5.2. Variation Law of Actual Optical Fiber Strain with Corrosion Time
The strain-time curves before and after temperature compensation for specimens 2-150# and 2-300# are shown as
Figure 11,
Figure 12 and
Figure 13, and the test parameters for significance of fitting curve is list in
Table 2,
Table 3,
Table 4,
Table 5,
Table 6 and
Table 7. The vertical axis represents the raw strain measured from the spiral distributed fiber sensor and actual strain subtracted the induced-strain by the temperature fluctuation. The top and below horizonal axes represent the mass loss rate and accumulated corrosion duration. The actual distributed strain of sensing fiber represents the corrosion-induced strain, whereas raw strain comprises that induced not only by corrosion expansion but also a varied temperature due to a corrosion current.
- (1)
Reinforced concrete specimen with a 67 mm concrete cover
The strain-time curves are shown in
Figure 11 before and after temperature compensation of 2-150# specimen. Since the distributed sensor located in steel bar layer is broken during the mold removal process, only the distributed sensor wrapped on the mortar layer is available. It is observed from the figures that the strain measured from the distributed sensor gradually grow, subsequently increases rapidly after 50 h. To the end, the strain increases to a maximum value and remain constant. Additionally, the concrete specimen cracks at 50 h, close to the observed crack time (55 h), the difference between the predicted cracking corrosion rate and the actual corrosion rate, observed crack time of 55 h, is approximately 0.17%. Enlarging the curve before specimen cracking, the raw strain along the distributed sensor increases to 150
sharply before 2 h in the inner illustration. Subsequently, the fiber strain increases linearly. Meanwhile, a rapid strain growth in first 2 h induced by the current is consistent with the temperature variation (
Figure 9). Thus, it is essential to use a temperature sensor for decreasing a tested strain error. In addition, the actual optical fiber strain (0~11 h) remains constant, which is defined as the corrosion rate threshold (0.36%), being consistent with the existed literature [
28,
32]. The thickness of porous zone
is approximately 0–20 um [
23], which contributes to the corrosion rate threshold. This reason is that the corrosion product used to fill porous area offsets the corrosive force, simultaneously alleviates the strain from a distributed sensor. Likewise, as more rusts are produced and accumulated at the concrete-steel interface, the expansive strain begins to increase until the corrosion products generate a compress on the surrounding concrete. Consequently, more corrosion products generate an expansive strain causing a distributed fiber deformation. Then the corrosion rate threshold is in turn increased.
Meanwhile, the raw and actual strains in the distributed sensor monotonically increase over time and corrosion mass loss rate. Each curve shows four stages, which the I, II, III stages are consistent with the degradation of reinforcement concrete in
Figure 2. Regression analysis is performed to determine the equation of stages 2, 3 and 4. Before reinforcement concrete cracks, the slope of the fitting equation between the distributed strain and corrosion mass loss rate is 125
as shown in
Table 2, while the slope of the fitting curve between the distributed strain and corrosive time is 3.37
as shown in
Table 3, less than 16.8
in this literature[
28,
32]. Possibly, their difference is attributed to their distinct thickness of concrete cover. This 3.1 section shows that the helix strain is dependent on the protective layer thickness greater than 35 mm. Simultaneously, the
P value of regression equation less than 0.05 illustrates that the linear arrogation equation developed in this work is credible.
- (2)
Reinforced concrete specimen with a 142 mm concrete cover
Figure 12a and
Figure 13a indicates the relationship between corrosion time and the distributed strains from the distributed sensor located in steel bar layer and mortar layer of specimen 2-300#. At first 2 h, the raw strain wrapped on the steel bar layer and the mortar layer increases rapidly to 200
and 250
up to 40 h. Subsequently, the optical fiber strain rises linearly. At the time t = 78 h, the raw strain of optical fiber in the reinforcement layer increases to 1000
and that in the mortar layer increases to 750
. At 80 h, the raw strain in the reinforcement layer and mortar layer decreases sharply (the reinforcement layer decreases to 500
and the mortar layer to 300
), subsequently, continue to decrease rapidly to 300
and 150
at 120 h. The above-mentioned phenomena are consistent with the current fluctuations adjusted from 0.1 A to 0.05 A and 0.03 A. At the time of 225 h, the epoxy resin layer is peeled off. The corrosion experiment is forced to stop, resulting in a strain decrease and then increase (at the marking position in
Figure 12a) after continuing to carry on the corrosion experiment. It is also found that the influence of the factors such as current adjustment and sealant leakage on the fiber strain before the crack of concrete are eliminated after temperature compensation(
Figure 12b and
Figure 13b). Moreover, the raw and actual fiber strain fluctuations after concrete cracks depend on the ambient temperature.
Meanwhile, the distributed expansive strain at the initial stage of specimen corrosion (about 0~40 h) after temperature compensation fail to be generated. The called corrosion rate threshold is about 1.34%, and cracking occurs at 160 h close to the observed cracking time of 155 h. The error is approximately 0.14%. Additionally, the distributed strain depends on a rising ambient temperature induced by the electro-accelerated corrosion.
To the end, the raw and actual strains from the distributed sensor monotonically increase over time and corrosion mass loss rate. Each curve shows three stages, being consistent with the degradation of reinforcement concrete. Regression analysis is performed to determine the equation of stages 2, 3 and 4. Before reinforcement concrete cracks, the slope of the fitting equation between the distributed strain and corrosion mass loss rate from the distributed sensor on the steel bar and mortar layer is 121
and 156
, as shown in
Table 4 and
Table 6, respectively. While their slopes of the fitting equation are 2.98
and 3.41
shown in
Table 5 and
Table 7, basically being consistent with 2-150# specimen. Simultaneously, the
P values of regression equation are less than 0.05, thus the linear equation is credible.
To sum up, each curve can be divided into four stages (I, II, III, IV), which mirrors applied electrical current fluctuations and the degradation of concrete structure. A comparative analysis of specimens with protective layer thicknesses of 67 mm and 142 mm and an effective length of 200 mm shows that the corrosion rate thresholds in the first stages are related to the protective layer thickness of concrete structures. Furthermore, the crack corrosion rates observed the crack from the distributed strain are basically consistent with the actual corrosion rate optically observing crack.
Moreover, the corrosion sensitivity (stage II) before cracking of 2-150# and 2-300# concrete specimens is shown in
Figure 11b,
Figure 12b and
Figure 13b,
Table 2 and
Table 6. The corrosion sensitivity of the distributed sensor located in steel bar is 125
. In the contrast, the corrosion sensitivity located in mortar layer is 156
. These experimental sensitivities are in good agreement with the theoretical sensitivity of 92.8
. The difference between the theoretical and measured data is attributed to these parameters such as corrosion expansion coefficient. Based on aforementioned corrosion sensitivity of 125, 156, 92.8
, the tested error of a helix distributed sensor is lowered or enhance its the corrosion sensitivity further to attain a higher precision of measured corrosion mass loss.