Next Article in Journal
Low Voltage Battery Management System with Internal Adaptive Charger and Fuzzy Logic Controller
Next Article in Special Issue
Computational Simulation and Dimensioning of Solar-Combi Systems for Large-Size Sports Facilities: A Case Study for the Pancretan Stadium, Crete, Greece
Previous Article in Journal
Lightweight Equipment Using Multiple Torches for Fast Speed Asphalt Roofing
Previous Article in Special Issue
A Novel Load Scheduling Mechanism Using Artificial Neural Network Based Customer Profiles in Smart Grid
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Energy Consumption Reduction of a Chiller Plant by Adding Evaporative Pads to Decrease Condensation Temperature

by
Francisco J. Rey Martínez
1,
Julio F. San José Alonso
1,*,
Eloy Velasco Gómez
1,
Ana Tejero González
1,
Paula M Esquivias
1 and
Javier M. Rey Hernández
2
1
Department of Energy and Fluid mechanics, School of Engineering (EII), University of Valladolid, Paseo del Cauce No. 59, 47011 Valladolid, Spain
2
Higher Polytechnic School, European University Miguel de Cervantes (UEMC), Padre Julio Chevalier, 47012 Valladolid, Spain
*
Author to whom correspondence should be addressed.
Energies 2020, 13(9), 2218; https://doi.org/10.3390/en13092218
Submission received: 16 March 2020 / Revised: 15 April 2020 / Accepted: 24 April 2020 / Published: 2 May 2020

Abstract

:
The high energy consumption of cooling systems justifies the need for strategies to increase the efficiency of the facilities, in order to reduce the related CO2 emissions. This study aims to improve the performance and reduce the energy consumption of an 8.6 MW air cooled chiller. This installed capacity is biased due to the screw compressors, of 2.98 Energy Efficiency Ratio (EER) at full load (characteristics provided by the manufacturer). The chiller unit has been modified by placing evaporating cooling pads before the condensing coils. The chiller has been monitored for three months, recording over 544,322 measurements (5 min-step data), with and without the evaporative cooling pads, to assess the performance. Data comparison has been done by selecting two days (with and without evaporative panels) with the same health care load and temperatures. Implementing the proposed strategy yields an improvement in the European Seasonal Energy Efficiency Ratio (ESEER) from 3.69 to 4.83, while the Total Equivalent Warming Impact (TEWI) decreases about 1000 tCO2. Energy savings of up to 32.6 MWh result into a payback period lower than 2 years.

1. Introduction

The building sector is responsible for 40% of the final energy consumption in the European Union [1]. For this reason, the EU promotes the renovation of existing buildings, the improvement of energy efficiency and the integration of renewable energies in buildings in order to get by 2050 a decarbonized building stock by means of getting nearly zero-energy buildings (nZEB) [2].
The increasing global temperature due to the climate change will decrease the heating energy demand and increase the cooling energy demand. In fact, simulated future weather climates for 2050 and 2080 on an existing nZEB provokes an increase on cooling energy demand around 9% for 2050 and 21% for 2080 regarding to 2020 results [3]. These results show that, in order to achieve an adequate indoor air quality (IAQ) in buildings, the focus should be on strategies for cooling demand reduction. According to Article 2(2) of the Energy Performance of Buildings Directive (EPBD) [4] a nZEB means a building that has a very high energy performance; it means that the amount of energy needed to meet the energy demand associated with a typical use of the building which includes, inter alia, energy used for heating, cooling, ventilation, hot water and lighting, is very low. However, although nZEB reduces considerably the cooling energy demand from the envelope, lighting and equipment, occupancy and ventilation are always non-modifiable thermal loads, as they are associated to the activity of the building and the requirements of air change in order to secure air quality for those occupants.
In order to cover the cooling energy demand of a building, air conditioning systems, which use compression refrigeration cycle, are used. The efficiency of these systems varies according to the working temperatures (evaporation and condensation temperatures).
The evaporation temperature in air-conditioned occupied spaces falls in a narrow temperature range because, due to comfort guidelines, air cannot be supplied at a temperature far below the body temperature. However, condensation temperature presents several options depending on the resource with which the heat is exchanged—water, earth or air. In this study, only air condensation is considered. The water heat exchange requires an aquifer and earth heat exchange implies an important investment.
Condensation temperature (Tc), when the air is used as a heat sink, directly depends on the local climate conditions of the placement of the building. There are two options, using the dry bulb temperature (TDB) or the adiabatic saturation temperature of the moist air (Tsat) as the heat sink for the condenser [5], enabling in the latter case a lower thermal level of the heat dissipation media.
Refrigeration systems permit condensation closer to Tsat if we make use of the phenomenon of evaporative cooling. The difference between TDB and Tsat increases, hence the potential of evaporative cooling, as the Relative Humidity (RH) of outside air decreases [6]. Condensers that apply this phenomenon may have higher levels of maintenance in order to avoid possible contamination by legionella [7], although they also allow to reduce the condensation temperature and improve the Coefficient of Performance (COP) of the equipment.
Condensers that apply the phenomenon of evaporative cooling can be classified in different typologies according to: (i) the contact of the saturated airflow and the condenser; (ii) the moment when water is added and (iii) the source of the water that will be evaporated. If the same airflow in which water is evaporated passes through the condenser, it is called direct; otherwise is indirect. If water is evaporated within the air before the condenser, it is called “dry”; but if water is supplied on the condenser, it is called wet evaporative condenser. If the water source comes from a loop, it is a recirculation water system; otherwise is referred as “lost water” system. Direct-dry systems are commonly called “adiabatic condenser.” Table 1 gathers these possible configurations of evaporative condensers (EC).
Condensation temperature is function of the minimum temperature of the environment, which is usually the Tsat in the direct-dry recirculated water configuration and the water temperature (Tw) in the direct-dry lost water case. The processes of mass and heat transfer at the condenser determines the condensation temperature of the refrigerant. Table 1 also indicates the condensation temperature according to the minimum temperature of the process.
Many studies have been carried out on this type of condenser in order to improve the efficiency of refrigeration systems. Wei et al. [8] study a direct wet EC using recirculated water. They propose a numerical model validated with experimental data, obtaining a 30% increase in the COP on an equipment that condenses at TDB. Chien et al. [9] study the water spraying on a direct wet EC using recirculated water in order to avoid the dragging of water drops and improve the air saturation process. They propose the optimal type and separation of nozzles in each case. This study is of interest as it is focused on one of the disadvantages of EC—the deterioration of the condenser by dragging drops and salts.
Fiorentino and Starace [10,11] studied a direct dry EC using recirculated water. They present an experimental study where the evaporation process is evaluated, concluding that an increase of 6% in relative humidity implies a reduction of 30% in the dry temperature. They also highlight the importance of the air speed when it crosses the saturator. Harby et al. [12] carried out a study on different systems and collected research on vapor compression cooling systems using EC, presenting a lot of experimental data on different technologies.
Martínez et al. [13] studied the improvement of a direct dry EC using recirculated water, due to the integration of an evaporative cellulose pad to the condenser of an Split Unit, obtaining an increase of 10.6% in the COP. In addition, they present a table with a compilation of previous researches on EC, organized by the type of analysis carried out, the equipment used and the results obtained.
This paper shows the results obtained by installing cellulose evaporative pads, with lost water humidification, before the airflow goes into the condensers, so a direct-dry lost water configuration, also known as adiabatic condenser. The air-conditioning system of the building under study has an installed cooling capacity of 8.70 MW and the strategy applied on the use of the evaporative pads consisted of an ON/OFF mode of the water supply pump to the cellulose pad, depending on the time, being ON from 3pm to 10pm and the remaining hours on standby.

2. Case Study

The case study is a chiller plant installed in a hospital building. The building has 115,354 m2 built area, around 3000 employees and 600 beds. The chiller plant has a cooling capacity of 8.70 MW and is composed by 6 TRANE chillers, R series, model RTAC 400, with a cooling capacity of 1442 kW/each and a COP of 2.89. Each chiller has four screw compressors, enabling partial cooling capacity of the chiller. Figure 1 shows the chiller plant at the roof of the hospital.
The produced cooled water by the chiller plant is distributed by a double ring system with inverted return that covers the whole building and enables the water supply to the installed 200 Air Handling Units and 1500 inductors (the inductors are installed at offices and meeting rooms). The temperature of the supply water is 7 °C and 12 °C for the returned water.
The SCADA system of the chiller plant, provided by siemens, measures and allows to display several operating parameters, due to the SITRANS sensors installed. Figure 2 shows a screenshot with all the data provided by the control system for each chiller.
  • Partial load ratio, based on the electric energy consumption (Row 1),
  • Temperature of the refrigerant at the condenser and the evaporator, in both circuits of each chiller (Rows 2–5),
  • Inlet and outlet water temperature to the chiller (Row 6–7),
  • Outdoor temperature in each chiller (Row 8),
  • Data about the performance state of each chiller (Row 9–10)—presence of evaporative pad and operation of the chiller (On/Off).
All measurements of the sensors were checked with calibrated equipment, verifying the accuracy of the results.
Before the research, the chiller plant produced peaks of power consumption, which exceed the maximum contracted electrical power during the peak hours of cooling demand in summer. This situation caused additional costs and overheating in the transformers of the electrical system. Figure 3 shows the electricity consumption curve in one year and the average trend line for the year from data taken from the SCADA system.
After observing the high power consumption, the proposed strategy was reducing the condensation temperature by installing evaporative pads before the condensation batteries. The decrease in the condensation temperature would mean an improvement in the COP and in the ESEER [14] of the system, taking into account that the chillers are located in a location where the dry bulb (TDB) and wet bulb (TWB) temperatures of the moist air are 33.2/19.1 °C respectively, at a percentile level of 1% [15]. The introduction of evaporative pads before the condensers allows to reduce 14 °C the condensation temperature, which would mean an increase in the EEC and in the ESEER.
An evaporative pad was selected from the MUNTERS company, model CELdek 7060-15, which is made of corrugated cellulose with different striation angles, with a 60-degree inclination (colored in pink at Figure 4) and another pad below with a 30-degree inclination (colored in blue at Figure 4), glued together to achieve a high evaporation efficiency and a very low pressure drop. Figure 4 and Table 2 show the characteristics of the evaporative pad.
Using the technical characteristics presented in Table 2, a 100 mm thick pad was installed in order to introduce the least pressure loss at the condenser and ensure that no water drops reaches the condenser, as the low saturation percentage of the pad does not allow the air to leave saturated, so the water drops released from the pad are evaporated in the airgap. The increase in the pressure loss due to the evaporative cooling pad was bearable by the fans without increasing the energy consumption; otherwise the frequency variator would be adjusted. The distance between each chiller, in order to avoid air bypassing, allows the introduction of the evaporative cooling pads between them.
The panels were placed before the condensing coils and were humidified by lost water. Figure 5 shows the before (a) and after (b) of the installation of the evaporative panels before the condensers of the chillers of the Hospital.

3. Analysis and Results

The operating parameters of each chiller, shown in Figure 2, were recorded every five minutes from July to August, “without” and “with” the evaporative cooling pads, getting a total of 544,320 data. In order to compare the chiller plant “without” and “with” the evaporative cooling pad, two days were selected, one when the system was operating “without” and other when it was operating “with” the evaporative cooling pad, fulfilling: (i) similar weather conditions, same external temperature and relative humidity; (ii) same evaporation temperature and (iii) similar equipment load ratio. The selected days were August 10th for operation without the evaporative cooling pads and August 17th for operation with them. Figure 6 shows the outside temperature on both days and an average of both.
The operation of the evaporative cooling pad was programmed to run from 3:00 p.m. to 10:00 p.m., which corresponds to the consumption peaks of the building. Figure 7 shows the evolution of the inlet air temperature at the condenser with and without the evaporative cooling pad and the condensation temperature with and without the evaporative cooling pad. In the case “without” the refrigerant condenses at 45 °C and “With” the refrigerant condenses at 30 °C.
The comparison of the performance of the chiller plant was made on the basis of: (i) the COP at partial loads and the ESEER in the summer period, (ii) the TEWI [16] carbon emission reduction and (iii) the economic analysis.

3.1. COP and ESEER analysis

In order to calculate the average COP of the chiller plant the operating values are collected from the SCADA system every five minutes, operating “with” and “without” the evaporative cooling pad and are introduced in the following Equation (1):
COP = m ˙ w Cp w Δ T w φ W ˙ max ,
where ṁw is the cooling water flow of the equipment (kg/s); cpw is the specific heat of water (4.18 kJ/kg°C); ΔTw is the difference between the outlet and inlet water temperature of the equipment (°C); φ is the chiller load factor; Ẇmax is the power consumption when the chillers work at full load (kW).
Figure 8 shows the calculated COP values for each load factor when the chiller plant operates “with” and “without” the evaporative cooling pads and the linear regression of each group of values.
Table 3 shows the average values for each load factor in order to get later the European Seasonal Energy Efficiency Ratio (ESEER).
Applying the definition of ESEER, the result is that “without” the evaporative cooling pads, the ESEER is 3.69 and “with” them, the ESEER is 4.83. The improvement in the ESEER is 30.89%.

3.2. TEWI Analysis

Total Equivalent Warming Impact (TEWI) is a measure of the greenhouse gas emissions (i.e., the global warming impact) associated with the use and disposal of a particular piece of refrigeration equipment. It considers two warming impacts: (i) the direct contribution of the refrigerant emissions to the atmosphere (from leaks, servicing losses and end-of-life disposal); and (ii) the indirect contribution due to the CO2 emissions from burning of fossil fuels to generate the electricity needed to run the equipment. TEWI factor can be calculated as (2):
TEWI = Directrefrigerant + Indirectelectricty = [GWP·X] + [αCO2·L·E],
where GWP is the Global Warming Potential of the refrigerant; X is annual leakage of refrigerant, in kg; αCO2 is the conversion factor to change energy use from CO2; L is the operating lifetime of the system, in years; and E is the annual energy consumption (kWh/year).
The refrigerant of the system is R134a having a GWP of 1300 kg CO2/kg R134a. It is assumed that the system loses 5% of the refrigerant charge (390 kg) per year and that at the end of its lifetime, 90% of the machine’s refrigerant is recovered. The addition of the evaporative cooling pads does not affect the refrigerant charge, so the direct refrigerant emissions are equal operating “without” and “with” the evaporative cooling pads.
The lifetime of the chillers is 15 years and the CO2 energy conversion factor is 0.331 kg CO2/kWh. The improvement of the energy efficiency of the system implies reducing the electricity energy needed to run the equipment, so the indirect CO2 emissions from electricity generation are reduced when the system operates with the evaporative cooling pad.
TEWI of the system without an evaporative cooling pad is 4632.0 tCO2 and under the operation of the evaporative cooling pads before the condensers, there is a reduction of about 1000.0 tCO2 during the lifetime of the system.

3.3. Economic Analysis

Each chiller has a cooling capacity of 1442.3 kW, with an average operation of 12 hours/day during an average of 92 days, so the operating hours sum up 1104 h during the summer period.
The energy consumption of the chiller plant, according to the load factor of the ESEER for the summer season, without the evaporative cooling pad using the calculated COP values of Table 3, is 247.78 MWh. By other side, considering the operation of the evaporative cooling pads when the load factor exceeds 7%, the electricity consumption is 215.18 MWh. Power consumption of the fans has not been increased due to the presence of the evaporative cooling pads and power consumption of the pump (500 W) has not been considered. Thus, the energy savings in the summer period are 32.6 MWh, using evaporative pads according to the strategy of using them in the hours with higher ambient temperature.
The economic study is based on the Pay-Back, the Net Present Value (NPV) and the Internal Rate of Return (IRR) considering the following initial conditions:
  • The price of the electricity in August was 0.114 €/kWh.
  • The installation of the evaporative cooling pads in a chiller involves an initial investment of 6000 € and increases the maintenance cost of the chiller.
  • The performance of the evaporative cooling pads decreases with water quality. Hard water produces calcareous deposits increased by lack of cleaning, depending on maintenance conditions. The building maintenance services disassemble and clean the pads during the winter season. Maintaining this routine, it is expected that the performance of the panels will be decreased by 25% per year, thus the lifetime of the pads is 4 years, when they will have to be replaced. The price of the evaporative cooling pads is 3500 €.
  • A timeframe of 15 years is established for the economic study, considering the expected life of the chiller.
  • Cost of capital (k) is updated according to the Consumer Price Index (CPI).
  • Considering these data, capital flow and, thus, the Net Present Value can be calculated according to the following expression (3):
NPV = A + i = 1 n Q i ( 1 + k ) i ,
where A is the initial investment; n is the timeframe; Q is the capital flow (savings-investment); and k is the cost of capital. Table 4 shows the economic savings due to decrease in energy consumption per year, the investment and operating costs and the NPV per year.
It can be seen that the incorporation of evaporative cooling pads pays off in the second year, although the fact that new panels have to be installed each four years. The improvement in the ESEER for the summer season gives an annual economic savings due to the reduction in the energy consumption of 3716.40 euros. The NPV at the 15th year is 23,119.64 euros without considering that, as with the incorporation of the evaporative cooling pads the electricity consumption is lower than the maximum contracted power, penalties for power exceedance are removed.

4. Conclusions

The incorporation of 100 mm thick evaporative cooling pads before the condenser of air-condenser chiller reduces the condensation temperature by 11 °C, increasing the relative humidity by 50%. Under these conditions, the refrigerant condenses at 30 °C instead of 45 °C.
Based on the measured data of the performance of the chiller plant without and with the evaporative cooling pads, COP values were calculated for each load factor at both conditions, obtaining the average COP values per load factor. With these data, the ESEER has been calculated resulting in an increase from 3.69 without the evaporative cooling pads to 4.83. It represents an improvement of 30.89%.
Taking into account that the incorporation of the evaporative cooling pads does not affect the refrigerant charge but it affects the electricity power consumed due to the improvement of the ESEER, direct refrigerant emissions remain equal for both cases but indirect CO2 emissions associated to power consumption are reduced when the system operates with the evaporative cooling pads. TEWI of the chiller plant has been reduced by 1000.0 tCO2, considering that evaporative cooling pads operates 12.60% of annual hours.
A complete economic analysis of a 15-year project with an estimated capital cost of 4.34% has been carried out. Savings due to the decrease in compressor power consumption caused by the installation of evaporative cooling pads technology are 32.6 MWh, thus an economic saving of 3716.40 € per year. A forecast of annual and accumulated savings has been made using the NPV, obtaining a value of 23,119.64 euros at the 15th year, although having to substitute the evaporative cooling pads each four years and not considering the removal of the pay penalties due to power exceedance.
The payback of the investment is less than two years, so the project is viable, profitable and has a fast return.

Author Contributions

Investigation (Conceptualization, methodology, resources and validation), J.F.S.J.A. and F.J.R.M.; data curation and formal analysis, E.V.G., A.T.G. and F.J.M.R.; writing—original draft preparation, J.F.S.J.A. and E.V.G.; writing—review and editing, P.M.E., A.T.G. and J.M.R.H.; visualization, P.M.E.; supervision, J.F.S.J.A.; funding acquisition and project administration, F.J.R.M. and E.V.G. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by the Education Department of the Regional Government of Castile and Leon and the European Regional Development Fund (ERDF) through the research project: “Análisis de tecnologías energéticamente eficientes para la sostenibilidad de los edificios” (Ref.: VA272P18).

Acknowledgments

The authors want to acknowledge people working on the thermal conditioning and air treatment of the Hospital Rio Hortega for their support and collaboration

Conflicts of Interest

The authors declare no conflict of interest.

Abbreviations

ESEEREuropean Seasonal Energy Efficiency Ratio.
EUROVENTEurope’s Industry Association for Indoor Climate (HVAC), Process Cooling and Food Cold Chain Technologies.
TEWITotal Equivalent Warming Impact.
nZEBNearly Zero Energy Buildings.
IAQIndoor Air Quality.
ECEvaporative condenser.
COPCoefficient of Performance.
GWPGlobal Warming Potential.
NPVNet Present Value.
IRRInternal Rate of Return.
CPIConsumer Price Index.
TCCondensing temperature of refrigerant (°C).
TAAir temperature at the condenser inlet (°C).
TrefMinimum temperature of the medium, where the condenser dissipates (°C).
TDBDry bulb temperature of moist air (°C).
TWBWet bulb temperature of moist air (°C).
TsatAdiabatic saturation temperature of moist air (°C).
RHRelative humidity of moist air (%).
TwWater temperature (°C).
wCooling water flow (kg/s).
CpwSpecific heat of water (kJ/(kg∙°C))
ΔTwDifference between water temperature at the entrance and exit of the unit (°C).
φChiller load factor.
maxPower consumed when the systems are operating at maximum capacity (kW).
XAnnual leakage of refrigerant (kg/year)
αCO2Carbon dioxide emission factor (CO2 equivalent emissions per kWh).
LOperating lifetime of the unit (years).
EEnergy consumption (kWh per year).
kCost of capital.
AInitial investment (€)
QCapital flow (€)

References

  1. European Commission. A Clean Planet for all. A European Strategic Long-Term Vision for A Prosperous, Modern, Competitive and Climate Neutral Economy; European Commission: Brussels, Belgium, 2018. [Google Scholar]
  2. European Commission. Guidelines for the Promotion of Nearly Zero-Energy Buildings and Best Practices to Ensure That, by 2020, All New Buildings are Nearly Zero-Energy Buildings; European Commission: Brussels, Belgium, 2016. [Google Scholar]
  3. Rey-Hernández, J.M.; Yousif, C.; Gatt, D.; Velasco-Gómez, E.; San José-Alonso, J.; Rey-Martínez, F.J. Modelling the long-term effect of climate change on a zero energy and carbon dioxide building through energy efficiency and renewables. Energy Build. 2018, 174, 85–96. [Google Scholar] [CrossRef]
  4. European Parliament and of the Council. Directive 2010/31/EU on the Energy Performance of Buildings; European Parliament and of the Council: Brussels, Belgium, 2010. [Google Scholar]
  5. ASHRAE. ASHRAE Handbook—HVAC Systems and Equipment; ASHRAE: Atlanta, GA, USA, 2016. [Google Scholar]
  6. ASHRAE. ASHRAE Handbook—Fundamentals; ASHRAE: Atlanta, GA, USA, 2017. [Google Scholar]
  7. Walser, S.M.; Gerstner, D.G.; Brenner, B.; Höller, C.; Liebl, B.; Herr, C.E. Assessing the environmental health relevance of cooling towers—A systematic review of legionellosis outbreaks. Int. J. Hyg. Environ. Health 2014, 217, 145–154. [Google Scholar] [CrossRef] [PubMed]
  8. Wei, J.; Liu, J.; Xu, X.; Ruan, J.; Li, G. Experimental and computational investigation of the thermal performance of a vertical tube evaporative condenser. Appl. Therm. Eng. 2019, 160, 114100. [Google Scholar] [CrossRef]
  9. Chien, L.H.; Xu, J.J.; Yang, T.F.; Yan, W.M. Experimental study on water spray uniformity in an evaporative condenser of a water chiller. Case Stud. Therm. Eng. 2019, 15, 100512. [Google Scholar] [CrossRef]
  10. Fiorentino, M.; Starace, G. Experimental Investigations on Evaporative Condensers Performance. Energy Procedia 2017, 140, 458–466. [Google Scholar] [CrossRef]
  11. Fiorentino, M.; Starace, G. Sensitivity Analysis of Evaporative Condensers Performance Using an Experimental Approach. Energy Procedia 2017, 126, 345–352. [Google Scholar] [CrossRef]
  12. Harby, K.; Gebaly, D.R.; Koura, N.S.; Hassan, M.S. Performance improvement of vapour compression cooling systems using evaporative condenser: An overview. Renew. Sustain. Energy Rev. 2016, 58, 347–360. [Google Scholar] [CrossRef]
  13. Martínez, P.; Ruiz, J.; Cutillas, C.G.; Martínez, P.J.; Kaiser, A.S.; Lucas, M. Experimental study on energy performance of a split air-conditioner by using variable thickness evaporative cooling pads coupled to the condenser. Appl. Therm. Eng. 2016, 105, 1041–1050. [Google Scholar] [CrossRef]
  14. Saheb, Y.; Becirspahic, S.; Simon, J. Effect of the Certification on Chillers Energy Efficiency. In Proceedings of the International Conference “Improving Energy Efficiency in Commercial Buildings-IEECB’06”, Frankfurt, Germany, 26–27 April 2006. [Google Scholar]
  15. AEN/CTN 100 Climatización. UNE 100001: Climatización. Condiciones Climáticas Para Proyectos; AENOR: Madrid, Spain, 2001. [Google Scholar]
  16. Fischer, S.K. Total equivalent warming impact: A measure of the global warming impact of CFC alternatives in refrigerating equipment. Int. J. Refrig. 1993, 16, 423–428. [Google Scholar] [CrossRef]
Figure 1. (a) Chiller plant at the roof of the hospital; (b) Scheme of principle.
Figure 1. (a) Chiller plant at the roof of the hospital; (b) Scheme of principle.
Energies 13 02218 g001
Figure 2. Screenshot of the Control System of the chiller plant.
Figure 2. Screenshot of the Control System of the chiller plant.
Energies 13 02218 g002
Figure 3. Power consumption of the building in one year, without changes in the cooling system.
Figure 3. Power consumption of the building in one year, without changes in the cooling system.
Energies 13 02218 g003
Figure 4. Evaporative cooling pad CELdek 7060-15.
Figure 4. Evaporative cooling pad CELdek 7060-15.
Energies 13 02218 g004
Figure 5. Chillers without (a) and with (b) evaporative cooling pads, (c) Schematic diagram.
Figure 5. Chillers without (a) and with (b) evaporative cooling pads, (c) Schematic diagram.
Energies 13 02218 g005
Figure 6. Outside temperature on August 10th and 17th and the average temperature.
Figure 6. Outside temperature on August 10th and 17th and the average temperature.
Energies 13 02218 g006
Figure 7. (a) Inlet air temperature and (b) condensation temperature “with” and “without” evaporative cooling pad.
Figure 7. (a) Inlet air temperature and (b) condensation temperature “with” and “without” evaporative cooling pad.
Energies 13 02218 g007aEnergies 13 02218 g007b
Figure 8. Determination of Coefficient of Performance (COP) “with” and “without” of refrigeration systems in service.
Figure 8. Determination of Coefficient of Performance (COP) “with” and “without” of refrigeration systems in service.
Energies 13 02218 g008
Table 1. Evaporative condenser types and condensation temperature over saturation temperature or spray water.
Table 1. Evaporative condenser types and condensation temperature over saturation temperature or spray water.
Type of Evaporative Condensers (EC)ConfigurationCondensation Temperature (Tc)
Indirect Energies 13 02218 i001Tc = (Tw + 20) °C
TA = (Tw + 5 + 5 + 5) °C
(Tw + 5 + 5) °C
(Tw + 5) °C (approach)
Tref = Tw
DirectDryRecirculation Energies 13 02218 i002TC = (Tsat + 15) °C
TA = (Tsat + 5 + 5) °C
Tsat + 5 °C (approach)
Tref = Tsat
Lost water Energies 13 02218 i003TC = (Tw + 15) °C
TA = (Tw + 5 + 5) °C
(Tw + 5) °C (approach)
Tref = Tw
WetRecirculation Energies 13 02218 i004TC = (Tsat + 10) °C
(Tsat + 5) °C (approach)
Tref = Tsat
Lost water Energies 13 02218 i005Tc = (Tw + 10) °C
(Tw + 5) °C (approach)
Tref = Tw
Table 2. Characteristics of the installed evaporative cooling pad, the selected cooling pad is highlighted with the grey background color.
Table 2. Characteristics of the installed evaporative cooling pad, the selected cooling pad is highlighted with the grey background color.
CELdek 7060-15 Thickness (mm)100150200300
Input temperature (°C)33.133.133.133.1
Adiabatic saturation temperature (°C)19.119.119.119.1
Saturation efficiency (%)68818896
Pressure drop (Pa)46812.5
Output temperature (°C)23.621.820.819.7
Table 3. Average COP values for each load factor of the chiller plant.
Table 3. Average COP values for each load factor of the chiller plant.
% Load“Without” Cooling Pad“With” Cooling Pad
1002.673.45
753.224.2
503.784.95
254.335.7
Table 4. Net Present Value (NPV) per year.
Table 4. Net Present Value (NPV) per year.
YearSavings (€)Investment (€)Capital Flow (€) [ Capital   Flow ( 1 + K ) n ] NPV (€)
0 6000.00−6000.00−6000.00−6000.00
13716.40300.003416.403274.30−1725.70
23716.40300.003416.403138.10412.40
33716.40300.003416.403007.573419.97
43716.404000.00−283.60−239.283180.69
53716.40300.003416.402762.585943.27
63716.40300.003416.402647.678590.94
73716.40300.003416.402537.5411,128.48
83716.404000.00−283.60−201.8810,926.60
93716.40300.003416.402330.8313,257.43
103716.40300.003416.402233.8815,491.31
113716.40300.003416.402140.9617,632.28
123716.404000.00−283.60−170.3317,461.95
133716.40300.003416.401966.5619,428.51
143716.40300.003416.401884.7621,313.27
153716.40300.003416.401806.3723,119.64

Share and Cite

MDPI and ACS Style

Rey Martínez, F.J.; San José Alonso, J.F.; Velasco Gómez, E.; Tejero González, A.; Esquivias, P.M.; Rey Hernández, J.M. Energy Consumption Reduction of a Chiller Plant by Adding Evaporative Pads to Decrease Condensation Temperature. Energies 2020, 13, 2218. https://doi.org/10.3390/en13092218

AMA Style

Rey Martínez FJ, San José Alonso JF, Velasco Gómez E, Tejero González A, Esquivias PM, Rey Hernández JM. Energy Consumption Reduction of a Chiller Plant by Adding Evaporative Pads to Decrease Condensation Temperature. Energies. 2020; 13(9):2218. https://doi.org/10.3390/en13092218

Chicago/Turabian Style

Rey Martínez, Francisco J., Julio F. San José Alonso, Eloy Velasco Gómez, Ana Tejero González, Paula M Esquivias, and Javier M. Rey Hernández. 2020. "Energy Consumption Reduction of a Chiller Plant by Adding Evaporative Pads to Decrease Condensation Temperature" Energies 13, no. 9: 2218. https://doi.org/10.3390/en13092218

APA Style

Rey Martínez, F. J., San José Alonso, J. F., Velasco Gómez, E., Tejero González, A., Esquivias, P. M., & Rey Hernández, J. M. (2020). Energy Consumption Reduction of a Chiller Plant by Adding Evaporative Pads to Decrease Condensation Temperature. Energies, 13(9), 2218. https://doi.org/10.3390/en13092218

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop