3.1. Superposition of Loop Currents
If there is a single-pole ground fault occurring at a substation, there will be a superposition of currents at the fault node (index
), as shown in
Figure 6. This conclusion is also drawn in Fickert et al. [
13].
In the example shown in this subsection, the fault is fed only by one side of the line. The load currents of the phase conductors are assumed to be symmetrical and are therefore ignored. The local grounding current of every substation is distributed along several paths. At the fault node these are represented by the impedances to earth of the supplied low voltage grid , the substations’s grounding electrodes and surrounding infrastructure .
This complex model in presented to give an understanding of all die current loops existing in the grounding system. For practical purposes, it may be simplified by summarising the impedances to earth to one impedance
with Equation (
18), which leads to the model shown in
Figure 4. Direct measurement of all illustrated currents is often not possible, because there is no defined point of entry to the grounding system. In this case, the grounding current
at the substation
can be calculated with Equation (
19), which results from the sum of current at this node.
The screen currents on the feeding side are primarily driven by the voltage induced into the screen-earth loop. Due to its inductive origin described by Equation (
3), the summarised screen current
has a phase angle close to
relative to that of the fault current
. This leads to a neutralization at the fault node and thus to a lower grounding current
. The current
can be determined and measured as a difference of the fault current
and the screen currents
and
. It should be noted that the screen current might not only contain the current share of the medium voltage screens (index MV), but also the current flowing through other conductors (index LV) running in parallel, as indicated in
Figure 6 and given in Equation (
20).
According to Equation (
19), the grounding current
is an artificial quantity containing different shares. These are the current flowing through the grounding system of the substation (Sst), the connected low voltage lines (LV) and other infrastructure (Is). Some current shares are expected to flow back to the neutral point through metallic conductors (as marked with the grey lines in
Figure 6). Therefore, they never enter the physical earth and have no potential raising effect. For that reason, the calculated current
is not mandatory equal to the current that actually flows through the earth. The grounding systems of adjacent substations may not be independent of each other, especially not in urban regions. For the analytical review, it is practical to define impedances to earth
and neglect the connections to other substations in order to achieve simplification and solvability of the model.
There may also be loops with earth return formed by the grounding system of the substation and connected conductors. If these loops are excited by inductive coupling (as implied grey in
Figure 6), rather by the fault current
or by other influences, a current flows inside of the loop and overlays with the grounding current driven through the substation’s grounding system. Because of this superposition, it is even possible that the current
becomes bigger than the grounding current
.
According to this effect and the mutual effect of distributed grounding electrodes, already mentioned in
Section 2.4, it is difficult to say, which of the current shares are caused by the fault current
and are part of the local earth current. It is also difficult to measure all these small current shares separately. Therefore, it is more practical to consider the summarised grounding current
for the comparison of measured data and calculations. This also results in a more practical simplification of the chain conductor model as illustrated in
Figure 4; but it also makes it impossible to differentiate between the influences of the various grid structures in a dedicated way as outlined in the following paragraphs.
The grounding current may also flow through the local impedances to earth
of adjacent substations. If they are placed on the feeding side of the line, the local grounding current
results from the superposition of the loop currents
and
flowing through the left- and right-side mesh touching
. The global grounding current
can not be measured, for it flows through grounding electrodes distributed in the whole electrical grid. From a mathematical point of view, the reduction factor
generally describes the ratio between the grounding current
and the fault current
:
The factor
characterizes the effect of all distributed grounding electrodes. For the evaluation of the local electricity distribution, it seems to be practical to define local reduction factors. The screen reduction factor
is based on the grounding current
at the substation and describes the reducing effect of the connected screen conductors:
If all the screens are inductively coupled to the fault current, the local reduction factor is analogue to shielding factor
known from the signal theory. The substation reduction factor
only considers the current
through the local grounding electrodes of the substation:
It additionally assumes these electrodes to form a voltage gradient, which is not influenced by other structures connected to the substation’s potential equalization bar. Both factors, and , are therefore theoretical quantities. In most constellations, it is difficult to separate the individual influencing factors.
There are already numerous publications addressing current reduction factors of cable systems, such as Fickert et al. [
13], Acevski et al. [
25], Medic et al. [
26], Popović [
27,
28,
29], Sarajcev et al. [
30], Collela et al. [
31] and many more. All of them provide methods for calculating the overall reduction effect. A separation which explicitly shows the influence of the individual current paths is not made. Furthermore, the frequency dependency of the reduction factor is not discussed.
3.2. Frequency Dependent Current Distribution
For the inductive coupling impedances and the self impedances of the return conductors are strongly frequency-dependent, the distribution of the fault current in the grounding system will be different for harmonics in the current than for the component of the fundamental frequency. Thus, the reduction factors, named in
Section 3.1, are functions of the frequency
.
The share of the screening currents
excited by the fault current
, can be calculated for one stationary frequency with Equation (
24), which results from the sum of voltages in the mesh. Here the impedances
define the effective grounding impedances of the left- and right-side chain conductors included in the mesh
x. To get the total screening current
, the coupling to the others screens has to be taken into account, according to Equation (
25).
The loop impedance is strongly affected by the resistances
and
of each screen and the grounding, the screens may carry a similar current share of the fundamental frequency. As allready implied in
Section 2.3 and
Figure 3, the self impedance
and the coupling impedance
of the screen of the cable, carrying the fault current
, become almost equal for higher frequency. As the influence of the earth return becomes less, the induced screen current
becomes almost equal to the fault current
, but with the inverse phase angle. This leads to an almost complete elimination of harmonics of higher order in the current at the fault node and thus to a low share of them in the grounding current
. Due to this, all the reduction factors
become smaller for currents of higher frequency.
Due to the equally growing self impedance
of the more distant screens but a lower coupling, the related currents in these conductors become smaller with increasing frequency. The remaining currents are mainly circular currents between the screens, which are driven by the different induced voltages in the loops. They are increasingly dominant in the higher frequency band, for the couple impedances between the screens and the faulty conductor begin to differ from each other, as illustrated in
Figure 3. This effect can also be extracted from the different phase angles of the screen currents, as shown further below in
Section 4.2.
The remaining grounding current splits up between the grounding system of the substation and all the other conductors connected to the local equipotential bonding. The ratio is depending on the number of connections and the terminating impedances . If the resistance of these additional conductive paths is low, their impedance is dominated by their reactance for higher frequencies. As the impedance can be assumed as an almost constant resistance, harmonic shares in the grounding current tend to flow through the substations grounding electrodes.
Big and meshed low voltage grids have an impedance to earth much lower than the earth transition impedance of the substation. Therefore, they usually carry almost the whole grounding current . Due to the reduction effect of the screens, the grounding current is dominated by lower frequencies. Thus the low voltage connections, as well as other infrastructure, have a huge reducing effect on the local earth current with the fundamental frequency.