Next Article in Journal
Organization Synchronization in Response to Complex Project Delays: Network-Based Analysis
Next Article in Special Issue
Investigation of Seismic Performance for Low-Rise RC Buildings with Different Patterns of Infill Walls
Previous Article in Journal
Satisfaction and Demands of Indoor Space in the High-Density Residential Areas in the COVID-19 Era
Previous Article in Special Issue
Study on Parameters’ Influence and Optimal Design of Tuned Inerter Dampers for Seismic Response Mitigation
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Study on Optimal Design of Grotto-Eave System with Cable Inerter Viscous Damper for Vibration Control

1
Institute for Conservation of Cultural Heritage, Shanghai University, Shanghai 200444, China
2
School of Mechanics and Engineering Science, Shanghai University, Shanghai 200444, China
3
School of Materials Science and Engineering, Shanghai University, Shanghai 200444, China
4
School of Civil Engineering, North China University of Technology, Beijing 100144, China
*
Author to whom correspondence should be addressed.
Buildings 2022, 12(5), 661; https://doi.org/10.3390/buildings12050661
Submission received: 2 May 2022 / Revised: 10 May 2022 / Accepted: 13 May 2022 / Published: 16 May 2022
(This article belongs to the Special Issue Advances in Design and Disaster Mitigation of Engineering Structures)

Abstract

:
In this paper, the mechanical model of grotto–eave system with cable inerter viscous damper (CIVD) is established, and the vibration control equations are established. Firstly, the stochastic response is carried out, and the optimization design of design parameters of CIVD is carried out for the grotto–eave systems with different connection types. Finally, the vibration mitigation control performance of CIVD under different seismic inputs is analyzed. The research shows that in the optimal design of CIVD, the inerter–mass ratio and damping ratio should be reduced as much as possible to improve the feasibility of the application of CIVD in cultural relics protection engineering under the condition of meeting the target damping ratio. The demand-based optimal method can minimize the cost by enhancing damping element deformation in a small damping ratio, while ensuring that the value of displacement index of grotto–eave system can be reached. Hence, the deformation and damping force of CIVD will increase simultaneously due to the efficient tuning and damping amplification of CIVD. CIVD can enlarge the apparent mass through rotation and damping force through enhancement deformation. Hence, compared with other conventional dampers (such as viscous damper), optimal CIVD has lower damping ratio under the same demand index of grotto–eave system. It can be realized that the lightweight and high efficiency of the damper, and can be applied to the vibration mitigation and reinforcement of the grotto–eave system.

1. Introduction

Historic buildings and cultural relics are valuable and must be preserved carefully. However, such structures, such as grotto–eave system, may be destroyed during earthquakes owing to the deterioration of their structural performance over time [1]. Moreover, the seismic resistance of most historic buildings is inferior to that of modern structures because the mechanical performance of the construction materials deteriorates with time [2,3]. Therefore, it is of significance to protect historic buildings and the cultural relics housed in such buildings. There are various types of immovable heritage structures, including wooden, bricked and rammed structures [4,5,6]. The historical buildings of the most historical and cultural value are mainly wooden structures and bricked structures. In general, non-structural components are often used for decoration, and they may have a certain architectural or utility function. However, in the immovable heritage structures [7], the non-structural components are also regarded as part of the heritage. Their cultural value is higher than the value of structures. It is the main difference between heritage buildings and modern buildings in seismic protection that non-structural components are as important as the main structure.
In order to improve the seismic performance of immovable cultural relics, we can use traditional reinforcement methods that including strengthening the connecting parts of structural members or adding shear walls and supports, and improving the rigidity of the structure. Bento et al. [8] proposed the use of steel or concrete to strengthen the connection of bricked walls, thereby increasing the lateral resistance of the structure. Aty [9] proposed another modification method by using wood support system, and analyzed the seismic performance of X-shaped wood support and K-shaped wood support structure. Witzany et al. [10] conducted experimental research and analysis on the failure mechanism and ultimate compressive bearing capacity of carbon fiber reinforced polymer (CFRP) reinforced bricked walls. Akcay et al. [11] performed reinforcement tests and numerical analyses of historic bricked buildings using different conventional techniques. Although the structural rigidity increases, it also increases the seismic damage to the structure, which heritage buildings may not be able to withstand. These traditional renovation methods all help to improve the seismic performance of heritage buildings. However, the original information of the cultural relics cannot be preserved, and the modern buildings and the cultural relics inside may be damaged during the renovation. Structural control is an efficient approach for suppressing the dynamic response of civil structures under external actions such as those exerted by wind, earthquake, and other hazardous events. Hence, it is necessary to develop a lightweight and high efficiency damper that can control the vibration response of historic buildings and cultural relics simultaneously. An cable inerter viscous damper (CIVD) for seismic response mitigation of typical historic buildings and immovable cultural relics system is proposed in this paper.
The vibration control technologies of inerter-based dampers have been developed based on electromechanical similarity theory [12]. Compared with the TMD, the inerter-based damper can control the inertial force at the two terminals directly. Moreover, the inerter element can effectively enlarge the small apparent mass through converting the translational motion into rotary motion such as ball screw. In 2001, Smith [13] put forward the concept of inerter element and gave the basic forms of ball screw inerter element and rack and pinion inerter element, and designed a hydraulic inerter element in 2013 [14]. Subsequently, shock absorbers were proposed such as tuned viscous mass damper (TVMD) and tuned inerter damper (TID). The design method of the inerter system was also studied. Ikago et al. [15] derived a closed-form formula for TVMD optimization design based on fixed-point theory. Pan et al. [16] considered the natural damping of the original structure and the cost of the inerter-based damper, and make up for the deficiency of fixed-point theory. Then, he proposed the design method of SPIS-Ⅱ inerter-based damper based on stochastic response mitigation ratio [17]. Hwang et al. [18] proposed a rotation inerter system connected with a toggle brace based on ball screw. It is shown that the system can be effectively used in the structure with small drift. Zhang et al. [19,20] applied the inerter damper system to high-rise structures such as chimneys and wind power towers, and proved the effectiveness of the inerter-based damper in high-rise structures. Gao et al. [21] put forward an optimum design method of viscous inerter damper (VID) based on the feedback control theory. De Domenico [22,23,24,25,26,27,28,29,30,31,32] proposed the optimal design methods of inerter-based TMD systems for seismic response mitigation.Although some scholars have used the inerter-based damper in practical engineering [33], most of the research on the inerter-based damper is still in the stage of theoretical analysis, and only a few scholars have proposed the connection mode and design method of the inerter system applied in building structures [34]. Xie et al. [35,36] put forward a cable-bracing inerter system (CBIS), and shows that it is easy to install and can effectively control displacement and acceleration of structure. Wang et al. [37] put forward a new tuned inerter-negative-stiffness damper (TINSD) based on fixed-point method, which is more effective than the TID, TVMD, and INSD in reducing the dynamic response of structures. It is the satisfactory scheme using inerter-based damper to suppress vibrations of some special structure, such as transmission line [38], tall building [39] and transformer-bushing system [40].
At present, the fixed-point method is mainly used in the parameters design of inerter systems and other vibration control systems, such as TMD, TID and TVMD. A better damping ratio or stiffness ratio can be obtained by fixed-point method, but the optimal inerter-mass ratio (or mass ratio) cannot be obtained directly. In this way, the obtained damping ratio is larger and the inerter element cannot amplify the damping effect as far as possible. At the same time, it is necessary to install lighter dampers to meet the higher seismic requirements for immovable historic buildings and cultural relics such as grottoes and eaves.
In this paper, a cable inerter viscous damper (CIVD) system is proposed. The end of the lightweight inerter viscous damper is directly connected with the elastic cable, which can be quickly installed in various historic buildings and cultural relics. The system can not only realize structural reinforcement and improve the integrity of the structure, but also realize the lightweight of the shock absorber. Firstly, Section 2 introduces the basic principle of CIVD. The motion control equations and frequency response functions of grotto–eave system with CIVD are established. In the Section 3, the parameter analysis is carried out to obtain the minimum additional damping ratio of CIVD under different vibration mitigation ratios. Additionally, the demand-based optimal design method of CIVD is proposed; Finally, it is carried out that the dynamic time history analysis of the grotto–eave system installed with CIVD under the ground motions in Section 4 to verify the vibration control effect and parameter optimization results of CIVD. The research in this paper can provide reference for the design of efficient and lightweight vibration mitigation scheme of immovable historic buildings and cultural relics based on inerter damping system.

2. Theoretical Analysis of Grotto-Eave System with CIVD

2.1. Mechanical Model of Inerter Element and CIVD

Equation (1) shows the output force of inerter element and it has different accelerations in two terminals. Hence, the output of inerter element is proportional to the relative acceleration at two terminals, which can be shown as follows:
f I = m d ( a 2 a 1 )
where, fI is the output force of the inerter element, a1 and a2 are the accelerations at terminals, md is the inertance, and Figure 1 is the mechanical model of the inerter element.
The inerter element cannot dissipate energy by itself and it is generally used in combination with the damper. Figure 2a shows the inerter viscous damper (IVD), the translation Δ of the structure, can be converted into rotation φ in the IVD through the ball screw. The input energy can be dissipated by the viscous fluid in the damper. IVD can be regarded as an inerter element with a damping element connected in parallel, and the mechanical model of IVD is shown in Figure 2b.
Where md and cd are equivalent mass and equivalent damping coefficient, corresponding to the translation Δ at both ends of IVD; J and cvd are the apparent mass (moment of inertia) and viscous damping constants. The expressions of md and cd can be obtained, where L is the lead of the ball screw:
m d = 4 π 2 L 2 J , c d = 4 π 2 L 2 c v d , φ = 2 π L Δ
CIVD is IVD connected with an elastic cable, and the cable in this paper is a short-span cable. The reason is that the prestress relaxation of the short cable can be almost ignored. When the angle of cable is an appropriate large constant, the sag of cable and stress relaxation in the short-span structure can be ignored. Compared with the long cable, the short cable has high efficiency of force transmission. The mechanical model is shown in Figure 3. Where kd is the equivalent stiffness of the elastic cable.

2.2. Mechanical Model of Grotto-Eave System with CIVD

The grotto–eave system is generally composed of eaves, connection and grotto. Generally, the eaves of the caves are wooden or steel structures. To protect the grottoes, the wooden structures are built in ancient times, while the steel structures are the modern architecture. The height of the structure is generally about 6–20 m, and its overall stiffness is small. The connection is the beam with the eaves lapped on the grotto or inserted into the grotto, so that the two parts are connected into a complete system. The material, type and position of the connection will influence the stiffness of the connection. Similar to the modern frame, the main structure of the grotto is generally an internal hollow structure. The materials of grotto are mostly rock materials such as sandstone, and grotto is generally adjacent to the mountain, the stiffness is relatively large. There is a large difference in stiffness between the eaves and the grottoes. When subjected to external excitation, the incongruity of deformation between the eaves and the grotto body will occur. Many precious cultural heritages are preserved in the grottoes, which have high historical and humanistic value, but are easily damaged by external disturbances; at the same time, since the grottoes are immovable cultural relics, it can only be protected at the original site. It will also lead to the cumulative damage of the cultural relics under frequent external vibration, and resulting in the instantaneous brittle failure of the stone cultural relics.
Under external excitation, it is generally considered to reduce the vibration of the eaves itself to reduce the vibration effect of the eaves on the grottoes. Due to the high demand for vibration mitigation of the system, the bearing capacity of the eave is small and the internal space is limited. Traditional vibration control system (such as TMD) cannot achieve the expected effect. Therefore, it needs to find a lightweight and efficient vibration control system, such as the CIVD, which has the flexible arrangement and the small size damper, and the obvious effect of vibration mitigation. Figure 4 is a layout of CIVD in an eave–grotto system.
For the grotto–eave system, the shock absorber cannot be directly installed in the grotto, so the CIVD can be installed inside the wooden eaves. Figure 5 shows the mechanical model of the grotto-eave system with CIVD. Where me, mc, mg and md are the mass of the eaves, the connection and the grotto, and the inerter of the CIVD; ce, cc, cg and cd are the damping coefficients of the eaves, connecting sections, grottoes, and the equivalent damping coefficient of CIVD; ke, kc, kg, and kd are the stiffnesses of the eaves, connection, grottoes and CIVD.

2.3. Motion Control Equation of Grotto-Eave System with CIVD

According to the mechanical model shown in Figure 5, the motion equation of the grotto–eave system with CIVD is established:
M X ¨ + C X ˙ + K X = M I a g
where, X ¨ , X ˙ , X is the acceleration, velocity and displacement vector of the grotto-eave system, ag is the acceleration of ground motion; M, C, K are the mass, damping and stiffness matrices, and I is the ground motion excitation vector. Therefore, M, C, K, I and motion vector can be expressed as:
M = [ m e + m c m d m g ] , C = [ c e + c c c c c d c c c g + c c ] , K = [ k e + k c + k d k d k c k d k d k c k g + k c ]
X = u e u d u g , X ˙ = u ˙ e u ˙ d u ˙ g , X ¨ = u ¨ e u ¨ d u ¨ g , I = 1 0 1
where u , u ˙ , u ¨ is the vectors of displacement, velocity and acceleration; the subscripts e, d, g represents the eaves, CIVD and grottoes. For the convenience of parameter analysis, we define the following dimensionless parameters. Where Equation (6) is the natural vibration frequency and damping ratio parameters of the eaves, connection and grottoes; Equation (7) is parameters of CIVD; Equation (8) is the parameters of relative mass.
ω e = k e m e ;   ζ e = c e 2 m e ω e ;   ω c = k c m c ;   ζ c = c c 2 m c ω c ;   ω g = k g m g ;   ζ g = c g 2 m g ω g
ζ d = c d 2 m e ω e ;   κ d = k d k e
μ d = m d m e ;   μ c e = m c m e ;   μ c g = m c m g  
where ωe is the natural circular frequency of the eaves, ζe is the damping ratio of the eaves; ωc is the natural circular frequency of the connection, and ζc is the damping ratio of the connection; ωg is the natural circular frequency of the grotto, and ζg is the damping ratio of the grotto; ζd is the damping ratio of CIVD, and κd is the stiffness ratio of CIVD; μd is the inerter–mass ratio, μce is the mass ratio of connection and eave, and μcg is the mass ratio of connection and grotto.
From Equations (5)–(8), Laplace transform is applied to Equation (3), so the equation of motion (9) and (10) of the CIVD grotto–eave system in frequency domain can be obtained, where M ^ , C ^ , K ^ , I ^ is the dimensionless mass, damping, stiffness matrix and external excitation vector of the system.
M ^ s 2 + C ^ s + K ^ U ^ = I ^ A g ;   U ^ = U e U d U g ;   I ^ = 1 μ c e 0 1
M ^ = 1 + μ c e μ d 1 ;   C ^ = 2 ω e ζ e + 2 ω c ζ c μ c e 2 ω c ζ c μ c e 2 ω e ζ d 2 ω c ζ c μ c g 2 ω g ζ g + 2 ω c ζ c μ c g ; K ^ = ω e 2 ( 1 + κ ) + ω c 2 μ c e ω e 2 κ d ω c 2 μ c e ω e 2 κ d ω e 2 κ d ω c 2 μ c g ω g 2 + ω c 2 μ c g
where s is the Laplace operator, s = iΩ, Ω is the external excitation frequency, Ue, Ud, Ug and Ag are the Laplace transforms of ue, ud, ug and ag. The linear matrix Equations (9) and (10) can be solved to obtain Ue, Ud and Ug, at the same time, the transfer functions HUe(s), HUd(s) and HUg(s) of the grotto–eave system with CIVD can be obtained:
H U e ( s ) = U e ( s ) A g ( s ) , H U d ( s ) = U d ( s ) A g ( s ) , H U g ( s ) = U g ( s ) A g ( s )  
Meanwhile, the transfer function of output force of CIVD HFd(s) can be expressed as follows:
H F d ( s ) = U d ( s ) A g ( s ) ( μ d s 2 + 2 ζ d ω e s )  

3. Parameter Analysis

According to Parseval’s theorem, the root mean square (RMS) response σ of the system excited by white noise is obtained:
σ = + | H ( i Ω ) | 2 S 0 d Ω
where S0 is the power spectrum of white noise. The primary index is the γUr, the relative displacement root mean square response ratio of the eaves and the grottoes before and after vibration mitigation by CIVD. It can be compared to evaluate the interaction between the eaves and the grottoes. At the same time, the γU, the displacement root mean square response ratio of the eaves before and after the vibration mitigation by CIVD, can directly measure the effect of the shock absorber, it can be regarded as an additional index. The smaller the γU and γUr are, the better the vibration mitigation effect of the grotto–eave system is; that γU and γUr are greater than 1 indicate that the CIVD has a displacement amplification effect on the system. The relative displacement ratio γUr and displacement ratio γU are expressed as:
γ U r ( ζ d , κ d , μ d ) = | σ U e σ U g | | σ U e , 0 σ U g , 0 | . γ U ( ζ d , κ d , μ d ) = σ U e σ U e , 0
where σUe,0 and σUg,0 are the displacement root mean square responses of the eaves and grottoes in the uncontrolled state. The CIVD parameter analysis selects the inerter–mass ratio μd, the stiffness ratio κd and the damping ratio ζd; and the parameter analysis index is the relative displacement ratio γUr. Similarly, using Equations (12) and (13), the RMS response of output force of CIVD σFd can be determined. In parameter analysis, the value range of parameters of CIVD is 0.01 to 1.
In addition to the CIVD parameters, it is also necessary to analyze the influence of the stiffness of the connection between grotto and eave. Defining the parameters of the Benchmark model of the grotto–eave system: ωg/ωe = 5, ζc = 0.015, ζe = ζg = 0.02, μce = 0.2, μcg = 0.04, and subsequent analyses are carried out according to this Benchmark model; then defining the frequency ratio of the connection: β = ωc/ωe, β can reflect the stiffness of the connection, and the smaller the β, the smaller the stiffness of the connection. Table 1 shows the frequency ratio β of different types of connection.

3.1. Parameter Analysis of CIVD

Based on the above analysis indexes, the parameters of the grotto–eave Benchmark model and different types of connection, the influence study of design parameters of CIVD, including inerter–mass ratio μd, stiffness ratio κd and damping ratio ζd.
Firstly, the influence of types of connection on grotto-eave system under different inerter-mass ratio μd is analyzed, and Figure 6, Figure 7 and Figure 8 show three-dimensional contour plot of γUr. When the stiffness ratio is 0.01 to 0.3 and the damping ratio is 0.1 to 1, it can be seen from figures that as the stiffness ratio and damping ratio increase, the relative displacement between the grotto and the eaves will decrease; when the damping ratio is 0.01 to 0.1, the value of the minimum γUr changes with the increase of the inerter–mass ratio, the larger the inerter-mass ratio, the greater requirement of additional stiffness of CIVD. However, in the case of low damping ratio and low stiffness ratio, the hard connection system has displacement amplification, which should be avoided in parameters selection. The maximum γUr of three types of connection is 0.2, but the stiffness ratio and damping ratio required by CIVD should be as large as possible. Figure 6, Figure 7 and Figure 8 show the analytical solutions of the equivalent mathematical problems, which cannot be realized in engineering applications. Generally, it is more appropriate to control the damping ratio within 0.2. Hence, further analysis of other parameters and indexes should be carried out.
Taking γUr as the index and fixing the damping ratio ζd to be 0.05, 0.1, and 0.15, from contour plot of γUr with κdd space, we can get the variation trend of γUr with ζd. Figure 9, Figure 10 and Figure 11 show the 2D contour plot of γUr in κdd space under different types of connection, in which the numbers in the figure are contour values, representing the value of γUr, the variation range is 0 to 1, and the interval value is 0.1. When the damping ratio ζd varies from 0.05 to 0.15, the value of the contour line of the soft connection system is 0.2 to 1, the equal stiffness connection system is 0.4 to 1, and the hard connection system is 0.5 to 1. Furthermore the smaller the damping ratio, the higher the contour line value, and the worse effect of vibration mitigation of relative displacement. At the same time, as the stiffness of the connection between the grotto and the eaves increases, CIVD needs greater the damping ratio to obtain the same relative displacement ratio γUr. We can also draw a conclusion from the number of contour lines intuitively, the more “hard” the connection (means the stiffness of connection is large), the less the number of contour lines. CIVD has a better control effect on the relative displacement index γUr, and it can indicate that the arrangement of CIVD can reduce the impact of the eaves on the grotto. However, at the same time, considering the vibration mitigation effect of the eaves themselves, if the displacement of the eaves themselves are too large, the CIVD cannot be used as the best vibration control device. To this end, we should continue to study another index γU with CIVD parameters.
The γU is also controlled by three parameters. For the convenience of research, a three-dimensional μddd space is established. The γU is any point in the parameter space, and it is represented by a specified color and a value corresponding to the color. We make slice plots on some specific parameter planes, and the two-dimensional spaces under the specified parameters are displayed. In this paper, we fixed μd to 0.01, 0.03, 0.1, 0.3 and 1, and it is used to study the response trend of the eaves under different types of connection based on the Benchmark model. Figure 12 is the γU slice plot of different connection systems. It can be seen from the figure that the displacement ratio of the SC system is the smallest, and the minimum value is 0.2. As the stiffness of the connection increasing, the minimum value of γU is larger, and the displacement mitigation of single eaves is worse. Figure 12a shows the displacement ratio of the eaves without connection, and it is similar to EC system. If the target displacement ratio of the eaves is specified as 0.5 (γU = 0.5), it can be seen that when μd is in the range of 0.03 to 0.3, the enclosed area of target contour γU is larger (the blue area), and the enclosed area tends to increase firstly and then decrease. When μd is in the range of 0.01 to 0.03, the γU is almost constant, so the range of μd can be determined between 0.03 and 0.3, and further discussions of influence of stiffness are continued.
Since the large stiffness of the cable is easier to achieve in practical, it can be assumed that the stiffness of the cable can be taken as any value. The γU of SC system under different inerter–mass ratios are shown in Figure 13. It can be seen from the figure that a large inerter–mass ratio requires a large stiffness to achieve the same displacement ratio of single eaves. At the same time, when ζd is less than 0.05, γU decreases firstly and then increases under a small damping ratio. Additionally, as the inerter–mass ratio increasing, this phenomenon becomes more obvious. Hence, the robustness of CIVD with small damping ratio is low. When ζd is greater than 0.1, increasing the stiffness of the cable cannot reduce the displacement ratio. In addition, a larger damping ratio (ζd is greater than 0.3) does not continue to reduce γU, but the stability of the curve and the trend of γU are better. However, in practical engineering, increasing damping ratio will lead to a higher cost and a larger volume of the damper. Therefore, while ensuring the index, further parameter optimization design is required to reduce the damping ratio.

3.2. Demand-Based Optimal Design of CIVD

The parameters of CIVD and other inerter-based shock absorbers can be determined by the fixed-point method [41]. Ikago et al. [16] has proposed corresponding inerter system design methods for single degree of freedom (SDOF) structures and multi-degrees of freedom structures. For the SDOF system of the eaves structure with CIVD, if the arrangement angle of the cables is not considered, the stiffness ratio and damping ratio can be obtained by the following formulas after the inerter–mass ratio μd is determined:
κ d = μ d 1 μ d , ζ d = μ d 2 3 μ d 1 μ d 2 μ d
However, the fixed-point theory does not consider the inherent damping ratio, external excitation characteristics and performance demands of main structure. For example, it cannot reflect the key index such as the relative displacement response of grottoes and eaves. Zhang et al. [42] consider the main performance of the structure based on closed-form solution and use extreme conditions to determine parameters of CIVD. Compared with fixed-point method, better structural performance index can be obtained by this methods. In addition to performance index, output force of CIVD can represent the cost index of shock absorber. The contour plot of σUe and σFd of SC system are shown in Figure 13.
It can be seen from Figure 14 that the minimum value of σUe is located at the upper right of the contour plot (white dot), but at this time, it corresponds to a large stiffness ratio and damping ratio. That means the output value of CIVD is also large, which is difficult to achieve in practical. However, compared with Figure 14a,b, it can be seen that there exists a parameter combination of a small stiffness ratio and a damping ratio when the inerter–mass ratio is determined, which can make the displacement and output smaller simultaneously (dark yellow dot). It means that the parameter combination can meet both the performance index (displacement ratio) and the cost index (output force of CIVD). If the main performance index of grottoes and eaves is determined, the optimization problem can be transformed from multi-objectives optimization problem to single-objective optimization problem, as shown in the following formula 16. It can be seen that the objective function of single-objective optimization problem is σFd.
minimize   σ F d ( ζ d , κ d , μ d ) s u b j e c t   t o { γ U r ( ζ d , κ d , μ d ) = γ U r , t ζ d ( 0 , 0.2 ) κ d ( 0 , 1 ) μ d ( 0 , 1 )
where, γUr,t is the relative displacement ratio of the grotto and the eaves. It is difficult to realize in practical engineering with large damping ratio. For this reason, the damping ratio is set within 0.2.
Moreover, compared with the conventional viscous damper (VD), the different topological connection forms of the inerter element can enhance the deformation of the damping element and improve the capacity of energy dissipation [43]. Therefore, a new index of damping effects of CIVD is proposed by comparing VD, namely, inerter-enhanced energy dissipation coefficient η:
η = σ U 0 ( ζ 0 ) σ U e ( ζ 0 , ζ d , κ d , μ d ) σ U 0 ( ζ 0 ) σ U e V D ( ζ 0 , ζ d )  
where σUeVD are the RMS displacement responses of the eave with VD. Additionally, η means the damping element with inerter element has a higher deformation effect under the same additional damping ratio. When η is greater than 1, it shows that the inerter can strengthen the energy dissipation of the structure, and it can be used as an index to evaluate the robustness of the CIVD. According to massive numerical case studies, the recommended range of η is [1,2] and the η can be also a constraint condition of formula 16. In this paper, η is fixed as 1.5 and γUr,t is fixed as 0.5, 0.6 and 0.7. Table 2 shows the results of parameters of CIVD after optimization. It can be seen from Table 2 that the value of parameters’ combination of HC system are larger, but the values of CIVD are generally small, especially the damping ratio (less than 0.05).
Figure 15 shows the transfer function of relative displacement of the grotto–eaves system under different types of connection. Where, the modulus of transfer function of the relative displacement HUr of the grotto–eaves is:
| H U r | = | H U e H U g |
It can be seen from Figure 15 that peak relative displacements of the grotto–eaves system are reduced under harmonic excitation, which controls the narrow-band resonance response of the system significantly. However, the HC system needs a smaller relative displacement ratio to control the resonance response. In order to better illustrate the advantages of this optimal method, the response of eaves and the deformation of damping element by using the classic fixed-point method should be compared under the same target relative displacement ratio.
Figure 16 and Figure 17 show the displacement amplification factor of eaves and transfer function of deformation of damping element of CIVD in SC system with different optimal design methods. It can be seen from Figure 16 and Figure 17 that the maximum displacement of demand-based optimal method is less than it of the fixed-point method. Meanwhile, the damping element deformation enhancement of the inerter system can be brought into full play by using demand-based optimal method. Hence, the demand-based optimal method can minimize the cost by enhancing damping element deformation in a small damping ratio.

4. Dynamic Response

In the previous study, parameter analyses in the frequency domain are carried out based on the performance index. In order to further verify the vibration mitigation effect of CIVD and the optimal parameters. Dynamic response analyses of the grotto–eave system with CIVD are carried out under the non-stationary ground motions in this section. The structural parameters of the grotto–eaves system refer to the Benchmark model in Section 2.1, and the parameters of CIVD are shown in Table 2. The ground motion records EL Centro record, Taft record, Chi-chi record and Kobe record are selected. The predominant frequencies of the four records are all different. Figure 18 shows the acceleration response spectrum of the four ground motion records.
Figure 19 shows the relative displacement time history response of SC eave–grotto system. It can be seen that CIVD has better vibration control performance intuitively. Additionally, the continuous vibration mitigation of CIVD is good on the grotto–eave system, and the controlled system can be stable and have small displacements quickly. As the seismic response progresses, the vibration control effects of CIVD in the later stage are better, indicating that a stable vibration state of eave–grotto system can be quickly got under control of CIVD.
Figure 20 shows that the decline of RMS displacement of the eave is between 25% and 60%. At the same time, it can be seen that the deformation of damping element in CIVD is always greater than displacement of main structure (eave). Compared with the hysteretic loops of CIVD and VD under the same damping coefficient as shown in Figure 21, it can be seen that the deformation and damping force of CIVD will increase simultaneously due to the efficient tuning and damping amplification of CIVD.
Hence, if the damping ratio ζd is a fixed, the damping force will be greater as the deformation of the damping element of CIVD is greater. Additionally, the damping effect of CIVD will be improved. Then, the deformation enhancement coefficient of damping element γUd can be defined, as shown in Equation (19):
γ U d ( ζ d , κ d , μ d ) = σ U d σ U e
where, σUd is the displacement root mean square responses of damping element of CIVD. The larger γUd means the better deformation amplification effect of the inerter on the damping element, corresponding the smaller displacement mitigation ratio γU. Additionally, the deformation enhancement coefficient of damping element of VD γUd,VD is equal to 1, indicating there is no deformation enhancement effect of VD. A large damping ratio is required in VD system in order to achieve the same displacement mitigation ratio γU as CIVD. That means the VD will produce large damping force even under small displacement the eave, which will have a great impact on historical buildings. Due to a small optimal damping ratio, CIVD have a smaller damping force under small displacement the eave, but can still control the eave through better tuning capacity.
Figure 22 shows the contour plot of γU and γUd of eave with optimal μd of CIVD, it can be seen that under the same damping ratio, the deformation of damping element of CIVD is about 2 times of VD, which can obtain better energy dissipation effect and reduce the energy transmitted to the historical buildings’ underground motions. Meanwhile, about five times the damping coefficient of CIVD are required for VD to achieve the same vibration mitigation effect as CIVD. Thus, compared with VD, the damping force of CIVD transmitted to the historical buildings will be much lower.

5. Conclusions

In this paper, the motion equation of grotto–eave systems with cable inerter viscous damper (CIVD) is established. Then, the stochastic analysis and demand-based parameters optimization of CIVD are carried out. Finally, the vibration control performance of CIVD is analyzed under different seismic inputs. The main conclusions are as follows:
  • The CIVD is easy to install, and can quickly improve the seismic performance of the structure. Therefore, it can be used in immovable cultural relics such as eaves and grottoes where the damper installation conditions are harsh.
  • In the parameters optimization design of CIVD, damping ratio should be reduced as much as possible under the condition of satisfying the target vibration mitigation ratio based on performance demand. The optimal design of a CIVD in grotto–eave system should be a balance process between response of different types of grotto–eave system and the cost of CIVD. It can improve the feasibility of the application of CIVD in cultural relics protection projects.
  • The proposed demand-based optimal method can minimize the cost by enhancing damping element deformation in a small damping ratio, while ensuring that the value of displacement index of grotto–eave system can be reached. Moreover, the inerter–mass ratio of the CIVD can be also determined by displacement index of grotto–eave system when using fixed-point method.
  • Considering the lower damping ratio and inerter–mass ratio of CIVD, applications of the CIVD designed by demand-based optimal method can be extended and its installation made more flexible in specific structures like eaves. The corresponding verification experiment should be conducted in the near future.

Author Contributions

J.H., supervision, funding acquisition, methodology, investigation, validation, writing—review and editing. R.Z., methodology, conceptualization, software, investigation, writing—original draft, writing—review and editing; Q.L., validation, writing—review and editing. X.G., validation, writing—review and editing. M.C., conceptualization, writing—review and editing. All authors have read and agreed to the published version of the manuscript.

Funding

This work is supported in part by National Key R&D Program of China (Grant no. 2019YFC1520500, 2020YFC1523004).

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

The data used to support the findings of this study are included within the article.

Conflicts of Interest

The authors declare that there is no conflict of interest regarding the publication of this paper.

References

  1. Mosoarca, M.; Onescu, I.; Onescu, E.; Azap, B.; Chieffo, N.; Sirbu, M.S. Seismic vulnerability assessment for the historical areas of the Timisoara city, Romania. Eng. Fail. Anal. 2019, 101, 86–112. [Google Scholar] [CrossRef]
  2. Cardoso, R.; Lopes, M.; Bento, R. Seismic evaluation of old masonry buildings. Part I: Method description and application to a case-study. Eng. Struct. 2005, 27, 2024–2035. [Google Scholar] [CrossRef]
  3. Betti, M.; Vignoli, A. Modelling and analysis of a Romanesque church under earthquake loading: Assessment of seismic resistance. Eng. Struct. 2008, 30, 352–367. [Google Scholar] [CrossRef]
  4. Zhao, X.B.; Zhang, F.L.; Xue, J.Y.; Ma, L.L. Shaking table tests on seismic behavior of ancient timber structure reinforced with CFRP sheet. Eng. Struct. 2019, 197, 109405. [Google Scholar] [CrossRef]
  5. Sayin, B.; Yildizlar, B.; Akcay, C.; Gunes, B. The retrofitting of historical masonry buildings with insufficient seismic resistance using conventional and non-conventional techniques. Eng. Fail. Anal. 2019, 97, 454–463. [Google Scholar] [CrossRef]
  6. Silva, R.A.; Mendes, N.; Oliveira, D.V.; Romanazzi, A.; Martínez, O.D.; Miranda, T. Evaluating the seismic behaviour of rammed earth buildings from Portugal: From simple tools to advanced approaches. Eng. Struct. 2018, 157, 144–156. [Google Scholar] [CrossRef]
  7. Zhang, R.; Wu, M.; Lu, W.; Li, X.; Lu, X. Seismic retrofitting of a historic building by using an isolation system with a weak restoring force. Soil Dyn. Earthq. Eng. 2021, 148, 106836. [Google Scholar] [CrossRef]
  8. Bento, R.; Lopes, M.; Cardoso, R. Seismic evaluation of old masonry buildings. Part II: Analysis of strengthening solutions for a case study. Eng. Struct. 2005, 14, 2014–2023. [Google Scholar] [CrossRef]
  9. Aty, Y.Y.A. Proposals for seismic retrofitting of timber roofs to enhance their in-plane stiffness and diaphragm action at historical masonry buildings in Cairo. J. Cult. Herit. 2018, 32, 73–83. [Google Scholar]
  10. Witzany, J.; Zigler, R.; Kroftová, K. Strengthening of compressed brick masonry walls with carbon composites. Constr. Build. Mater. 2016, 112, 1066–1079. [Google Scholar] [CrossRef]
  11. Akcay, C.; Bozkurt, T.S.; Sayin, B.; Yildizlar, B. Seismic retrofitting of the historical masonry structures using numerical approach. Constr. Build. Mater. 2016, 113, 752–763. [Google Scholar] [CrossRef]
  12. Lee, S.H.; Min, K.W.; Hwang, J.S.; Kim, J. Evaluation of equivalent damping ratio of a structure with added dampers. Eng. Struct. 2004, 26, 335–346. [Google Scholar] [CrossRef]
  13. Smith, M.C.; Wang, F.C. Performance benefits in passive vehicle suspensions employing inerters. Veh. Syst. Dyn. 2004, 42, 235–257. [Google Scholar] [CrossRef] [Green Version]
  14. Smith, M.C. Synthesis of mechanical networks: The inerter. IEEE Trans. Autom. Control 2002, 47, 1648–1662. [Google Scholar] [CrossRef] [Green Version]
  15. Ikago, K.; Saito, K.; Inoue, N. Seismic control of single-degree-of-freedom structure using tuned viscous mass damper. Earthq. Eng. Struct. Dyn. 2012, 41, 453–474. [Google Scholar] [CrossRef]
  16. Pan, C.; Zhang, R.; Luo, H.; Li, C.; Shen, H. Demand-based optimal design of oscillator with parallel-layout viscous inerter damper. Struct. Control Health Monit. 2018, 25, e2051. [Google Scholar] [CrossRef]
  17. Pan, C.; Zhang, R. Design of structure with inerter system based on stochastic response mitigation ratio. Struct. Control Health Monit. 2018, 25, e2169. [Google Scholar] [CrossRef]
  18. Hwang, J.S.; Kim, J.; Kim, Y.M. Rotational inertia dampers with toggle bracing for vibration control of a building structure. Eng. Struct. 2007, 29, 1201–1208. [Google Scholar] [CrossRef]
  19. Zhang, R.F.; Zhao, Z.P.; Dai, K.S. Seismic response mitigation of a wind turbine tower using a tuned parallel inerter mass system. Eng. Struct. 2019, 180, 29–39. [Google Scholar] [CrossRef]
  20. Zhao, Z.P.; Zhang, R.F.; Wierschem, N.E.; Jiang, Y.Y.; Pan, C. Displacement mitigationoriented design and mechanism for inerter-based isolation system. J. Vib. Control 2020, 27, 1991–2003. [Google Scholar] [CrossRef]
  21. Gao, H.; Wang, H.; Li, J.; Wang, Z.; Liang, R.; Xu, Z.; Ni, Y. Optimum design of viscous inerter damper targeting multi-mode vibration mitigation of stay cables. Eng. Struct. 2021, 226, 111375. [Google Scholar] [CrossRef]
  22. De Domenico, D.; Ricciardi, G. An enhanced base isolation system equipped with optimal tuned mass damper inerter (TMDI). Earthq. Eng. Struct. Dyn. 2018, 47, 1169–1192. [Google Scholar] [CrossRef]
  23. De Domenico, D.; Impollonia, N.; Ricciardi, G. Soil-dependent optimum design of a new passive vibration control system combining seismic base isolation with tuned inerter damper. Soil Dynam. Earthq. Eng. 2018, 105, 37–53. [Google Scholar] [CrossRef]
  24. De Domenico, D.; Ricciardi, G. Optimal design and seismic performance of tuned mass damper inerter (TMDI) for structures with nonlinear base isolation systems. Earthq. Eng. Struct. Dyn. 2018, 47, 2539–2560. [Google Scholar] [CrossRef]
  25. Zhao, Z.P.; Zhang, R.F.; Jiang, Y.Y.; Pan, C. Seismic response mitigation of structures with a friction pendulum inerter system. Eng. Struct. 2019, 193, 110–120. [Google Scholar] [CrossRef]
  26. Nakamura, Y.; Fukukita, A.; Tamura, K.; Yamazaki, I.; Matsuoka, T.; Hiramoto, K.; Sunakoda, K. Seismic response control using electromagnetic inertial mass dampers. Earthq. Eng. Struct. Dyn. 2014, 43, 507–527. [Google Scholar] [CrossRef]
  27. Wang, F.C.; Chen, C.W.; Liao, M.K.; Hong, M.F. Performance analyses of building suspension control with inerters, in: Decision and Control. In Proceedings of the 2007 IEEE Conference on Decision and Control, New Orleans, LA, USA, 12–14 December 2007; pp. 3786–3791. [Google Scholar]
  28. Lazar, I.F.; Wagg, D.J.; Neild, S.A. An inerter vibration isolation system for the control of seismically excited structures. In Proceedings of the 10th International Conference on Urban Earthquake Engineering, Tokyo, Japan, 1–2 March 2013. [Google Scholar]
  29. Luo, H.; Zhang, R.F.; Weng, D.G. Mitigation of liquid sloshing in storage tanks by using a hybrid control method. Soil Dyn. Earthq. Eng. 2016, 90, 183–195. [Google Scholar] [CrossRef]
  30. Marian, L.; Giaralis, A. Optimal design of a novel tuned mass-dampereinerter (TMDI) passive vibration control configuration for stochastically support-excited structural systems. Probabilistic Eng. Mech. 2014, 38, 156–164. [Google Scholar] [CrossRef]
  31. Hashimoto, T.; Fujita, K.; Tsuji, M.; Takewaki, I. Innovative base-isolated building with large mass-ratio TMD at basement for greater earthquake resilience. Future Cities Environ. 2015, 1, 9. [Google Scholar] [CrossRef]
  32. Pietrosanti, D.; Angelis, M.D.; Basili, M. Optimal design and performance evaluation of systems with tuned mass damper inerter (TMDI). Earthq. Eng. Struct. Dyn. 2017, 46, 1367–1388. [Google Scholar] [CrossRef]
  33. Sugimura, Y.; Goto, W.; Tanizawa, H.; Saito, K.; Nimomiya, T. Response control effect of steel building structure using tuned viscous mass damper. In Proceedings of the 15th World Conference on Earthquake Engineering, Lisbon, Portugal, 24 September 2012; Volume 9, pp. 24–28. [Google Scholar]
  34. Kurata, M.; Leon, R.T.; Desroches, R. Rapid seismic rehabilitation strategy: Concept and testing of cable bracing with couples resisting damper. J. Struct. Eng. 2012, 138, 354–362. [Google Scholar] [CrossRef]
  35. Xie, L.; Ban, X.; Xue, S.; Ikago, K.; Kang, J.; Tang, H. Theoretical Study on a Cable-Bracing Inerter System for Seismic Mitigation. Appl. Sci. 2019, 9, 4096. [Google Scholar] [CrossRef] [Green Version]
  36. Xue, S.; Kang, J.; Xie, L.; Zhang, R.; Ban, X. Cross-Layer Installed Cable-Bracing Inerter System for MDOF Structure Seismic Response Control. Appl. Sci. 2020, 10, 5914. [Google Scholar] [CrossRef]
  37. Wang, H.; Gao, H.; Li, J.; Wang, Z.; Ni, Y.; Liang, R. Optimum design and performance evaluation of the tuned inerter-negative-stiffness damper for seismic protection of single-degree-of-freedom structures. Int. J. Mech. Sci. 2021, 212, 106805. [Google Scholar] [CrossRef]
  38. Liu, X.; Yang, Y.; Sun, Y.; Zhong, Y.; Zhou, L.; Li, S.; Wu, C. Tuned-Mass-Damper-Inerter Performance Evaluation and Optimal Design for Transmission Line under Harmonic Excitation. Buildings 2022, 12, 435. [Google Scholar] [CrossRef]
  39. Weber, F.; Huber, P.; Borchsenius, F.; Braun, C. Performance of TMDI for Tall Building Damping. Actuators 2020, 9, 139. [Google Scholar] [CrossRef]
  40. Zhang, R.; Cao, M.; Huang, J. Study on Seismic Response and Parameter Influence in a Transformer-Bushing with Inerter Isolation System. Buildings 2022, 12, 530. [Google Scholar] [CrossRef]
  41. Den Hartog, J.P. Mechanical Vibrations, 4th ed.; Dover: New York, NY, USA, 1956. [Google Scholar]
  42. Zhang, R.; Cao, M. Study on Vibration Control and Parameters Influence of Cable Inerter Viscous Damping System. Shock Vib. 2022, 2022, 2983700. [Google Scholar] [CrossRef]
  43. Zhang, R.; Huang, J.; Cao, M.; Luo, Q.; Guo, X. Study on Parameters’ Influence and Optimal Design of Tuned Inerter Dampers for Seismic Response Mitigation. Buildings 2022, 12, 558. [Google Scholar] [CrossRef]
Figure 1. Mechanical model of an inerter element.
Figure 1. Mechanical model of an inerter element.
Buildings 12 00661 g001
Figure 2. Structure and mechanical model of an inerter viscous damper (IVD): (a) Structure of IVD; and (b) mechanical model.
Figure 2. Structure and mechanical model of an inerter viscous damper (IVD): (a) Structure of IVD; and (b) mechanical model.
Buildings 12 00661 g002
Figure 3. Mechanical model of a cable inerter viscous damper (CIVD): (a) Structure of CIVD; (b) and mechanical model.
Figure 3. Mechanical model of a cable inerter viscous damper (CIVD): (a) Structure of CIVD; (b) and mechanical model.
Buildings 12 00661 g003
Figure 4. Layout of CIVD in eave–grotto system.
Figure 4. Layout of CIVD in eave–grotto system.
Buildings 12 00661 g004
Figure 5. Mechanical model of eave–grotto system with CIVD.
Figure 5. Mechanical model of eave–grotto system with CIVD.
Buildings 12 00661 g005
Figure 6. Contour plot of γUt of SC system: (a) μd = 0.1; (b) μd = 0.2; and (c) μd = 0.3.
Figure 6. Contour plot of γUt of SC system: (a) μd = 0.1; (b) μd = 0.2; and (c) μd = 0.3.
Buildings 12 00661 g006
Figure 7. Contour plot of γUt of EC system: (a) μd = 0.1; (b) μd = 0.2; and (c) μd = 0.3.
Figure 7. Contour plot of γUt of EC system: (a) μd = 0.1; (b) μd = 0.2; and (c) μd = 0.3.
Buildings 12 00661 g007
Figure 8. Contour plot of γUt of HC system: (a) μd = 0.1; (b) μd = 0.2; and (c) μd = 0.3.
Figure 8. Contour plot of γUt of HC system: (a) μd = 0.1; (b) μd = 0.2; and (c) μd = 0.3.
Buildings 12 00661 g008
Figure 9. 2D Contour plot of γUr of SC system: (a) ζd = 0.05; (b) ζd = 0.10; and (c) ζd = 0.15.
Figure 9. 2D Contour plot of γUr of SC system: (a) ζd = 0.05; (b) ζd = 0.10; and (c) ζd = 0.15.
Buildings 12 00661 g009
Figure 10. 2D Contour plot of γUr of EC system: (a) ζd = 0.05; (b) ζd = 0.10; and (c) ζd = 0.15.
Figure 10. 2D Contour plot of γUr of EC system: (a) ζd = 0.05; (b) ζd = 0.10; and (c) ζd = 0.15.
Buildings 12 00661 g010
Figure 11. 2D Contour plot of γUr of HC system: (a) ζd = 0.05; (b) ζd = 0.10; and (c) ζd = 0.15.
Figure 11. 2D Contour plot of γUr of HC system: (a) ζd = 0.05; (b) ζd = 0.10; and (c) ζd = 0.15.
Buildings 12 00661 g011
Figure 12. Slice plot of γU: (a) β = 0; (b) β = 0.2; (c) β = 1; and (d) β = 5.
Figure 12. Slice plot of γU: (a) β = 0; (b) β = 0.2; (c) β = 1; and (d) β = 5.
Buildings 12 00661 g012
Figure 13. γU of SC system: (a) μd = 0.03; (b) μd = 0.1; (c) μd = 0.2; and (d) μd = 0.3.
Figure 13. γU of SC system: (a) μd = 0.03; (b) μd = 0.1; (c) μd = 0.2; and (d) μd = 0.3.
Buildings 12 00661 g013
Figure 14. 2D Contour plot of σUe and σFd of SC system (μd = 0.1): (a) σUe; and (b) σFd.
Figure 14. 2D Contour plot of σUe and σFd of SC system (μd = 0.1): (a) σUe; and (b) σFd.
Buildings 12 00661 g014
Figure 15. Transfer function curves of relative displacement of grotto-eaves system: (a) β = 0; (b) β = 0.2; (c) β = 1; and (d) β = 5.
Figure 15. Transfer function curves of relative displacement of grotto-eaves system: (a) β = 0; (b) β = 0.2; (c) β = 1; and (d) β = 5.
Buildings 12 00661 g015aBuildings 12 00661 g015b
Figure 16. Displacement amplification factor of eaves in SC system: (a) γUr = 0.7; (b) γUr = 0.6; and (c) γUr = 0.5.
Figure 16. Displacement amplification factor of eaves in SC system: (a) γUr = 0.7; (b) γUr = 0.6; and (c) γUr = 0.5.
Buildings 12 00661 g016
Figure 17. Transfer function of deformation of damping element of CIVD in SC system: (a) γUr = 0.7; (b) γUr = 0.6; and (c) γUr = 0.5.
Figure 17. Transfer function of deformation of damping element of CIVD in SC system: (a) γUr = 0.7; (b) γUr = 0.6; and (c) γUr = 0.5.
Buildings 12 00661 g017
Figure 18. Normalized acceleration spectra of ground motion records.
Figure 18. Normalized acceleration spectra of ground motion records.
Buildings 12 00661 g018
Figure 19. Relative displacement responses of SC eave-grotto system (γUr = 0.6): (a) EL Centro; (b) Taft; (c) Chi-Chi; and (d) Kobe.
Figure 19. Relative displacement responses of SC eave-grotto system (γUr = 0.6): (a) EL Centro; (b) Taft; (c) Chi-Chi; and (d) Kobe.
Buildings 12 00661 g019aBuildings 12 00661 g019b
Figure 20. Displacement responses of SC eave and damping element of CIVD (γUr = 0.6): (a) EL Centro; (b) Taft; (c) Chi-Chi; and (d) Kobe.
Figure 20. Displacement responses of SC eave and damping element of CIVD (γUr = 0.6): (a) EL Centro; (b) Taft; (c) Chi-Chi; and (d) Kobe.
Buildings 12 00661 g020
Figure 21. Hysteretic loops damping element of CIVD in SC eave under EL Centro record: (a) γUr = 0.7; (b) γUr = 0.6; and (c) γUr = 0.5.
Figure 21. Hysteretic loops damping element of CIVD in SC eave under EL Centro record: (a) γUr = 0.7; (b) γUr = 0.6; and (c) γUr = 0.5.
Buildings 12 00661 g021
Figure 22. 2D Contour plot of γU and γUd of eave with optimal μd (β = 0, γU = 0.7): (a) γU; and (b) γUd.
Figure 22. 2D Contour plot of γU and γUd of eave with optimal μd (β = 0, γU = 0.7): (a) γU; and (b) γUd.
Buildings 12 00661 g022
Table 1. Frequency ratio of different types of connection.
Table 1. Frequency ratio of different types of connection.
Types of ConnectionSoft ConnectionEqual-StiffnessHard Connection
SymbolSCECHC
β0.215
Table 2. Optimal parameters of CIVD.
Table 2. Optimal parameters of CIVD.
γUrParametersβ = 0SC (β = 0.2)EC (β = 1)HC (β = 5)
0.7μd0.01210.01630.02770.0391
κd0.02130.02540.04420.0782
ζd0.00540.00610.01140.0183
0.6μd0.02210.02250.04850.0584
κd0.03320.04550.07820.1327
ζd0.00910.01110.02160.0341
0.5μd0.03440.04830.06920.0994
κd0.06710.07550.13010.2031
ζd0.01640.01920.03660.0485
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Huang, J.; Zhang, R.; Luo, Q.; Guo, X.; Cao, M. Study on Optimal Design of Grotto-Eave System with Cable Inerter Viscous Damper for Vibration Control. Buildings 2022, 12, 661. https://doi.org/10.3390/buildings12050661

AMA Style

Huang J, Zhang R, Luo Q, Guo X, Cao M. Study on Optimal Design of Grotto-Eave System with Cable Inerter Viscous Damper for Vibration Control. Buildings. 2022; 12(5):661. https://doi.org/10.3390/buildings12050661

Chicago/Turabian Style

Huang, Jizhong, Ruoyu Zhang, Qingyang Luo, Xiuwei Guo, and Meigen Cao. 2022. "Study on Optimal Design of Grotto-Eave System with Cable Inerter Viscous Damper for Vibration Control" Buildings 12, no. 5: 661. https://doi.org/10.3390/buildings12050661

APA Style

Huang, J., Zhang, R., Luo, Q., Guo, X., & Cao, M. (2022). Study on Optimal Design of Grotto-Eave System with Cable Inerter Viscous Damper for Vibration Control. Buildings, 12(5), 661. https://doi.org/10.3390/buildings12050661

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop