Investigating the In-Flow Characteristics of Multi-Operation Conditions of Cross-Flow Fan in Air Conditioning Systems
Abstract
:1. Introduction
2. Numerical Methods
2.1. Calculation Model
2.2. Grid Independence
2.3. Turbulence Model
2.4. Boundary Conditions
2.5. Monitoring Points
3. Experiment
3.1. Noise Test Rig
3.2. Test Rig of the Air Volume
4. Results and Discussion
4.1. Comparison of External Characteristics between Simulation and Experiment
4.2. Distribution of Pressure
4.2.1. Distribution of Static Pressure
4.2.2. Distribution of Pressure Contour
4.3. Distribution of Velocity Vector
4.4. Distribution of Vorticity
4.5. Distribution of Pressure on the Circumferential Direction
4.5.1. Distribution of Pressure on Different Operating Conditions (R = 33 mm)
4.5.2. Distribution of Total Pressure Inside and Outside the Blade at the Same Operating Conditions (R = 59 mm)
- The suction zone (60–210°): In this zone, the total pressure inside and outside the blade remains stable. In fact, the suction zone is the most stable area in the rotation cycle of the blade.
- The volute tongue zone (0–60°): This zone is close to the eccentric vortex of the inner side of the blade in the volute tongue area, where the total pressure is low, the total pressure on the outside of the blade is not affected, and the pressure difference between the inner and outer sides is considerable.
- The volute zone (210–240°): The distance between the fan blade and the volute in the volute zone is relatively low, and the total pressure inside and outside the blade is significantly low.
- The exhaust zone (240–360°): In this zone, the total pressure on the outer side of the blade increases significantly, so that it reaches the maximum value at the air duct system. The total pressure on the inner side increases first and then decreases, and gradually decreases toward the direction of the volute tongue.
4.6. Analysis of Spectral Characteristics
5. Conclusions
- (1)
- As the system flow changes, the static pressure in the air duct changes significantly, and the larger the flow rate, the larger the negative pressure value. It was found that the pressure distribution range under different working conditions and flow rates is different. Moreover, the pressure at the eccentric vortex core is different. Minor changes occur at the position of the eccentric vortex core.
- (2)
- As the flow of the cross-flow fan decreases, the area of the airflow passage area decreases, the area of the eccentric vortex gradually increases, the airflow at the outlet expands, and the uniformity gets worse.
- (3)
- As the flow rate increases, the distribution of vorticity increases gradually. Moreover, the area with large vorticity under various working conditions is basically distributed in the vicinity of the blade surface. It was observed that there are obvious wakes in the vicinity of the blade and the tail of the volute tongue. These wake and blade interactions generate pressure pulsation, resulting in the generation of aerodynamic noise.
- (4)
- The pressure on the circumferential direction (R = 59 mm, R = 33 mm) was consistent with the total pressure cloud result. The total minimum pressure appears in the eccentric vortex near the volute tongue and the volute return near the zone. Moreover, it is indicated that the total pressure near the eccentric vortex is significantly smaller than the total pressure of the main flow zone. As the flow rate decreases, the pressure pulsation amplitude of the eccentric vortex region greatly increases, and the static pressure and total pressure pulsation amplitude gradually increase. Close to the eccentric vortex on the inner side of the blade in the volute tongue area, the total pressure is low, the total pressure on the outside of the blade is not affected, and the pressure difference between the inner and outer sides is large.
- (5)
- Spectral characteristics show that the cross-flow fan is operating at the designed flow rate. The first peak appears at two times the blade passing frequency, indicating that the internal flow state is more reasonable under the flow condition. When the flow rate of the cross-flow fan is 0.4 Qd, there is no obvious peak at the harmonic frequency of the blade passage frequency. This indicates that the aerodynamic noise is caused by the main unstable flow.
Author Contributions
Funding
Acknowledgments
Conflicts of Interest
References
- Chunlu, H.J. Simulation of aero acoustic on air-conditioner. Chin. J. Mech. Eng. 2004, 40, 188–192. [Google Scholar]
- Zhi, N.G.; Xiao, B.S. Fan Noise Control Technology; Mechanical Industry Press: Beijing, China, 1985. [Google Scholar]
- Fan, B.E. Shen Yang Blower Research Institute and Other Translations, 1st ed.; Mechanical Industry Press: Beijing, China, 1983. [Google Scholar]
- Porter, A.M.; Markland, E. A Study of the Cross Flow Fan. J. Mech. Eng. Sci. 1970, 12, 421–431. [Google Scholar] [CrossRef]
- Fukutomi, J. Internal Flow and Performance of Cross-Flow Fan; JSME: Tokyo, Japan, 1995; pp. 3669–3705. [Google Scholar]
- Tsurusaki, H.; Tsujimoto, Y.; Yoshida, Y.; Kitagawa, K. Visualization measure and numerical analysis of internal flow in cross flow fan. J. Fluids Eng. 1997, 119, 633–638. [Google Scholar] [CrossRef]
- Tsurusaki, H.; Shimizu, H.; Tsujimoto, Y.; Yoshida, Y.; Kitagawa, K. Study of cross-flow fan internal flow by flow visualization(discussion of measured results by particle-tracking velocimetry. J. Fluids Eng. 1996, 39, 540–545. [Google Scholar] [CrossRef] [Green Version]
- Yang, B.; Zhong, F.Y.; Yuan, H.Q. Experimental study on internal flow of cross-flow fans. J. Mech. Eng. 2000, 36, 68–70. [Google Scholar] [CrossRef]
- Tanaka, S.; Murata, S. Scale effects in cross flow fans (effects of fan dimentions on flow details and the universal representation of performances). JSME 1995, 38, 388–397. [Google Scholar]
- You, B.; Wu, K.Q. Computational fluid dynamics simulation of unsteady evolvement of vortices flow in cross flow fan. J. Eng. Thermophys. 2004, 25, 238–240. [Google Scholar]
- You, B.; Wu, K.Q. Comparison research of the twisted impeller and the straight impeller in the cross flow fan. J. Eng. Thermophys. 2005, 26, 58–60. [Google Scholar]
- Akaike, S. Internal flow and fan characteristics of a cross flow fan. JSME 1997, 63, 583–589. [Google Scholar] [CrossRef]
- Liu, M. Numerical Analysis and Experimental Research on the Aeroacoustics of Cross-Flow Fans; Huazhong University of Science and Technology: Wuhan, China, 2009. [Google Scholar]
- Zhao, X.L. Internal Flow Mechanism and Noise Analysis for Cross-Flow Fan in Air-Conditioning; Huazhong University of Science and Technology: Wuhan, China, 2013. [Google Scholar]
- Liu, Q. Research on the Flow Field Characteristics in Duct System of Indoor Air Conditioner; Huazhong University of Science and Technology: Wuhan, China, 2011. [Google Scholar]
- Zhou, S.; Kong, F.; Wang, Z.; Yi, C.; Zhang, Y. Numerical simulationfor low specific-speed centrifugal pump with structured grid. J. Agric. Mach. 2011, 42, 66–69. [Google Scholar]
- Xing, G.L.; Zhou, S.P. Comparison and Analysis of Two K-ε Turbulence Models for Simulation of Flow Field in a Cross-Flow Fan; China Engineering Thermophysics Society: Shao Xing, China, 2008. [Google Scholar]
- Shih, Y.; Hou, H.; Chiang, H. On similitude of the cross flow fan in a split-type air-conditioner. Appl. Therm. Eng. 2008, 28, 1853–1864. [Google Scholar] [CrossRef]
Diameter (mm) | Dt | 111.5 |
Hub ratio | v | 0.63 |
Blade height (mm) | l | 66.8 |
Blade number | z | 35 |
Inlet angel (°) | β1 | 90 |
Outlet angel (°) | β2 | 26 |
Nominal Speed (rpm) | n | 800 |
Nominal flow rate (m3/h) | Qd | 822 |
Nominal power (w) | P | 20 |
© 2019 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (http://creativecommons.org/licenses/by/4.0/).
Share and Cite
Zhang, W.; Yuan, J.; Si, Q.; Fu, Y. Investigating the In-Flow Characteristics of Multi-Operation Conditions of Cross-Flow Fan in Air Conditioning Systems. Processes 2019, 7, 959. https://doi.org/10.3390/pr7120959
Zhang W, Yuan J, Si Q, Fu Y. Investigating the In-Flow Characteristics of Multi-Operation Conditions of Cross-Flow Fan in Air Conditioning Systems. Processes. 2019; 7(12):959. https://doi.org/10.3390/pr7120959
Chicago/Turabian StyleZhang, Weijie, Jianping Yuan, Qiaorui Si, and Yanxia Fu. 2019. "Investigating the In-Flow Characteristics of Multi-Operation Conditions of Cross-Flow Fan in Air Conditioning Systems" Processes 7, no. 12: 959. https://doi.org/10.3390/pr7120959
APA StyleZhang, W., Yuan, J., Si, Q., & Fu, Y. (2019). Investigating the In-Flow Characteristics of Multi-Operation Conditions of Cross-Flow Fan in Air Conditioning Systems. Processes, 7(12), 959. https://doi.org/10.3390/pr7120959