An Experimental Comparison of the Performances of a Small Water-to-Water Heat Pump Working with R1234ze(E) and Its Mixture R515B †
Abstract
:1. Introduction
2. Experimental Setup and Experimental Procedure
2.1. Experimental Setup
2.2. Refrigerant Tested and Testing Conditions
2.3. Experimental Procedure
- At the beginning of each test, the pumps of the cold water + ethylene glycol loop and of the hot water loop are switched on. The rotational frequency of each pump shaft is set to the value required to guarantee the mass flow rates needed by the test (see experimental conditions in Table 4). This value is continuously monitored during the test and is adjusted to keep the mass flow rate constant.
- The compressor is switched on and its shaft rotational frequency is set to the value required by the test. At the same time, the electronic expansion valve begins to modulate its cross-section area in order to guarantee a superheating at evaporator outlet equal to 5 K.
- The temperatures of the cold water + ethylene glycol and of the hot water that respectively flow through the evaporator and the condenser begin changing. In both the secondary fluid loops, a PID (Proportional Integral Derivative) controller acts on the 3-way valve with the aim of setting the secondary fluid temperature at heat exchanger outlet to the value required by the test. During the test, the PID controllers continuously adjust the 3-way valve position to keep the outlet temperatures to the set-point.
- Once the set-point temperatures are reached, the data acquisition starts with a sampling frequency equal to 1 Hz. For each measured pressure and temperature, the moving average over the last 900 samples is computed. For each of them, the entire 900 samples batch is checked to lay within ±2.5 kPa (for the pressures) and ±0.2 K (for the temperatures) with respect to the just calculated moving average. When this constraint is simultaneously satisfied by all the measured pressures and temperatures simultaneously, the test is considered in steady-state condition.
- Once steady-state operation is achieved, the data acquisition starts and further 900 samples are recorded for data analysis. An additional check of the accuracy of the test is performed at its end calculating the refrigerant-side and the secondary fluid-side heat transfer rates at the evaporator and at the condenser. The test is considered valid if the two values agree within ±4% with respect to their average value, otherwise it is repeated.
2.4. Data Reduction and Uncertainty Calculation
3. Results
4. Conclusions
Author Contributions
Funding
Data Availability Statement
Acknowledgments
Conflicts of Interest
Nomenclature
isobaric heat capacity (J·kg−1·K−1) | |
Coefficient of performance (-) | |
enthalpy (J·kg−1) | |
mass flow rate (kg·s−1) | |
heat transfer rate (W) | |
Student’s distribution multiplier at 95% confidence level (-) | |
temperature (K) | |
uncertainty (various) | |
compressor swept volume (m3·s−1) | |
directly measured quantity (various) | |
calculated quantity (various) | |
power (W) | |
Greek symbols | |
pinch point (K) | |
volumetric efficiency (-) | |
density (kg·m−3) | |
standard deviation (various) | |
Subscripts | |
COMP | compressor |
COND | condenser |
DIS | discharge of the compressor |
EVAP | evaporator |
IN | inlet |
OUT | outlet |
REF | refrigerant |
SAT | saturation |
W | water |
References
- European Union. Regulation (EU). No 573/2024 of the European Parliament and the council of 7 February 2024 on fluorinated greenhouse gases, amending Directive (EU) 2019/1937 and repealing Regulation (EU) No 517/2014. Off. J. Eur. Union 2024, 1–67. Available online: https://eur-lex.europa.eu/eli/reg/2024/573/oj (accessed on 23 September 2024).
- United Nations. The amendment to the Montreal Protocol agreed by the Twenty-Eighth Meeting of the Parties (Kigali, 10–15 October 2016). United Nations Climate Change, 2013. The Paris Agreement. Available online: https://unfccc.int/processand-meetings/the-paris-agreement/the-paris-agreement (accessed on 23 September 2024).
- Ally, M.R.; Sharma, V.; Nawaz, K. Options for low-global-warming-potential and natural refrigerants part I: Constrains of the shape of the P–T and T–S saturation phase boundaries. Int. J. Refrig. 2019, 106, 144–152. [Google Scholar] [CrossRef]
- Nawaz, K.; Ally, M.R. Options for low-global-warming-potential and natural refrigerants part 2: Performance of refrigerants and systemic irreversibilities. Int. J. Refrig. 2019, 106, 213–224. [Google Scholar] [CrossRef]
- Calleja-Anta, D.; Nebot-Andres, L.; Cabello, R.; Sánchez, D.; Llopis, R. A3 and A2 refrigerants: Border determination and hunt for A2 low-GWP blends. Int. J. Refrig. 2022, 134, 86–94. [Google Scholar] [CrossRef]
- Bell, I.H.; Domanski, P.A.; McLinden, M.O.; Linteris, G.T. The hunt for nonflammable refrigerant blends to replace R-134a. Int. J. Refrig. 2019, 104, 484–495. [Google Scholar] [CrossRef]
- Mota-Babiloni, A.; Mateu-Royo, C.; Navarro-Esbrí, J.; Barragán-Cervera, Á. Experimental comparison of HFO-1234ze(E) and R-515B to replace HFC-134a in heat pump water heaters and moderately high temperature heat pumps. App. Therm. Eng. 2021, 196, 117256. [Google Scholar] [CrossRef]
- Mateu-Royo, C.; Mota-Babiloni, A.; Navarro-Esbrí, J.; Barragán-Cervera, Á. Comparative analysis of HFO-1234ze(E) and R-515B as low GWP alternatives to HFC-134a in moderately high temperature heat pumps. Int. J. Refrig. 2021, 124, 197–206. [Google Scholar] [CrossRef]
- Azzolin, M.; Berto, A.; Bortolin, S.; Del Col, D. Condensation heat transfer of R1234ze(E) and its A1 mixtures in small diameter channels. Int. J. Refrig. 2022, 137, 153–165. [Google Scholar] [CrossRef]
- Diani, A.; Liu, Y.; Wen, J.; Rossetto, L. Experimental investigation on the flow condensation of R450A, R515B, and R1234ze(E) in a 7.0 mm OD micro-fin tube. Int. J. Heat Mass Transf. 2022, 196, 123260. [Google Scholar] [CrossRef]
- Liu, Y.; Rossetto, L.; Diani, A. Flow Boiling of R450A, R515B, and R1234ze(E) Inside a 7.0 mm OD Microfin Tube: Experimental Comparison and Analysis of Boiling Mechanisms. Appl. Sci. 2022, 12, 12450. [Google Scholar] [CrossRef]
- Colombo, L.P.M.; Frigerio, D.; Lucchini, A.; Molinaroli, L. Experimental assessment of the use of R515B as R1234ze(E) alternative in a small water-to-water heat pump. In Proceedings of the 26th International Congress of Refrigeration, Paris, France, 21–25 August 2023. [Google Scholar]
- Janković, Z.; Sieres Atienza, J.; Martínez Súarez, J. Thermodynamic and heat transfer analyses for R1234yf and R1234ze(E) as drop-in replacements for R134a in a small power refrigerating system. App. Therm. Eng. 2015, 80, 42–54. [Google Scholar] [CrossRef]
- Colombo, L.; Lucchini, A.; Molinaroli, L. Experimental analysis of the use of R1234yf and R1234ze(E) as drop-in alternatives of R134a in a water-to-water heat pump. Int. J. Refrig. 2020, 115, 18–27. [Google Scholar] [CrossRef]
- Molinaroli, L.; Lucchini, A.; Colombo, L.P.M. Drop-in analysis of R450A and R513A as low-GWP alternatives to R134a in a water-to-water heat pump. Int. J. Refrig. 2022, 135, 139–147. [Google Scholar] [CrossRef]
- Lemmon, E.W.; Bell, I.; Huber, M.L.; McLinden, M.O. NIST Standard Reference Database 23: Reference Fluid Thermodynamic and Transport Properties-REFPROP, Version 10.0, National Institute of Standards and Technology. 2018. Available online: https://www.nist.gov/srd/refprop (accessed on 18 November 2024).
- Moffat, R. Describing the uncertainties in experimental results. Exp. Therm. Fluid Sci. 1988, 1, 3–17. [Google Scholar] [CrossRef]
- Domanski, P.; Brown, J.; Heo, J.; Wojtusiak, J.; McLinden, M. A thermodynamic analysis of refrigerants: Performance limits of the vapor compression cycle. Int. J. Refrig. 2014, 38, 71–79. [Google Scholar] [CrossRef]
Component | Parameter | Value |
---|---|---|
Compressor | Swept volume @ 50 Hz | 13.15 m3/h |
Shaft rotational frequency | 30 Hz–87 Hz | |
Oil type | POE ISO 32 | |
Oil charge | 1.1 dm3 | |
Condenser | Dimensions | 289 mm × 119 mm × 93.6 mm |
Number of plates | 40 | |
Evaporator | Dimensions | 376 mm × 119 mm × 71.2 mm |
Number of plates | 30 | |
Expansion valves | Capacity range | 175 W–1750 W |
1690 W–16900 W | ||
Pumps (both cold heat source and hot heat sink loops) | Nominal flow rate | 28.7 m3/h |
Nominal head | 160 kPa | |
Shaft rotational frequency | 16 Hz–58 Hz |
Parameter | Instrument | Range |
---|---|---|
Refrigerant mass flow rate | Coriolis mass flow meter (Endress Hauser, Cernusco sul Naviglio, Italy) | 0 kg/h–300 kg/h |
Refrigerant pressure (low side) | Pressure transducer (Huba Control, Würenlos, Switzerland) | 0 kPa–700 kPa |
Refrigerant pressure (high side) | Pressure transducer (Huba Control, Würenlos, Switzerland) | 0 kPa–4000 kPa |
Refrigerant temperature | RTD Pt 100 (Tersid, Sesto San Giovanni, Italy) | 243.15 K–373.15 K |
Compressor power | Power meter (Cewe, Nyköping, Sweden) | 0 W–4000 W |
Water mass flow rate | Vortex flow meter (Huba Control, Würenlos, Switzerland) | 0.21 m3/h–3 m3/h |
Water temperature | RTD Pt 100 (Tersid, Sesto San Giovanni, Italy) | 263.15 K–353.15 K |
Parameter | R1234ze(E) | R515B |
---|---|---|
Composition | Pure | R1234ze(E) 91.1%w R227ea 8.9%w |
Critical pressure | 3634.9 kPa | 3583.9 kPa |
Critical temperature | 382.51 K | 382.03 K |
Molar mass | 114.04 g/mol | 117.48 g/mol |
95.13 J/(mol·K) | 97.18 J/(mol·K) | |
Normal Boiling Point (Dew) | 254.18 K | 254.37 K |
Glide (p = 101,325 kPa) | 0 K | 0.021 K |
ODP (Ozone Depletion Potential) | 0 | 0 |
GWP (Global Warming Potential) (IPCC 6th revision) | 1.37 | 321 |
ASHRAE classification | A1 | A1 |
Test | Compressor | Evaporator | Condenser | ||||
---|---|---|---|---|---|---|---|
1 | 50 Hz | As Test 03 | * | 268.15 K | As Test 03 | * | 308.15 K |
2 | 50 Hz | As Test 03 | * | 273.15 K | As Test 03 | * | 308.15 K |
3 | 50 Hz | Identified | 283.15 K | 278.15 K | Identified | 303.15 K | 308.15 K |
4 | 50 Hz | As Test 03 | * | 283.15 K | As Test 03 | * | 308.15 K |
5 | 50 Hz | As Test 03 | * | 288.15 K | As Test 03 | * | 308.15 K |
6 | 50 Hz | As Test 08 | * | 268.15 K | As Test 08 | * | 318.15 K |
7 | 50 Hz | As Test 08 | * | 273.15 K | As Test 08 | * | 318.15 K |
8 | 50 Hz | Identified | 283.15 K | 278.15 K | Identified | 313.15 K | 318.15 K |
9 | 50 Hz | As Test 08 | * | 283.15 K | As Test 08 | * | 318.15 K |
10 | 50 Hz | As Test 08 | * | 288.15 K | As Test 08 | * | 318.15 K |
11 | 50 Hz | As Test 13 | * | 268.15 K | As Test 13 | * | 328.15 K |
12 | 50 Hz | As Test 13 | * | 273.15 K | As Test 13 | * | 328.15 K |
13 | 50 Hz | Identified | 283.15 K | 278.15 K | Identified | 323.15 K | 328.15 K |
14 | 50 Hz | As Test 13 | * | 283.15 K | As Test 13 | * | 328.15 K |
15 | 50 Hz | As Test 13 | * | 288.15 K | As Test 13 | * | 328.15 K |
16 | 50 Hz | As Test 18 | * | 268.15 K | As Test 18 | * | 338.15 K |
17 | 50 Hz | As Test 18 | * | 273.15 K | As Test 18 | * | 338.15 K |
18 | 50 Hz | Identified | 283.15 K | 278.15 K | Identified | 333.15 K | 338.15 K |
19 | 50 Hz | As Test 18 | * | 283.15 K | As Test 18 | * | 338.15 K |
20 | 50 Hz | As Test 18 | * | 288.15 K | As Test 18 | * | 338.15 K |
21 | 50 Hz | As Test 23 | * | 268.15 K | As Test 23 | * | 348.15 K |
22 | 50 Hz | As Test 23 | * | 273.15 K | As Test 23 | * | 348.15 K |
23 | 50 Hz | Identified | 283.15 K | 278.15 K | Identified | 343.15 K | 348.15 K |
24 | 50 Hz | As Test 23 | * | 283.15 K | As Test 23 | * | 348.15 K |
25 | 50 Hz | As Test 23 | * | 288.15 K | As Test 23 | * | 348.15 K |
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2024 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/).
Share and Cite
Molinaroli, L.; Lucchini, A.; Colombo, L.P.M. An Experimental Comparison of the Performances of a Small Water-to-Water Heat Pump Working with R1234ze(E) and Its Mixture R515B. Energies 2024, 17, 5812. https://doi.org/10.3390/en17235812
Molinaroli L, Lucchini A, Colombo LPM. An Experimental Comparison of the Performances of a Small Water-to-Water Heat Pump Working with R1234ze(E) and Its Mixture R515B. Energies. 2024; 17(23):5812. https://doi.org/10.3390/en17235812
Chicago/Turabian StyleMolinaroli, Luca, Andrea Lucchini, and Luigi Pietro Maria Colombo. 2024. "An Experimental Comparison of the Performances of a Small Water-to-Water Heat Pump Working with R1234ze(E) and Its Mixture R515B" Energies 17, no. 23: 5812. https://doi.org/10.3390/en17235812
APA StyleMolinaroli, L., Lucchini, A., & Colombo, L. P. M. (2024). An Experimental Comparison of the Performances of a Small Water-to-Water Heat Pump Working with R1234ze(E) and Its Mixture R515B. Energies, 17(23), 5812. https://doi.org/10.3390/en17235812