1. Introduction
The dynamic development of the economy and industrialization in the nineteenth and twentieth century was associated with higher energy consumption, which resulted in an increasing demand for fossil fuels, especially bituminous coal and lignite. However, burning more fossil fuels has caused various ecological and environmental issues, which people have been trying to solve since recent years. One of the instruments to reduce the negative impact of burning fossil fuels on the environment are numerous European Union directives regarding climate protection. These directives concern, for example, the reduction of greenhouse gas emissions, supporting the development of renewable energy and low-carbon technologies, as well as the Emissions Trading System [
1]. Similar efforts are also carried out at the global level, as exemplified by the Paris Agreement adopted at the Paris Climate Conference (COP21) in December 2015 [
2], and the 24th Conference of the Parties to the United Nations Framework Convention on Climate Change (COP24) at Katowice in 2018 [
3]. The main aims of the agreements made during the conferences mentioned above are reducing energy and natural resources consumption and minimizing the level of pollution emitted to the environment.
According to the Energy Statistics in 2016 and 2017 [
4], the global consumption of total energy in Poland in 2017 was 4410 PJ, while the energy consumption by households (including energy consumption by cars) was 1146 PJ, which accounted for approximately 26% of the global consumption of total energy in Poland. In Poland in 2016, the global consumption of total energy and the energy consumption by households (including energy consumption by cars) was 4216 and 1142 PJ, respectively. Furthermore, the energy consumption forecast prepared by Agencja Rynku Energii S.A. [
5] indicates the growth of the total primary energy demand and the electricity demand in 2030 by 27% and 54%, respectively, compared to the demand in 2010. It is worth mentioning that electricity consumption by air conditioning and refrigeration systems is one of the factors that significantly contributes to the overall electricity consumption growth. Refrigeration has been developing dynamically since the nineteenth century due to its application in numerous fields, including production, transport and food storage, industry (the necessity of cooling various devices and machines), air conditioning of buildings, household refrigerators, etc. Additionally, more and more rigorous legal regulations concerning environmental protection, e.g., Regulation (European Union) No. 517/2014 of the European Parliament and of the Council of 16 April 2014, on fluorinated greenhouse gases and repealing Regulation (European Commission) No. 842/2006 [
6], are being introduced. Therefore, searching for new possibilities for refrigeration systems development seems to be unavoidable.
The technology that meets the challenges of legal regulations and environment protection turned out to be adsorption refrigeration systems. The adsorption refrigerators are a more promising and attractive field for research than conventional electrically-driven vapor compression chillers, since the adsorption systems do not use undesirable chlorofluorocarbons that cause ozone depletion. Substances, e.g., water, used as refrigerants in the adsorption chillers, are environmentally friendly and do not cause ozone depletion [
7].
The refrigeration cycles’ working principle in adsorption chillers with water as a refrigerant is based on the sorbent’s hygroscopic properties, which is a non-toxic substance. The sorbent adsorbs water vapor in the adsorption bed due to the electrostatic attraction and van der Waals forces. A silica-gel, aluminum fumarate, and ferro-aluminophospate can be used as sorbents [
8]. Regardless of the sorbent used, heat must be supplied to the saturated sorbent to release the adsorbed water after the adsorption process. Thus, the adsorption chillers use heat to operate, unlike vapor compression chillers that use electricity to operate. The sources of the above mentioned heat include:
Warm water from a district heating system [
9];
Direct burning of fossil fuels, e.g., gas [
9];
Waste heat from exhaust gases [
9];
Waste heat from power plants or combined heat and power systems [
9];
Renewable energy, especially solar energy [
10].
Furthermore, adsorption chillers possess additional advantages over electrically-driven vapor compression chillers, such as the possibility of using water as a refrigerant [
10,
11], low level of noise, lack of vibrations, and lack of moving parts [
9]. Adsorption chillers might be applied wherever the heat in the temperature range of 60–75 °C or a steam in the pressure range of 1-8 bar is available. Nevertheless, adsorption chillers possess a low Coefficient of Performance (COP), not exceeding approximately 0.6 [
11], compared to vapor compressor chillers whose COP might be as high as 6 [
12]. As a result, many methods of increasing the COP have been investigated. For example, Shabir et al. [
13] investigated the COP of the adsorption chiller with different adsorbent/refrigerant pairs. It was found that among the investigated pairs (KOH6-PR/ethanol, WPT-AC/ethanol, Maxsorb-III/methanol, Maxsorb-III/CO
2, Maxsorb-III/n-butane, Maxsorb-III/R-134a, SAC-2/R32, and Maxsorb-III/R507a), the Maxsorb-III/methanol pair showed the highest COP. Uyun et al. [
14] applied the internal heat recovery in the investigated adsorption chiller. The COP of the improved chiller increased by 13.4% compared to the COP of the chiller without heat recovery. Chorowski et al. [
15] found that the chiller’s COP can be raised by 7.5% by modifying only the control system, i.e., switching time and cycle allocation.
In addition to the low COP of adsorption chillers, a cyclic operation resulting in an irregular cold production is their significant drawback [
16]. Thus, several (two, three, or more) sub-processes are working alternately, obtaining a quasi-continuous cooling capacity [
17,
18,
19]. Two-bed and four-bed adsorption chillers have gained much attention in the scientific community in the last years. For example, Pan et al. [
20] experimentally investigated the influence of the heating water temperature on the two-bed adsorption chiller’s performance. Woo et al. [
21] also examined the two-bed adsorption chiller’s performance under different operating conditions, but their chiller possessed another water desalination function. Similar studies were conducted by Kim et al. [
22], who investigated the water quality produced in the four-bed adsorption chiller. On the other hand, there are only a few studies concerning three-bed adsorption chillers in the literature. Saha et al. [
23], who experimentally investigated the three-bed adsorption chiller’s performance, reported that its Coefficient of Performance (COP) increased from approximately 0.28 to 0.38 when the heating water temperature increased from 60 to 90 °C. A slightly greater COP, i.e., 0.64, of the three-bed adsorption chiller was obtained by Chorowski and Pyrka [
24]. Furthermore, it was concluded that the three-bed application allows chillers to work more effectively compared to two-bed chillers.
This paper presents the results of an experimental study on the influence of the heat source temperature on the Specific Cooling Power (SCP) and the COP of the three-bed adsorption chiller with desalination function, in which two beds work in parallel while the third bed works individually. The present work is the first in the literature dealing with the presented approach, i.e., two beds working in parallel and the third bed working individually, in the considered three-bed adsorption chiller. Water in the temperature range of 57–85 °C was used as a heat source for bed regeneration during the desorption process. Based on the literature review presented in the paragraphs above, it seems that the research on the three-bed adsorption chiller is necessary and justified due to the following reasons: Three-bed chillers are supposed to work more efficiently than two-bed chillers, but they are less complicated and require fewer elements than four-bed chillers. Furthermore, the three-bed adsorption chiller investigated in this work has the water desalination function, and to the best of the authors’ knowledge, an experimental study on such a chiller has not been done before.
3. Results and Discussion
The experimental studies focused on the impact of heating water temperature, which varied in the range of 57–85 °C, on the three-bed adsorption chiller’s main operating parameters. The results show that changing the temperature of heating water strongly influences the COP and SCP of the chiller with two beds working in parallel and one bed working individually, as presented in
Figure 3 and
Figure 4, respectively. When the heating water temperature increased from 57 to 85 °C, the COP increased by 190% (from 0.20 to 0.58).
The COP of the investigated chiller, in this work the three-bed adsorption chiller, is difficult to be compared to the COP of the other chillers investigated by the other researchers, since the COP is influenced by many factors, including the beds’ construction, capacity, and material. Therefore, the three-bed adsorption chiller’s COP obtained in this work is compared only to the COP of the same chiller but working in a two-bed mode, as investigated in the authors’ previous study [
26]. It should be noted that the temperatures of chilled and cooling water in the case of the two-bed adsorption chiller were 13 and 18 °C, respectively, which is almost the same as in the case of the three-bed chiller.
As can be seen in
Figure 3, the three-bed chiller’s COP increased by about 190% when the heating water temperature increased from 57 to 85 °C. Similarly, the SCP, which determines the cooling capacity obtained from 1 kg of the sorbent, increased from 27 to 160 W/kg when the heating water temperature was increased from 57 to 85 °C. Additionally, for the heating water temperature above 75 °C, the COP of the considered three-bed adsorption chiller is higher by the maximum value of about 16% than the two-bed adsorption chiller’s COP investigated in the previous work [
26]. This confirms that the three-bed adsorption chiller performance in temperatures above 75 °C is higher than the chiller with two adsorption beds. On the other hand, the three-bed chiller’s COP (two beds working in parallel and one bed working individually) is lower compared to the two-bed chiller’s COP for the heating water temperature below 75 °C. A possible explanation of such a result is most likely due to a low heat transfer rate caused by a small temperature difference between the heating water and beds. As a result, a power shortage occurs in each chiller’s element, especially in the evaporator, which is enhanced in the three-bed chiller due to an increased number of beds and larger sorbent mass.
The experiments’ results indicate the strong influence of the heating water temperature on the COP and SCP. As the heating water temperature increased, both the COP and SCP rose due to a more intense water release from the silica gel and faster desorption process. The heating water temperature increment shortened the desorption time and accelerated the regeneration of the bed. As a result, more water from the evaporator was adsorbed by the sorbent. Consequently, the evaporator’s cooling capacity increased, and the generated chilled water’s temperature decreased, which is shown in
Figure 5. The chilled water mass flow rate was constant during the experiments, and when the heating water temperature increased from 57 to 85 °C, the chilled water temperature decreased from approximately 16 to 10 °C. This means that the chilled water temperature decreased by 6 °C while maintaining a constant mass flow rate through the evaporator.
The chilled water temperature drop caused by increasing the heating water temperature was related to the increment of the adsorbent sorption properties. As a result, the average evaporator pressure and the average evaporator temperature decreased, which is shown in
Figure 6. As can be seen, the average evaporator pressure and the average evaporator temperature were 2 kPa and 16 °C, respectively, when the heating water temperature was 57 °C. As the heating water temperature increased to 85 °C, the average evaporator pressure and the average evaporator temperature decreased to 1.05 kPa and 7 °C, respectively. The evaporator temperature changes were a result of the processes in the chiller related to the adsorption/desorption of water vapor in the silica-gel in the beds.
As mentioned before, the heating water temperature was changed in the range of 57–85 °C. As shown in
Figure 7, the temperature changes of beds are uniform, and the temperature changes resulted from the alternating adsorption/desorption processes. Additionally, when the heating water temperature decreased, the beds’ temperatures decreased from 70 to 50 °C during the desorption. Moreover, for low heating water temperatures, the bed working individually heated up and cooled down faster than the two beds working in parallel. Moreover, as the heating water temperature decreased, the evaporator temperature increased, which indicates a low heat transfer rate from the evaporator to the water, and confirms a less intensive beds’ operation. It is worth noting that the beds’ temperatures were measured inside the heat exchanger, between the silica gel and the heat exchanger pipes, and manual settings set the time of the adsorption phases. The evaporator temperature increased from 7 to 16 °C when the heating water temperature decreased. On the other hand, the condenser temperature was constant, independently from the heating water temperature.
Figure 8 presents the beds’ pressure in the function of time during the adsorption/desorption cycles. The results show that bed number one and bed number two worked in a parallel arrangement, which means they worked simultaneously during the adsorption/desorption phase, as explained in
Section 2.1. Bed number three worked in a singular arrangement during the different working phases. The pressure changes in the beds reflect the operating cycle of the adsorption chiller. When the water vapor flows between the evaporator and the bed during the adsorption phase, the system is trying to equalize the pressure between the evaporator and bed. The pressure in the beds during the adsorption is approximately 1 kPa. During the desorption phase, the heating water is pumped through the beds. As a result, silica gel is heated, and the adsorbed water molecules evaporate. The released water vapor flows to the condenser, and the bed pressure increases to the condenser pressure. The bed pressure is 7.5 kPa during the desorption cycles. As can be seen, there is a dependency between the phases that is related to the pressure and temperature distribution. Furthermore, the pressure in bed numbers one and two is very similar, so the beds could be regarded as one big bed. However, the beds are divided into two beds to allow changing the beds’ configuration into the two-bed mode or three-bed mode, as mentioned in
Section 2.1. Additionally, the working configuration of the beds in the three-bed mode can be changed, i.e., beds one and two work in parallel, while bed three works singularly, or bed one and three work in parallel, while bed two works singularly, or bed two and three work in parallel, while bed one works singularly.
4. Conclusions
This paper deals with effective cooling and desalination technology, suitable for cleaner production and environmental conservation. It constitutes the first paper available in open literature dealing with the considered three-bed adsorption chiller with two beds working in parallel and one bed working individually, and the heating water’s influence on its main operating parameters.
According to the obtained results, it can be concluded that the COP and SCP of the three-bed adsorption chiller are strongly dependent on the heating water temperature. When the heating water temperature increased from 57 to 85 °C, the COP increased from 0.20 to 0.58 (by 190%). Therefore, increasing the heating water temperature results in an increase in the COP. Furthermore, SCP, which determines the cooling capacity obtained from 1 kg of the adsorbent, increases. As the heating water temperature increased from 57 to 85 °C, the SCP also increased from 27 to 160 W/kg. An increase in the heating water temperature accelerates the desorption process; thus, the silica gel’s water adsorbed is released faster, and the chiller’s cooling capacity rises.
The experimental studies show that the COP of the three-bed adsorption chiller is higher than the two-bed adsorption chiller, which was investigated in the previous work [
26], by about 16% for the heating water temperature of 85 °C. However, the three-bed chillers’ COP was lower compared to the two-bed chiller for the heating water temperature below 75 °C. Such a decline in the COP was caused by the slow heat transfer rate, and thus power shortage, especially in the evaporator.
In further studies, the authors are planning to investigate experimentally the performance of the three-bed chiller with alternately working beds, which may improve the chiller’s COP, especially at low heating water temperatures.