Next Article in Journal
Demand Response of Residential Houses Equipped with PV-Battery Systems: An Application Study Using Evolutionary Algorithms
Next Article in Special Issue
Evaluation of School Building Energy Performance and Classroom Indoor Environment
Previous Article in Journal
Preparation and Properties of Capric–Myristic Acid/Expanded Graphite Composite Phase Change Materials for Latent Heat Thermal Energy Storage
Previous Article in Special Issue
Energy Effects of Retrofitting the Educational Facilities Located in South-Eastern Poland
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Human Comfort-Based-Home Energy Management for Demand Response Participation

Division of Electrical and Biomedical Engineering, Hanyang University, Seoul 04763, Korea
Energies 2020, 13(10), 2463; https://doi.org/10.3390/en13102463
Submission received: 18 April 2020 / Revised: 5 May 2020 / Accepted: 11 May 2020 / Published: 14 May 2020
(This article belongs to the Special Issue Building Energy Audits-Diagnosis and Retrofitting)

Abstract

:
The residential building sector is encouraged to participate in demand response (DR) programs owing to its flexible and effective energy resources during peak hours with the help of a home energy management system (HEMS). Although the HEMS contributes to reducing energy consumption of the building and the participation of occupants in energy saving programs, unwanted interruptions and strict guidance from the system cause inconvenience to the occupants further leading to their limited participation in the DR programs. This paper presents a human comfort-based control approach for home energy management to promote the DR participation of households. Heating and lighting systems were chosen to be controlled by human comfort factors such as thermal comfort and visual comfort. Case studies were conducted to validate the proposed approach. The results showed that the proposed approach could effectively reduce the energy consumption during the DR period and improve the occupants’ comfort.

1. Introduction

A building energy management system (BEMS) measures, analyzes, reports, and optimizes the demand and supply of energy in a building for saving its energy and cost, and for realizing the occupant’s comfort [1]. As the BEMS can globally control the demand and supply of energy inside a building, it should be installed in green energy buildings to balance their energy generation and consumption. The BEMS can be integrated into both residential and non-residential buildings by focusing on the energy-saving potentials of these buildings [2].
Moreover, the BEMS can generate the profile of demand resources of the buildings for realizing their participation in demand response (DR) programs. The demand resources in DR programs are proactive resources that are assured by modifying the energy consumption pattern of occupants in the buildings. The energy saving accomplished by the occupants is considered as a form of energy resource and is traded in power markets by load aggregators. The load aggregators need to collect a quantity of demand resources from individual DR participants and provide the individuals with benefits of energy savings and economic profits from power markets [3]. The power markets and utilities take advantage of demand resources by reducing energy production and operational costs of the grid, and by improving the reliability of power systems through demand resources [4].
In industrial and commercial buildings, several electricity customers have participated in the DR programs with the help of BEMS, and they followed fixed building control strategies. Most of the occupants of these buildings were the general public, and therefore, services were provided to them via BEMS operation. In other words, the occupants did not have any authority to control the building, and they generally accepted the hierarchical control schedule of the buildings via energy management systems. Therefore, the energy management of these buildings was relatively simple and effective for participating in DR programs. However, the fast cut-off in these buildings can cause malfunction, failure, or life-shortening of mechanical and electrical equipment and their installations [5,6].
In contrast, household-level occupants found it difficult to participate in DR programs due to several barriers such as lack of individual smart infrastructures, home energy management systems (HEMS) and smart meters to monitor and control their appliances, technical mismatches among systems, and their small energy resource quantity [3]. However, aggregated demand resources of households are still attractive to utility operators and load aggregators, as these resources are flexible and effective during peak hours [7,8]. Several researchers have investigated HEMS algorithm for DR participation [9,10,11,12,13]. They formulated optimization problems to minimize the electricity cost of the households [9,10,11], physical and operational constraints of appliances [12], and the cost of energy and thermal discomfort [13]. These investigations focused on the generation of appropriate input scenarios for the households and their load scheduling.
Even though these algorithms allow the household occupants to participate in DR programs owing to the advanced logic and reasonable scheduling of households, it is not easy for them to allow unidirectional and formulated energy management. For example, a unidirectional HEMS oriented to the reduction of energy consumption causes inconvenience to occupants via unwanted interruptions or strict guidelines on the usage of building sub-systems such as washing machines, refrigerators, computers, rice cookers, electrical ovens, televisions, lighting fixtures, and other home appliances. Further, the occupants at home tend to actively interact with their energy management system and with its connected systems. Therefore, it is important to develop a bi-directional HEMS which follows the occupants’ behavioural patterns and their preferences for the usage of appliances and equipment to reduce their fatigue [13,14]. As one of the methods to preserve the user’s comfort and to reduce the peak load and electricity bill at smart homes, control algorithms of home appliances, renewables, electric vehicles, and energy storage system based on the quality of experience (QoE) were presented for the HEMS [15,16]. Even though these investigations did not consider the DR programs, the proposed algorithms may further cover the DR programs.
More specifically, building environmental conditions such as indoor/outdoor temperature, meteorological and thermal response characteristics of the building, as well as the occupants’ preferences should be considered to control a heating, ventilation, and air-conditioning (HVAC) system. While the operational response characteristic of the HVAC system is faster, the thermal response of the building is slower due to its slower thermal dynamics. It is considered to be one of the advantages of using the HVAC system as an important demand resource. This means that switching on/off the HVAC system does not directly influence the thermal satisfaction of occupants and thus, they have a relatively smaller amount of risks to participate in DR programs and to reply to DR events by using HVAC loads. In addition, the acceptable operating range of HVAC systems contributes to large energy savings owing to their relatively larger power capacity than that of small appliances in buildings. However, despite its potentials as a demand resource, there are few studies on the HVAC system for DR programs in residential buildings, whereas considerable effort has been devoted to this system in industrial and commercial buildings [14,17,18].
Apart from the occupant’s thermal comfort, visual comfort was also considered as an important environmental issue in buildings. For achieving low energy consumption and high thermal and visual comforts, natural lighting by using large glazing windows was investigated in different buildings [19,20,21,22]. The illuminance level, luminance, and glare indices affecting the visual comfort in these buildings were used as a control input of these buildings [22,23]. However, although much research on natural lighting in the analysis of building energy performance and visual comfort were conducted, there is still less study to apply the natural lighting to HEMS algorithms. As a related study by Li et al. [24] suggested a smart lighting control methodology integrated in a smart home control system to save energy consumption at home with respect to the design of lighting systems for buildings. They confirmed in detail the feasibility and the performance of the lighting control algorithm in the smart home control system. Owing to the effectiveness of the lighting system and the HVAC system for both energy management and user’s comfort, these systems should be prior-candidates integrated in the HEMS.
To maintain the satisfaction of occupants, HEMS implementing technologies are required to sense, monitor the environmental conditions and occupants’ individual data, store and reproduce the data as knowledge and information of the overall building system. As such, home appliances and equipment should finely be controlled by HEMS by considering the influence of the occupants’ preference and fatigue. They should be also considered as demand resources for the purpose of energy savings of the household during DR events. The contributions of this paper are highlighted as follows.
  • The human comfort factors including both thermal and visual comforts were integrated into the HEMS algorithm in this study. As mentioned above, the effectiveness of the lighting system and the HVAC system in terms of energy savings and user’s comfort have been confirmed in several investigations. However, there has rarely been the investigations dealing with both systems in different perspectives of energy savings and human thermal and visual comfort integrated into the HEMS.
  • To reduce the response fatigue of occupants and to slow down the negative effect of curtailment of appliances during DR events, an HVAC system was proposed as a prior demand resource in the household due to its slower thermal dynamics and higher power capacity than those of other appliances. The HVAC system was controlled to follow the DR events as well as the occupant’s thermal comfort in the household.
  • In addition to the occupants’ thermal comfort, a visual comfort-based-control algorithm for a dimming artificial lighting system using natural lighting was integrated into HEMS to improve the visual comfort and energy savings of the household.
  • Simulation case studies were performed using Matrix Laboratory (MATLAB)/Simulink® to verify the effectiveness of the proposed approach.
The rest of this paper is organized as follows. Section 2 suggests the comfort-based HEMS algorithm and the human comfort factors considered in the proposed algorithm. Section 3 describes a building integrated HEMS to present the thermal and visual dynamics of the building and its HVAC and lighting systems controlled by HEMS. Section 4 elaborates on case studies to test and validate the proposed approach. Finally, Section 5 draws the conclusions of this study.

2. Comfort-Based Home Energy Management System

2.1. Main Features of the Comfort-Based HEMS

The HEMS accomplishes the sensing, processing, monitoring, and reproducing of information to control the electric and thermal energy fluxes of the building by appropriately combining the operations of electrical and thermal appliances. In this study, human comfort factors such as the thermal and visual comforts were integrated into the HEMS algorithm. The thermal condition of the indoor environment was controlled by the predicted mean vote (PMV) and the predicted percentage of dissatisfied (PPD) values. The PMV-based control strategy of a heating system as an HVAC system was integrated into the proposed HEMS. Even though several metrics of user comfort were defined and proposed in the literature [15,16,25], this study only considered the PMV and PPD as the evaluation index of user’s thermal comfort in order to present that the suggested HEMS algorithm could be useful to control an HVAC system to participate in DR programs preserving user’s thermal comfort. Then, a dimmable light-emitting diode (LED) lighting system was applied to the proposed HEMS to efficiently use the daylight as a natural lighting and to satisfy the visual comfort of occupants. Illuminance inside a building was the factor that assessed the visual comfort of the occupants in this study.
The comfort-based control algorithm comprises the following sequences. At first, the presence of occupants was detected to assess the necessity of operation of heating/cooling and lighting systems. If any occupant was detected inside the target space, the PMV values were calculated. The thermal condition of the household was then controlled by the predefined ranges of the PMV values. Because the main idea of this study was the availability of the proposed HEMS algorithm during the occurrence of DR events, the acceptable ranges of the PMV values was adjusted and the control command signals of the heating/cooling system depended on these values. At the same time, the lighting system was controlled for the purpose of visual comfort and energy savings.

2.2. Thermal Comfort

Thermal comfort is defined as ‘the expression of mind that expresses satisfaction with the thermal environment‘, according to the American society of heating, refrigerating, and air-conditioning (ASHRAE) [26]. It is a personally determined sensation that has a large discrepancy among different people. It is also difficult to quantify the value and analyze it. Several researchers have investigated the parameters influencing thermal comfort and have developed models to express a common range of thermal comfort among people. Among the models, the PMV model introduced by Fanger is the most used model to assess thermal sensation of the human body with respect to the environment [25]. The thermal comfort was assessed by considering six parameters including the indoor air temperature, mean radiant temperature, relative humidity, air velocity, clothing, and metabolic rate of the occupant. As a result of the evaluation, PMV was obtained and PPD was expressed as a function of the PMV value as follows [27]:
P M V = [ 0.303 · exp ( 0.036 · M ) + 0.028 ] · L
P P D = 100 95.0 · exp ( 0.03353 · P M V 4 0.2179 · P M V 2 )
where M is the metabolic rate (W/m2) and L is the thermal load of the human body (W/m2). The PPD value is symmetric with respect to thermal neutrality, whereas the PMV value is zero. However, as shown in Equation (2), a minimum rate of dissatisfaction of 5% always exists. The index of the PMV is listed in Table 1. The PPD as a function of the PMV is depicted in Figure 1.
Acceptable ranges of PMV and PPD variations were defined by the ASHRAE, the European Committee for Standardization (CEN), and the International Organization for Standardization (ISO) [26,28,29,30,31]. ASHRAE Standard 55-2013 [26] indicates an acceptable thermal environment for general comfort. It recommends that the PPD is inferior by 10% and the PMV is between −0.5 and +0.5. This indicated that 10% of the people were dissatisfied [26,28]. The CEN Standard EN 15251 and ISO EN 7730 recommend four categories by prescribing a maximum PPD value for the body and the corresponding PMV range [29,30,31]. Category I commonly describes a high level of expectation for spaces occupied by very sensitive and fragile persons. Categories II and III explain a normal and moderate expectation, respectively. Category IV is applicable only for a limited period of the year. The first three recommended PPD and PMV ranges are listed in Table 2.
Based on the above recommended thermal comfort values in the standards, appropriate values of PMV and PPD could be selected to control the heating/cooling system of the building.

2.3. Visual Comfort

The European standard EN 12665 [32] defines the visual comfort as ’the subjective condition of visual well-being induced by the visual environment’. The visual environment inside a building is formed by both natural and artificial lighting. To immediately respond to an occupant’s visual demand, the visual comfort index should be easily measured for on-demand services. The quantity, quality, uniformity, and glare of light are the four main factors that evaluate the visual environment.
Among them, the value of the illuminance, which was found to be independent of the light source, was easily and immediately measured. The illuminance is a physical quantity, and is measured in lux (lx) at a point on a given surface by an illuminometer, an illuminance sensor, or by a smartphone that has an illuminance measurement application and its calibration algorithm. It is defined as the ratio between the luminous flux incident on an infinitesimal surface and the area of that surface. It has threshold values for each task or space inside a building. The illuminating engineering society (IES), the commission Internationale de I’Éclairage (CIE), the U.S. general services administration (GSA), the chartered institution of building services engineers (CIBSE), and most countries have their own recommended lighting levels [32,33]. An example of the recommended illuminance levels indicated in the illuminance recommendations [34] is listed in Table 3.

3. Building Integrated HEMS

3.1. Thermal Dynamics of the Building

Based on the first principle of thermodynamics, a heat balance of a building with a HVAC system could be developed based on the first principle of thermodynamics as follows [35]:
d U s t o r e d d t = Q ˙ H V A C Q ˙ e n v e l o p e
d U s t o r e d d t = C b u i l d i n g d T b u i l d i n g d t
Q ˙ H V A C = Q ˙ h e a t i n g Q ˙ c o o l i n g Q ˙ v e n t i l a t i o n
Q ˙ e n v e l o p e = 1 R b u i l d i n g ( T b u i l d i n g T o u t s i d e )
where U s t o r e d is the stored heat energy inside the building (J), Q ˙ H V A C is the heat flow (W) through the HVAC system including heating flow Q ˙ h e a t i n g (W), ventilation flow Q ˙ v e n t i l a t i o n (W), and cooling flow Q ˙ c o o l i n g (W). However, in heating mode of the HVAC system, the cooling flow Q ˙ c o o l i n g (W) is zero, while the heating flow Q ˙ h e a t i n g is zero in cooling mode of the system. Q ˙ e n v e l o p e is the heat loss (W) through the building envelope, C b u i l d i n g is the thermal capacitance (J/kg·°C) of the building, Rbuilding is the thermal resistance (°C/W) of the building Tbuilding  and T o u t s i d e are the indoor temperature and outdoor temperature (°C) of the building, respectively. Focusing on the control command of the HVAC system, the thermal dynamics of the building could be established as follows:
C b u i l d i n g d T b u i l d i n g d t = δ ( t ) Q ˙ H V A C 1 R b u i l d i n g ( T b u i l d i n g T o u t s i d e )
where δ ( t ) is the binary control command of the HVAC system. The conventional control strategy of the HVAC system is to follow the acceptable temperature range of the building. The control command of the system follows the temperature of the building, as depicted in Figure 2.
When the temperature was at the desired temperature, the system turned off. When the difference between the present temperature and the desired temperature was beyond a specified threshold, the system turned on. However, the proposed control strategy of this study focused on human comfort. The control command based on the thermal comfort index PMV is depicted in Figure 3. The control command was determined by the acceptable range of the PMV. When the PMV value reached the desired PMV, the system turned off. When the difference between the values of the present PMV and the desired PMV was beyond a specified threshold, the system turned on.

3.2. Visual Comfort-Based Control of Artificial Lighting Systems

Artificial lighting systems are designed based on their power consumption, illumination, working area, and functionality. In this study, a dimmable LED lighting fixture was selected for both visual comfort of the occupants and low energy consumption of the building. The required illumination of the artificial lighting, Eart, total is expressed as follows:
E a r t , t o t a l = η ( t ) κ ( t ) E a r t + E a u x
η ( t ) = 0 ( E n a t E r e f )
η ( t ) = E r e f E n a t E a r t ( E n a t < E r e f )
where η ( t ) is the lighting control command, E n a t and E a r t are the illumination (lx) by natural lighting and artificial lighting, respectively. E a u x is the auxiliary illumination (lx) for night time or for emergency. E r e f is the illumination reference (lx) of the building. κ ( t ) is the binary switch following the time schedule of the lighting system. κ ( t ) was 1 when the occupants were present, whereas, it was 0 during both night time as well as when the occupants were absent. However, during night time or in emergency, occupants may use the auxiliary illumination as indicated in Equation (8). The required artificial illumination of the building and its operating time schedule is depicted in Figure 4.

4. Case Study

4.1. Simulation Conditions

To investigate the effect of human comfort-based algorithm-integrated HEMS, a numerical study on building energy performance was conducted using MATLAB/Simulink®. A simple RC-lumped building model for a house was developed based on the first principle of thermodynamics. Three cases were selected to investigate the HEMS function for DR participation and human comfort. Each scenario of the cases is listed in Table 4. The simulation of each scenario was conducted assuming that the house was occupied during the simulation and that the DR command was provided from 9 to 12 h and 18 to 22 h for a week during winter to avoid peak loads and peak electricity pricing. The meteorological data provided by the French Technical Research Center for Building (CSTB) were used [36,37]. The time step of the simulation was in a minute. A heating system was used for heating the space and was considered as a demand resource for replying to the DR commands. If the simulation is conducted during summer, a cooling system may be preferred. In addition, a lighting system is operated for the occupants’ visual comfort during the day and night time. To ensure the occupants’ visual comfort, the lighting system inside the house was controlled to keep the illuminance above 300 lx from 7 to 22 h [34]. The illuminance data was calculated by using a simple window model and a lighting system model integrated in a building simulation tool developed by the CSTB [36].
Case 1 represents a basic case followed a predefined temperature range without any additional adjustment of a heating system for responding to DR. The temperature-based control strategy was applied to case 1, as depicted in Figure 2. The temperature ranges of the heating system in case 1 was fixed from 19 to 21 °C. There was only one scenario with a metabolic heat of 115 W in case 1.
Meanwhile, cases 2 and 3 followed the DR commands by controlling the heating systems. In case 2, a heating system was controlled by a temperature range similar to that of case 1 without the DR command. However, the heating system was controlled in the temperature range of 18–20 °C with the DR command. To reduce the power consumption of the heating system during the DR period, the indoor temperature remained relatively lower than that in the normal conditions without DR events. The heating system in case 3 was regulated by PMV ranges as depicted in Figure 3. The PMV ranged from 0 to −0.2 without DR events, and from −0.2 to −0.5 with DR events. The range of PMV was first set from 0 to −0.2 to ensure the occupants’ thermal comfort when there was no DR command. When a DR command was provided during a certain period, the PMV value within the range of −0.2 to −0.5 was applied as acceptable ranges at normal expectation. There were three types of scenarios in each of cases 2 and 3. However, they differed from the aspect of metabolic heat quantity. Scenario A represented a low metabolic heat of 100 W. Scenario B showed a moderate metabolic heat of 115 W. Scenario C indicated a high metabolic heat of 130 W.

4.2. Simulation Results

The indoor and outdoor temperatures of the house in scenario 1 of case 1 is depicted in Figure 5. The outdoor temperature varied from −2 °C to 6 °C during the simulation, and this was applied to all the scenarios of this study. In scenario 1 of case 1, the heating system of the house was always set from 19 to 21 °C, although there were DR commands from 9 to 12 h and from 18 to 22 h. In scenario 1, the amount of heat energy consumed during a week was 1166 kWh.
The zoomed indoor temperature of scenario 1 for reference and that of scenario 2 B for comparing the DR participation with and without a heating system as demand resources is depicted in Figure 6a. In these scenarios, a metabolic heat of 115 W was applied. In scenario 2 B, the temperature ranges of the house were modified when DR commands arrived during a DR period. As stated above, the DR events were sent to the house for 9–12 h and 18–22 h. During this period, the temperature was set from 18 to 20 °C.
The heater command of scenarios 1 and 2 B based on the temperature-based control strategy is depicted in Figure 6b. The indoor temperature varied (increased and decreased) with respect to the thermal dynamics of the building once the power was on and off, respectively. The indoor temperature was set below 19 °C during the DR period in scenario 2 B and therefore, the heater command was not rapidly reversed compared to the heater command of scenario 1. It permitted the curtailing of the heater’s power consumption during DR periods and reduced the energy consumption of the house while there were DR commands. The amount of heat energy consumed during a week in scenario 2 B was 1136.6 kWh. In this scenario, less amount of heat energy was required compared to that of the heat energy in scenario 1.
This result showed that lower temperature ranges for a heating system reduced the energy consumption of the house and realized its participation in DR programs with a heating system as the demand resource. However, this did not mean that the temperature ranges ensured the thermal comfort of the occupants. The occupants dissipated different amounts of metabolic heat according to their physical properties, physical activities, and conditions. The indoor temperature of the house in scenarios 2 A, B, and C distinguished by different quantity of the metabolic heat of occupants is depicted in Figure 7. As the heating system of the house operated in fixed temperature ranges in these scenarios, all the evolutions of indoor temperatures for the three scenarios were in the range of 19–21 °C in a non-DR period and 18–20 °C in a DR period.
Therefore, the problem of thermal comfort increased as depicted in Figure 8. Under the same indoor temperature conditions, occupants dissipated different metabolic heat with different thermal comfort values. Although the occupants could successfully participate in the DR programs by controlling the temperature ranges of heating systems, it had a negative effect on personal satisfaction. This may induce a short continuity of DR participation in households. Therefore, during a DR period, a simple curtailment of power cannot be recommended as a single solution for all the occupants. To satisfy the thermal comfort of occupants as well as to participate in DR programs with an HVAC system, a PMV-based-control strategy has to be proposed as stated in the previous section. From the perspective of energy saving, the quantities of energy consumption in scenarios 2 A, B, and C were 1138.6, 1136.6, and 1133.1 kWh, respectively, during the given period. As higher metabolic heat contributed in heating the space, the energy consumption of the house was more in scenario 2 C than those in 2 A and B.
The evolution of the indoor temperature of the house in scenarios 3 A, B, and C is depicted in Figure 9. Although the difference in temperature was more than 3 °C among the three scenarios of the same case, the thermal comfort of occupants in each scenario was ensured at the expected PMV ranges between −0.2 and 0 during the non-DR period and between −0.5 and −0.2 during the DR period as depicted in Figure 10. In scenario 3 A, the indoor temperature was higher than those in other scenarios. It explains that the lowest metabolic heat requires the more quantity of heat in the house for improving occupant’ thermal comfort. In other words, the occupant dissipated lower heat feels colder than the occupants dissipating higher metabolic heat. Therefore, in a house where an occupant dissipating lower metabolic heat, more heat should be supplied to this house for thermal satisfaction of the occupant. In contrast, the indoor temperature was lower in scenario 3 C as the occupant dissipated more heat and thus feels warmer or hotter than others. This led to a higher PMV value of the occupant even at a lower temperature. This indicated that the occupants dissipating different quantities of heat have a significant gap with the satisfaction on the indoor thermal condition. This result supported the previously obtained results depicted in Figure 7 and Figure 8. Moreover, the highest metabolic heat required less heating energy in the house. The quantities of energy consumption during the given period in scenarios 3 A, B, and C were 1263, 1094, and 920 kWh, respectively. This showed that thermal comfort could be obtained by controlling a heating system based on the expected PMV values of the occupants. As the curtailment of heating power depended on the thermal comfort of the occupants, their satisfaction in DR programs could be ensured by maintaining their thermal comfort.
To achieve the visual comfort of occupants and energy savings of the building, a dimming artificial lighting system was integrated into the building model. The illuminance level of the house and natural illuminance are depicted in Figure 11. When the occupant was awake from 7 to 22 h, the minimum artificial illuminance was maintained at 300 lx. Therefore, the artificial illuminance was controlled by dimming the artificial lighting with respect to the recommended illumination level of 300 lx, a lighting system operated for the occupants’ visual comfort during the day and night time. The dimming level of the lighting system is depicted in Figure 12. Compared to the system without dimming control, this system reduced 27% of the lighting energy. However, in this study, glare occurrence was not considered. In further studies, a blind system for avoiding glares would be investigated.

5. Conclusions

Home appliances and equipment should be finely controlled by HEMS by considering the influence of occupant’s preferences and behaviour patterns. To promote the occupant’s participation in DR programs, this paper has presented an algorithm based on human comfort factors that can be integrated into the HEMS. The proposed algorithm included PMV and PPD values for the thermal comfort of the occupants, and illuminance level for their visual comfort. To reduce response fatigue of occupants and the curtailment of small appliances, the HVAC system with a relatively larger power capacity and faster dynamics was preliminarily selected to be used as the demand resource of a household. The HVAC system could be controlled to follow the DR events and to reduce the energy consumption of the household. To perform the proposed approach, the thermal comfort-based-control algorithm for a heating system in HEMS was proposed to improve the occupants’ thermal comfort. At the same time, a dimming artificial lighting system (LED) was integrated into the visual comfort-based-control algorithm of the lighting system in HEMS to improve the visual comfort and energy savings of the household. Simulation studies were carried out using MATLAB/Simulink® to verify the effectiveness of the proposed approach. Because the simulation was conducted during winter, the heating process of the HVAC system was controlled. The results showed that the heating system with PMV-based control significantly improved the thermal comfort of the occupants during both the DR and non-DR periods compared to the temperature-based control in scenarios with different metabolic heat dissipation of occupants. In addition, visual comfort based on illuminance and energy savings of a lighting system controlled by the proposed approach in HEMS was also validated. Further study includes advanced control strategies of the HVAC system by using thermal inertia of the households before and after DR events and a blind system control for avoiding glare occurrences.

Funding

This research was funded by Basic Science Research Program through the National Research Foundation of Korea (NRF) funded by the Ministry of Education, grant number 2017R1D1A3B03035693.

Conflicts of Interest

The author declares no conflict of interest. The funders had no role in the design of the study; in the collection, analyses, or interpretation of data; in the writing of the manuscript, or in the decision to publish the results.

References

  1. Aste, N.; Manfren, M.; Marenzi, G. Building automation and control systems and performance optimization: A framework for analysis. Renew. Sustain. Energy Rev. 2017, 75, 313–330. [Google Scholar] [CrossRef]
  2. Martirano, L.; Parise, G.; Greco, G.; Manganelli, M.; Massarella, F.; Cianfrini, M.; Parise, L.; Frattura, P.L.; Habib, E. Aggregation of Users in a residential/commercial building managed by a building energy management system (BEMS). IEEE Trans. Ind. Appl. 2019, 55, 26–34. [Google Scholar] [CrossRef]
  3. Park, H.; Bae, S.; Chang, M.; Park, S.H.; Yoon, G.G. A community-scale energy management system for demand response participation of households with DERs and EVs. In Proceedings of the 2019 IEEE 4th International Future Energy Electronics Conference (IFEEC), Singapore, 23–25 November 2019; pp. 1–5. [Google Scholar]
  4. Palensky, P.; Dietrich, D. Demand side management: Demand response, intelligent systems, and smart loads. IEEE Trans. Ind. Inf. 2011, 7, 381–388. [Google Scholar] [CrossRef] [Green Version]
  5. Shoreh, M.H.; Siano, P.; Shafie-khah, M.; Loia, V.; Catalão, J.P.S. A survey of industrial applications of Demand Response. Electr. Power Syst. Res. 2016, 141, 31–49. [Google Scholar] [CrossRef]
  6. Eissa, M.M. Developing incentive demand response with commercial energy management system (CEMS) based on diffusion model, smart meters and new communication protocol. Appl. Energy 2019, 236, 273–292. [Google Scholar] [CrossRef]
  7. Liu, Y.; Xial, L.; Yao, G.; Bu, S. Pricing-based demand response for a smart home with various types of household appliances considering customer satisfaction. IEEE Access 2019, 7, 86463–86472. [Google Scholar] [CrossRef]
  8. Yan, X.; Ozturk, Y.; Hu, Z.; Song, Y. A review on price-driven residential demand response. Renew. Sustain. Energy Rev. 2018, 96, 411–419. [Google Scholar] [CrossRef]
  9. Samuel, O.; Javaid, S.; Javaid, N.; Ahmed, S.H.; Afzal, M.K.; Ishmanov, F. An efficient power scheduling in smart homes using jaya based optimization with time-of-use and critical peak pricing schemes. Energies 2018, 11, 3155. [Google Scholar] [CrossRef] [Green Version]
  10. Du, Y.F.; Jiang, L.; Li, Y.; Wu, Q. A robust optimization approach for demand side scheduling considering uncertainty of manually operated appliances. IEEE Trans. Smart Grid 2018, 9, 743–755. [Google Scholar] [CrossRef] [Green Version]
  11. Javaid, N.; Ahmed, A.; Iqbal, S.; Ashraf, M. Day ahead real time pricing and critical peak pricing based power scheduling for smart homes with different duty cycles. Energies 2018, 11, 1464. [Google Scholar] [CrossRef] [Green Version]
  12. Huang, Y.; Wang, L.; Guo, W.; Kang, Q.; Wu, Q. Chance constrained optimization in a home energy management system. IEEE Trans. Smart Grid 2018, 9, 252–260. [Google Scholar] [CrossRef]
  13. Shafie-Khah, M.; Siano, P. a stochastic home energy management system considering satisfaction cost and response fatigue. IEEE Trans. Ind. Inf. 2018, 14, 629–638. [Google Scholar] [CrossRef]
  14. Park, H.; Rhee, S.B. IoT-based smart building environment service for occupants’ thermal comfort. J. Sens. 2018, 2018, 1757409. [Google Scholar] [CrossRef]
  15. Lee, S.; Choi, D.-H. Energy management of smart home with appliances, energy storage system and electric vehicle: A hierarchical deep reinforcement learning approach. Sensors 2020, 20, 2157. [Google Scholar] [CrossRef] [PubMed] [Green Version]
  16. Li, M.; Li, G.-Y.; Chan, H.-R.; Jiang, C.-W. QoE-aware smart home energy management considering renewable and electric vehicles. Energies 2018, 11, 2304. [Google Scholar] [CrossRef] [Green Version]
  17. Vand, B.; Martin, K.; Jokisalo, J.; Kosonen, R.; Hast, A. Demand response potential of district heating and ventilation in an educational office building. Sci. Technol. Built Environ. 2019, 26, 304–319. [Google Scholar] [CrossRef]
  18. Yao, L.; Huang, J.-H. Multi-objective optimization of energy saving control for air conditioning system in data center. Energies 2019, 12, 1474. [Google Scholar] [CrossRef] [Green Version]
  19. Hawila, A.A.W.; Merabtine, A.; Troussier, N.; Bennacer, R. Combined use of dynamic building simulation and metamodeling to optimize glass facades for thermal comfort. Build. Environ. 2019, 157, 47–63. [Google Scholar] [CrossRef]
  20. Hee, W.J.; Alghoul, M.A.; Bakhtyar, B.; Elayeb, O.; Shameri, M.A.; Alrubaih, B.; Sopian, K. The role of window glazing on daylighting and energy saving in buildings. Renew. Sustain. Energy Rev. 2015, 42, 323–343. [Google Scholar] [CrossRef]
  21. Vanhoutteghem, L.; Skarning, G.C.J.; Hviid, C.A.; Svendsen, S. Impact of façade window design on energy, daylighting and thermal comfort in nearly zero-energy houses. Energy Build. 2015, 102, 149–156. [Google Scholar] [CrossRef] [Green Version]
  22. Huang, X.; Wei, S.; Zhu, S. Study on daylighting optimization in the exhibition halls of museums for chinese calligraphy and painting works. Energies 2020, 13, 240. [Google Scholar] [CrossRef] [Green Version]
  23. Kolokotsa, D.; Tsiavos, D.; Stavrakakis, G.S.; Kalaitzakis, K.; Antonidakis, E. Advanced fuzzy logic controllers design and evaluation for buildings’ occupants thermal–visual comfort and indoor air quality satisfaction. Energy Build. 2001, 33, 531–543. [Google Scholar] [CrossRef]
  24. Li, M.; Lin, H.-J. Design and implementation of smart home control systems based on wireless sensor networks and power line communications. IEEE Trans. Ind. Electron. 2015, 62, 4430–4442. [Google Scholar] [CrossRef]
  25. Enescu, D. Models and indicators to assess thermal sensation under steady-state and transient conditions. Energies 2019, 12, 841. [Google Scholar] [CrossRef] [Green Version]
  26. American Society of Heating, Refrigeration and Air Conditioning Engineers. Standard 55: Thermal Environmental Conditions for Human Occupancy; ASHRAE: New York, NY, USA, 2013. [Google Scholar]
  27. Fanger, P.O. Thermal Comfort: Analysis and Applications in Environmental Engineering; Danish Technical Press: Copenhagen, Denmark, 1970. [Google Scholar]
  28. ISO7730. Moderate Thermal Environments—Determination of the PMV and PPD Indices and Specification of the Conditions for Thermal Comfort; ISO: Geneva, Switzerland, 1984. [Google Scholar]
  29. Kao, J.C.M.; Sung, W.-P.; Chen, R. Green Building, Materials and Civil Engineering; CRC Press: Boca Raton, FL, USA, 2014. [Google Scholar]
  30. Nicol, F.; Wilson, M. An overview of the European Standard EN 15251. In Proceedings of the Adapting to Change: New Thinking Comfort, London, UK, 9–11 April 2010; pp. 1–13. [Google Scholar]
  31. CEN/TC 156. Indoor Environmental Input Parameters for Design and Assessment of Energy Performance of Buildings—Addressing Indoor Air Quality, Thermal Environment, Lighting and Acoustics; CEN/TC: Brussels, Belgium, 2006. [Google Scholar]
  32. EN 12665. Light and Lighting—Basic Terms and Criteria for Specifying Lighting Requirements; European Committee for Standardization: Brussels, Belgium, 2011. [Google Scholar]
  33. Mahoney, E. Using Luminance for Design and Evaluation of Energy Efficient and Sustainable Luminous Environments to Supplement Current Illuminance-Based Design Codes. Master’s Thesis, University of Kansas, Lawrence, KS, USA, 2019. [Google Scholar]
  34. Grondzik, W.T.; Kwok, A.G.; Stein, B.; Reynolds, J.S. Mechanical and Electrical Equipment for Buildings; Wiley: Hoboken, NJ, USA, 2011. [Google Scholar]
  35. Park, H. Dynamic Thermal Modeling of Electrical Appliances for Energy Management of low Energy Buildings. In Electric Power. Ph.D. Thesis, Université de Cergy-Pontoise, Cergy-Pontoise, France, 2013. [Google Scholar]
  36. SIMBAD. Building and HVAC Toolbox; entre Scientifique du Bâtiment: Marne-la-Vallée, France, 2005. [Google Scholar]
  37. Ruellan, M.; Park, H.; Bennacer, R. Residential building energy demand and thermal comfort: Thermal dynamics of electrical appliances and their impact. Energy Build. 2016, 130, 46–54. [Google Scholar] [CrossRef]
Figure 1. Percentage of dissatisfied (PPD) as a function of PMV.
Figure 1. Percentage of dissatisfied (PPD) as a function of PMV.
Energies 13 02463 g001
Figure 2. Control command of the heating, ventilation, and air-conditioning (HVAC) system based on acceptable temperature range: (a) cooling process and (b) heating process.
Figure 2. Control command of the heating, ventilation, and air-conditioning (HVAC) system based on acceptable temperature range: (a) cooling process and (b) heating process.
Energies 13 02463 g002
Figure 3. Control command of the HVAC system based on acceptable PMV range: (a) cooling process and (b) heating process.
Figure 3. Control command of the HVAC system based on acceptable PMV range: (a) cooling process and (b) heating process.
Energies 13 02463 g003
Figure 4. The required artificial illumination of the building. (a) Artificial lighting versus natural lighting and (b) control command based on a time schedule.
Figure 4. The required artificial illumination of the building. (a) Artificial lighting versus natural lighting and (b) control command based on a time schedule.
Energies 13 02463 g004
Figure 5. Indoor () and outdoor (- -) temperatures in scenario 1.
Figure 5. Indoor () and outdoor (- -) temperatures in scenario 1.
Energies 13 02463 g005
Figure 6. Comparison of indoor temperature and heater signal: (a) temperature and (b) heater command (—: scenario 1 and - -: scenario 2 B).
Figure 6. Comparison of indoor temperature and heater signal: (a) temperature and (b) heater command (—: scenario 1 and - -: scenario 2 B).
Energies 13 02463 g006
Figure 7. Comparison of indoor temperature (—: scenario 2 A, - -: scenario 2 B, and —- -: scenario 2 C).
Figure 7. Comparison of indoor temperature (—: scenario 2 A, - -: scenario 2 B, and —- -: scenario 2 C).
Energies 13 02463 g007
Figure 8. Comparison of PMV (—: scenario 2 A, - -: scenario 2 B, and —- -: scenario 2 C).
Figure 8. Comparison of PMV (—: scenario 2 A, - -: scenario 2 B, and —- -: scenario 2 C).
Energies 13 02463 g008
Figure 9. Comparison of indoor temperature (—: scenario 2 A, - -: scenario 2 B, and —- -: scenario 2 C).
Figure 9. Comparison of indoor temperature (—: scenario 2 A, - -: scenario 2 B, and —- -: scenario 2 C).
Energies 13 02463 g009
Figure 10. Comparison of PMV (—: scenario 2 A, - -: scenario 2 B, and —- -: scenario 2 C).
Figure 10. Comparison of PMV (—: scenario 2 A, - -: scenario 2 B, and —- -: scenario 2 C).
Energies 13 02463 g010
Figure 11. Illuminance (—: natural illuminance and - -: indoor illuminance).
Figure 11. Illuminance (—: natural illuminance and - -: indoor illuminance).
Energies 13 02463 g011
Figure 12. Dimming level of lighting system.
Figure 12. Dimming level of lighting system.
Energies 13 02463 g012
Table 1. Index of predicted mean vote (PMV).
Table 1. Index of predicted mean vote (PMV).
Index−3−2−10123
SensationColdCoolSlightly CoolNeutralSlightly WarmWarmHot
Table 2. Three categories of thermal comfort.
Table 2. Three categories of thermal comfort.
CategoryPPDPMV Range
I<6−0.2 < PMV < +0.2
II<10−0.5 < PMV < +0.5
III<15−0.7 < PMV < +0.7
Table 3. Illuminance threshold values of tasks.
Table 3. Illuminance threshold values of tasks.
Visual TasksIlluminance (lx)
Resting, causal visual tasks10–50
Simple activities, ordinary visual tasks100
Visual tasks of high contrast and large size300
Visual tasks of high contrast and small size/
Visual tasks of low contrast and large size
500
Difficult visual tasks of low contrast and small size1000
Severe visual tasksAbove 3000
Table 4. Scenario description of case studies.
Table 4. Scenario description of case studies.
CaseScenarioRegulation MethodRegulation RangeMetabolic Heat
1Scenario 1TemperatureWithout DR: 19–21 °C
With DR: 19–21 °C
115 W
2Scenario 2 ATemperatureWithout DR: 19–21 °C
With DR: 18–20 °C
100 W
Scenario 2 BTemperatureWithout DR: 19–21 °C
With DR: 18–20 °C
115 W
Scenario 2 CTemperatureWithout DR: 19–21 °C
With DR: 18–20 °C
130 W
3Scenario 3 APMVWithout DR: −0.2–0
With DR: −0.5–−0.2
100 W
Scenario 3 BPMVWithout DR: −0.2–0
With DR: −0.5–−0.2
115 W
Scenario 3 CPMVWithout DR: −0.2–0
With DR: −0.5–−0.2
130 W

Share and Cite

MDPI and ACS Style

Park, H. Human Comfort-Based-Home Energy Management for Demand Response Participation. Energies 2020, 13, 2463. https://doi.org/10.3390/en13102463

AMA Style

Park H. Human Comfort-Based-Home Energy Management for Demand Response Participation. Energies. 2020; 13(10):2463. https://doi.org/10.3390/en13102463

Chicago/Turabian Style

Park, Herie. 2020. "Human Comfort-Based-Home Energy Management for Demand Response Participation" Energies 13, no. 10: 2463. https://doi.org/10.3390/en13102463

APA Style

Park, H. (2020). Human Comfort-Based-Home Energy Management for Demand Response Participation. Energies, 13(10), 2463. https://doi.org/10.3390/en13102463

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop