. When the circuit came into steady state, the flux in the core was approximately equal to the stray flux produced by the adjacent bus-bar.
The experimental result, the FEM-based simulation result and the analytical result of the stray flux are plotted together in
Figure 11. It was expected that with the correction factor
ks, the simulation and the analytical curves would be close to each other. However, the analytical curve turned out to be slightly weaker. This discrepancy is due to the limited length (4 m) of the bus-bar in the model. The connecting bars between the primary and the adjacent bars, which are only 2 m away from the CT, intensifies the stray flux in the core. As a result, the flux in the simulation model is slightly stronger (about 18% in this case) than the analytical model, where the connecting bars are considered to be at infinity. When the analytical curve is corrected by a factor (about 1.18 in this case), it becomes close to the experimental curve, proving that the proposed stray flux model is capable of calculating the stray flux.
The last step was to verify the shielding coil model. The shielding coils were connected in the “all parallel topology”, and then the bus-bar current was finally raised to 24 kA (4000 A for each copper bar). The measured in-core remnant flux and the coil currents were recorded for analysis.
The experimental results and the corrected analytical results of the remnant flux are plotted together in
Figure 12. It can be seen that for both the remnant flux and the coil currents, the shape of the analytical curve is very close to the experimental curve, which validates the coil leakage flux model proposed in this paper. However, obvious disparities between the three curves can still be observed. It is worth noting that the remnant flux is the difference between two significantly larger quantities: the stray flux and the leakage flux produced by the shielding coils. Therefore, even if the discrepancies between the analytical, simulation, and experimental results are relatively small in the two intensive fluxes, the discrepancies will become much more significant in the remnant flux. Additionally, the figure shows that the experiment results are close to the analytical results when 0° <
θ < 45°, and close to the simulation results when 45° <
θ < 110°, but according to the analysis above, this is more likely to be a coincidence.
The results of the coil currents are listed in
Table 6, showing that the analytical, simulation, and experimental results of the average coil currents are close to each other. In addition, the discrepancies between the currents of different segments are only observed in the experimental column. This is due to the inevitable deviations of the primary bus bar, the adjacent bus bar, and the shielding coils in the experimental setup. As the deviations are relatively small, they have very little influence on the flux and the average coil currents, but they do cause some extra circulating current and change the current distribution between the coils. However, they will not influence the general amplitude of the four coil currents.
5.2. Verification of the Optimal Shielding Coil Design
To verify the optimal shielding coil design for the three-phase scenario discussed in
Section 4, a second experiment was carried out on a 5 kA CT sample, whose parameters are shown in
Table 7. The 30 kA CT was substituted due to the difficulty in producing a set of three-phase 30 kA currents.
The experimental arrangement was similar to that of the first experiment. However, as the current in the three-phase experiment was lower, the number of turns of the bus-bar was reduced to 1. The adjacent distance c was set to 0.7 m, mirroring the case of a real 5 kA generator. A reactive compensation was applied by connecting a 3000 pF capacitor in parallel with the primary winding of the transformer. The arrangement was duplicated three times, to be the A, B, and C phases, respectively. The CT was installed on the B phase bus-bar, and the direction of the C phase bus-bar was defined as θ = 0°. As before, a total of 30 coils were enwound on the CT beforehand.
The shielding coil position β was set to 0° at first, and was then rotated to 45°. At each coil position, the shielding coils were connected in the “separated loop topology” and “all parallel topology” successively. Due to the limitation of the voltage regulators, the current of the bus-bars finally reached 4 kA.
The experimental and analytical results of the performance parameters are listed in
Table 8. Although all of the experimental values are higher than the corresponding analytical values, the regulation of the performance parameters is identical to the theoretical analysis: the
β = 0° shielding coils connected in the “separated loop topology” have the highest |
Φr|
max and the lowest
; The
β = 45° shielding coils connected in either way have the lowest |
Φr|
max and the highest
.
The result proves the validity of the conclusions given in
Section 4: setting
β to 45° minimizes the remnant flux intensity, and the core can maximally avoid saturation; setting
β to 0° and connecting the coils in the “separated loop topology” minimizes the temperature rise, and the CT is more unlikely to become overheated than in the other cases.