1. Introduction
Reactive compensation, a crucial strategy in the management of electrical systems, is used to attenuate the power losses present in the system. However, its impact goes far beyond simply reducing these losses. In addition to this effect, a series of benefits are triggered that collectively contribute to the optimization of the system. The marked voltage profile improvement is one of the most outstanding reactive compensation results. Since inadequate voltages can cause various problems in the operation of electrical equipment and devices, this improvement is essential to ensure stable and efficient operation. Likewise, work is being conducted on raising the power factor, representing the relationship between the active power consumed and the total apparent power. Increasing this factor maximizes active power utilization, minimizing losses from reactive power [
1,
2]. Another relevant aspect of reactive compensation is its impact on power transmission capacity. By mitigating the reactive currents in the system, additional capacity is released to transport active power. This can be especially beneficial in high-demand situations, avoiding network congestion and improving overall system efficiency [
3]. In summary, reactive compensation is not only limited to reducing power losses. Its scope extends to the optimization of the voltage profile, the increase in the power factor and the improvement of the power transmission capacity. These combined effects contribute significantly to electrical systems’ efficient and reliable operation [
4,
5].
This improvement in power transmission capacity is achieved with flexible alternating current transmission systems (FACTS); a device of this type is the DSTATCOM, capable of absorbing or delivering reactive power depending on the system requirement. These devices can be incorporated into all nodes of the system. However, an inadequate location can become counterproductive for the system’s proper operation [
6,
7].
In this way, implementing optimization techniques for the location and size of reactive compensation devices translates into substantial improvements in the voltage profile and the reduction in power losses in electrical systems. This strategic approach contributes to a more efficient and reliable operation and positively impacts daily life by ensuring a more stable and sustainable electricity supply.
This optimization problem has been extensively addressed in the literature, leading to the proposal of various methodologies to tackle and solve this issue. In [
8], an immune algorithm (AI) is implemented to size and locate the optimal connection point, improving the voltage profile, currents, power losses, and the installation cost of DSTATCOM; the author implements the technique in the 33- and 69-bar systems. In [
7], the implementation of a hybrid immune and genetic algorithm (IA-GA) is proposed to size and locate the optimal connection point to reduce power losses, as well as the annual cost of operation of the DSTATCOM; this technique is performed on the 33-bar test system. In [
9], the implementation of the improved bacterial foraging search algorithm (IBFA) is proposed; the objective function seeks to reduce power losses and improve both stability and the voltage profile. This proposal is implemented in a 78-bar system. In [
10], it is proposed to implement an analytical technique to optimally determine the location and dimensions of distributed generation (DG) and DSTATCOM; this proposal is carried out in the 34- and 69-bus systems. The author proposes improving the voltage profile as well as reducing power losses. In [
11], the implementation of the differential evolution algorithm is proposed to locate the DSTATCOM optimally, considering the maximization of a net cost savings/benefit analysis approach while minimizing the power lost in the network. In [
12], the optimal location and size of a STATCOM are addressed to improve the voltage stability margin; this is achieved via multi-criteria optimization by applying the CPF method to adjust the objective function. Ref. [
13] presents a multi-objective optimization approach to locate and size the DSTATCOM in radial distribution networks optimally, using the whale optimization algorithm (WOA) to reduce power losses, improve the voltage profile and increase the system reliability. The authors of [
14] address the simultaneous placement of renewable distributed generation (DG) and DSTATCOM in a radial distribution system to minimize power losses using the loss sensitivity factor and the hybrid lightning search algorithm-simplex method.
By carefully examining the current research landscape, it is observed that most researchers focus on addressing the problems of the localizing and sizing of reactive compensation using approaches based on heuristic techniques. In this context, the predominant objective is minimizing power losses inherent to the electrical system while constantly seeking to significantly improve the voltage profile in the network and achieve economic optimization. However, the influence of harmonics in the electrical system needs to be considered and included.
Within this context, it is essential to address the existing research gap and explore the integration of harmonics consideration into modelling heuristic techniques. This approach will not only enrich the understanding of reactive compensation but also enable the development of more comprehensive and effective solutions to current challenges in power system management. For this reason, in this document, in modelling the JAYA algorithm via simple harmonic penetration analysis, the incorporation of the harmonics generated via reactive compensation is addressed.
2. Materials and Methods
The present research study is distinguished by its innovative approach by integrating the power of MATLAB in combination with the specialized tool Matpower, using the JAYA optimization algorithm for the optimal determination of the location and sizing of the reactive compensation while taking advantage of Matpower to carry out the rigorous calculation of the power flows in the study systems, thus providing an outstanding level of precision in the analysis. It seeks to complement and expand the previously mentioned research. It presents a new horizon by introducing a fundamental restriction in the algorithm: establishing the maximum THDv that the bars can withstand due to the strategic incorporation of reactive compensation via the DSTATCOM.
The results anticipated, as a result of implementing the JAYA algorithm, a broadened spectrum of substantial improvements: a significant decrease in both the average and maximum voltage deviation is expected, together with a marked reduction in power losses, all within the framework of the ambitious goal that the THDv registered in each bus remain below the 3% limit, thus establishing an optimal energy quality threshold and guaranteeing the viability of reactive compensation in the analyzed system.
2.1. Simple Harmonic Penetration
After an exhaustive evaluation, the simplified harmonic penetration method is chosen, which is the ideal instrument to accurately calculate the total harmonic distortion index in voltage (THDv) in all the system bars by incorporating the DSTATCOM. In this instance, the DSTATCOM is conclusively defined as a harmonic enhancing source characterized by a 6-pulse converter. The manifestation of the harmonic spectrum inherent in this configuration is shown graphically in
Figure 1.
Harmonic penetration is based on the fact that it does not consider the harmonic interaction between the network and the non-linear elements [
15].
To determine the voltage of the bars via the inclusion of a harmonic generating source, the following equation is implemented:
where
is a vector made up of all the voltages of each system node at a frequency “
h”. The term
refers to the inverse of the admittance matrix considering the harmonic modelling for each harmonic “
”.
is also a vector of dimension “
”, where all the elements are 0, except for the bars where the harmonic generating devices are located. These values, different from 0, are calculated as a certain quantity of the current determined at fundamental frequency; this quantity is determined based on the harmonic spectrum of the harmonic generating source [
5].
2.2. Harmonic Distortion
The calculation of the total voltage harmonic distortion for each node is conducted using the following equation:
is the node voltage at the fundamental frequency, and is the harmonic “” order voltage.
2.3. JAYA Algorithm
JAYA algorithm, proposed in 2016 by Venkata Rao in [
16], is based on the concept that the solution obtained for a given problem should be directed towards the most favourable solution and avoid the worst solution.
JAYA is a population-based algorithm characterized by not depending on specific control parameters, which makes it easier to implement. It only requires using standard control parameters such as the number of design variables, the maximum number of generations and the size of the population [
16,
17,
18].
2.4. JAYA Algorithm Focused on the Optimal Location and Sizing of the DSTATCOM
The JAYA algorithm was implemented in the MATLAB software(2021 B), and the power flow calculation was performed using the Newton–Raphson algorithm proposed by Matpower.
For the implementation of the algorithm, two variables were determined: the first, the reactive power that the device must inject or absorb, and the second, the bar where the device is located.
The objective function is the minimization of the average voltage deviation and the reduction of power losses in the feeders.
where
and
are weighted by which the improvement priority is determined, either the voltage profile or the power losses, and the lost power is defined as the sum of the power sent from node “
i” to node “
” and the power transmitted from node “
” to node “
i”. The equation outlined in [
15] determines the average voltage deviation.
where
is the desired voltage value at node “
”,
is the real voltage value of node “
”, and “
” is the number of bars in the system.
2.4.1. Restrictions
The constraints used in the algorithm are the following:
where the minimum and maximum voltage limits are 0.90 and 1.10, respectively, the limits of the reactive power that can be injected or absorbed via the DSTATCOM are determined with the following criteria: the maximum value is obtained by adding the reactive power of the entire system, while the minimum value is calculated as the negative of the maximum power. The
value is determined as the maximum
value of all the bars in the system, and its limit is 3%, that is, the
.
2.4.2. Pseudocode
- Step 1:
Initialize the population size , termination criterion , priority of the weights , , the number of design variables , minimum and maximum limit of reactive power injected via the DSTATCOM; , maximum limit of acceptable , the number of system bars and the initial power losses of the system .
- Step 2:
Determine the values of the population considering the limits , , and .
- Step 3:
Evaluate the initial population in the objective function .
- Step 4:
Identify the values of the population particle with which the best and worst result in the . The best solution is when OF is minimum, and the worst solution is when is maximum.
- Step 5:
Modify the population with the values obtained in Step 4 using the following equation: .
- Step 6:
Evaluate the new population in the OF.
- Step 7:
Update the population to if the result obtained with is better than that obtained with .
- Step 8:
Repeat steps 1–7 until the completion criterion has been satisfied.
- Step 9:
Show the optimal result.
The OF is determined via the results obtained from the power flow using Newton–Raphson considering the values of the population (power delivered via the DSTATCOM in the bar ).
To determine the in all bars as a consequence of the incorporation of DSTATCOM, the following subroutine is used.
- Step 1:
Obtain data for the following: , and
- Step 2:
Calculate
matrix for harmonics 5, 7, 11, 13, 17 and 19;
Harmonic current as a function of the harmonic spectrum of the 6-pulse converter ;
Voltages for each harmonic in all buses ;
Calculate the . .
- Step 3:
Export results.
3. Test Systems and Case Studies
The systems in which the proposed model will be used are the 33- and 34-bar systems; a description of the proposed test systems is presented below.
This proposed system has a base power of 10 [MVA] and a base voltage of 11 [kV]. The total load connected to the system is 4636 [MW] of active power and 2873 [MVAr] of reactive power. The graphical representation of the system is shown in
Figure 2.
The 33-bar system establishes a base voltage of 12.66 [kV] and a base power of 10 [MVA]. The total load installed in this system is 3715 [MW] of active power and 2.3 [MVAr] of reactive power. The graphic representation of the system is presented in
Figure 3.
With the application of the proposed methodology in the two case studies, the results are presented for each system analyzed considering scenarios with and without harmonic restriction. The first analysis scenario does not incorporate the harmonic injection restriction, while the second scenario does include said restriction. This restriction prevents the total harmonic distortion of the voltage in all the bars from exceeding the established 3% limit.
4. Results
This section presents the results obtained using the optimization model in the 33- and 34-bar test systems.
4.1. 33-Bar System
In scenario 1, without the harmonic injection constraint, the algorithm converges on the optimal solution of incorporating the DSTATCOM at bus 30 with a capacity to deliver 1300 [kVAr]. With this incorporation of DSTATCOM, the voltage profile presents an improvement concerning the initial or base case; this is graphically evidenced in
Figure 4.
The red line represents the voltage level at each node in the scenario without reactive compensation. The blue graph represents the voltage profile when incorporating a DSTATCOM of the power and at the location determined using the algorithm.
In addition to the improvement in the voltage profile, there is evidence of a reduction in the power losses of the system under study; this reduction can be seen in
Figure 5.
Both active and reactive power losses are reduced by incorporating DSTATCOM.
Implementing a DSTATCOM of 854 [kVAr] in bus 27 is achieved by making the optimal location and dimensioning with the harmonic injection restriction. With this incorporation, an improvement is made in the voltage profile, reducing the voltage deviation, and both active and reactive power losses are also reduced; this can be evidenced in
Figure 6 and
Figure 7, respectively.
As can be seen, there is a reduction in the voltage deviation, which indicates a better voltage profile; in other words, the voltage in the system bars has values closer to 1 per unit concerning the initial case; additional evidence is a reduction in both active and reactive power losses.
Because, in the present scenario, there is a restriction of harmonic injection, it must be evidenced that the THDv in all the bars, due to the incorporation of the DSTATCOM, must be less than 3%; this is evidenced in
Figure 8.
The THDv in all nodes of the system remains at a value less than 3%; this is because, in the current scenario, the power of the DSTATCOM is restricted so that this low THDv is guaranteed in the system bars.
Table 1 details the results obtained by applying the optimization technique proposed in the 33-bar system, both for scenario 1 and scenario 2. Additionally, the values obtained are compared with the immune algorithm proposed by [
8].
Compared to the immune algorithm, the results obtained using the proposed method improve the reduction in power losses in scenarios 1 and 2. The average voltage deviation, as well as the maximum voltage deviation obtained with the immune algorithm, is surpassed by the results obtained with the JAYA algorithm in scenario 1.
The evolution of the objective function for the two scenarios of the 33-bar system is presented in
Figure 9. This figure shows the behaviour of the objective function as a function of the iterations. The system converges because there are particles that satisfy all the restrictions. If no particles satisfy all the restrictions, the system does not converge, implying that there is no solution for the scenario.
4.2. 34-Bar System
The results obtained in the scenario without the harmonic injection restriction, scenario 1, are presented. By implementing the proposed technique without restriction, the result is that the system must have a DSTATCOM of 1842 [MVAr] connected to bus 21. When implementing the DSTATCOM with the specified power and in the mentioned bus, there is a reduction in power losses and an improvement in the voltage profile. This is evidenced in
Figure 10 and
Figure 11, respectively.
To limit the total harmonic distortion of voltage in the system bars, the restriction is implemented in the proposed mathematical model; in this way, scenario 2 is obtained for the 34-bar system. In this scenario, the DSTATCOM must be added to bus 21 and inject 1476 [MVAr] into the network. With this implementation, it is possible to reduce both the voltage deviation and the power losses, ensuring that the THDv in all the bars is less than 3%.
In this configuration, similar to the unrestricted scenario, an improvement in voltage profile and a reduction in voltage deviation are observed.
Figure 12 graphically represents the reduction in the voltage drift and the improvement of the voltage profile.
Power losses in the current scenario are reduced as in the unrestricted scenario. Both active and reactive power losses for the 34-bar system are presented in
Figure 13.
Figure 14 demonstrates that in the study system, no bar exceeds the limit established for the THDv.
Table 2 details the results obtained for the case without the harmonic injection restriction and the scenario with the restriction.
The behaviour of the objective function for the scenario without the harmonics restriction and for the scenario with the harmonics restriction is presented in
Figure 15. This graph represents the evolution of the value of the objective function as a function of the iterations. It can be seen that a satisfactory result is achieved for the two proposed scenarios.
5. Conclusions
Through an exhaustive analysis and the implementation of the JAYA algorithm, the precise identification of the optimal location for integrating the DSTATCOM in the distribution 33- and 34-bar systems was achieved. This strategy proved highly effective in achieving optimal reactive power compensation, culminating in significantly reduced power losses and a palpably improved system voltage profile.
The results obtained via the JAYA algorithm underline the recommendation of placing the DSTATCOM devices on bars 27 and 21 for the 33- and 34-bar systems, respectively, with compensation capacities of 0.841 MVAr and 1.46 MVAr. This configuration has proven worth generating noticeable improvements compared to the initial conditions. In the 33-bar system, there was an 11.7% decrease in average voltage deviation, a 9.7% reduction in maximum voltage deviation, and a substantial 18.7% decrease in apparent power losses. For the 34-bar system, a 10.5% reduction in average voltage deviation, a 9.7% decrease in maximum voltage deviation, and a staggering 21.2% decrease in apparent power losses were achieved.
A significant achievement of this implementation is that the maximum total harmonic distortion in voltage (THDv) registered in both test systems is kept below the maximum limit established by 3%. This compliance demonstrates the effectiveness of the location and sizing strategy and the JAYA algorithm to improve power quality in the distribution systems analyzed substantially.
Author Contributions
Conceptualization, R.A., A.Á.T. and L.O.; Methodology, R.A. and A.Á.T.; Software, R.A. and A.Á.T.; Validation, R.A., A.Á.T. and L.O.; Formal analysis, R.A., A.Á.T. and L.O.; Investigation, R.A. and A.Á.T.; Resources, R.A. and L.O.; Data curation, R.A. and L.O.; Writing—original draft, R.A. and A.Á.T.; Writing—review & editing, R.A., A.Á.T. and L.O.; Visualization, R.A.; Supervision, A.Á.T.; Project administration, A.Á.T. and L.O.; Funding acquisition, A.Á.T. and L.O. All authors have read and agreed to the published version of the manuscript.
Funding
This research received no external funding.
Data Availability Statement
Data are contained within the article.
Conflicts of Interest
The authors declare no conflict of interest.
References
- Medina, S.M.; Aguila, A. Óptima Compensación de Potencia Reactiva en Redes de Distribución Radiales considerando periodo de diseño Optimal Compensation of Reactive Power in Radial Distribution Networks considering design period. In Proceedings of the 2019 International Conference on Information Systems and Computer Science (INCISCOS), Quito, Ecuador, 20–22 November 2019; pp. 108–115. [Google Scholar] [CrossRef]
- Téllez, A.Á.; López, G.; Isaac, I.; González, J.W. Optimal reactive power compensation in electrical distribution systems with distributed resources. Review. Heliyon 2018, 4, e00746. [Google Scholar] [CrossRef] [PubMed]
- Téllez, A.A. Optimización Multicriterio de Flujos de Potencia Reactiva en Sistemas Eléctricos de Distribución. Ph.D. Thesis, Universidad Pontificia Bolivariana de Medellín, Medellín, Colombia, 2021. Available online: http://hdl.handle.net/20.500.11912/8699 (accessed on 7 June 2023).
- Marcial M, S.; Aguila T, A.; Cuasapaz, D. Optimal Capacitor Placement and Sizing in Radial Distribution Networks, Using Modified IGHS. In Lecture Notes in Networks and Systems; Springer: Cham, Switzerland, 2023; Volume 512, pp. 166–179. [Google Scholar] [CrossRef]
- de Souza, A.G.U. Óptima Ubicación y Dimensionamiento de D-STATCOM Para la Compensación de Potencia Reactiva en Redes de Distribución Considerando la Incidencia de Armónicos. 2018. Available online: http://dspace.ups.edu.ec/handle/123456789/16314 (accessed on 7 June 2023).
- Gadupudi, L.; Rao, G.S.; Narayana Divakar, R.V.L.; Malik, H.; Alsaif, F.; Alsulamy, S.; Ustun, T.S. Fuzzy-Based Fifteen-Level VSC for STATCOM Operations with Single DC-Link Voltage. Sustainability 2023, 15, 6188. [Google Scholar] [CrossRef]
- Kallon, M.A.; Nyakoe, G.N.; Muriithi, C.M. Development of DSTATCOM Optimal Sizing and Location Technique Based on IA-GA for Power Loss Reduction and Voltage Profile Enhancement in an RDN. Int. J. Electr. Electron. Res. 2021, 9, 96–106. [Google Scholar] [CrossRef]
- Taher, S.A.; Afsari, S.A. Optimal location and sizing of DSTATCOM in distribution systems by immune algorithm. Int. J. Electr. Power Energy Syst. 2014, 60, 34–44. [Google Scholar] [CrossRef]
- Khan, B.; Redae, K.; Gidey, E.; Mahela, O.P.; Taha, I.B.M.; Hussien, M.G. Optimal integration of DSTATCOM using improved bacterial search algorithm for distribution network optimization. Alex. Eng. J. 2022, 61, 5539–5555. [Google Scholar] [CrossRef]
- Amin, A.; Kamel, S.; Yu, J. Developed Analytical Technique for Optimal Placement and Sizing of DG and DSTATCOM in Radial Distribution Systems. In Proceedings of the 2018 20th International Middle East Power Systems Conference, MEPCON 2018—Proceedings, Cairo, Egypt, 18–20 December 2018; pp. 1087–1091. [Google Scholar] [CrossRef]
- Sanam, J. Optimization of planning cost of radial distribution networks at different loads with the optimal placement of distribution STATCOM using differential evolution algorithm. Soft Comput 2020, 24, 13269–13284. [Google Scholar] [CrossRef]
- Ababssi, N.; Loulijat, A.; Semma, E.A. Implementation Optimal Location of STATCOM on the IEEE New England Power System Grid (100 kV). Int. J. Intell. Eng. Syst. 2022, 15, 441–454. [Google Scholar]
- Noori, A.; Zhang, Y.; Nouri, N.; Hajivand, M. Multi-Objective Optimal Placement and Sizing of Distribution Static Compensator in Radial Distribution Networks with Variable Residential, Commercial and Industrial Demands Considering Reliability. IEEE Access 2021, 9, 46911–46926. [Google Scholar] [CrossRef]
- Chinnaraj, S.G.R.; Kuppan, R. Optimal sizing and placement of multiple renewable distribution generation and DSTATCOM in radial distribution systems using hybrid lightning search algorithm-simplex method optimization algorithm. Comput. Intell. 2021, 37, 1673–1690. [Google Scholar] [CrossRef]
- Martínez, J.C. Estudios de Flujo Armónico de Cargas en Sistemas Eléctricos Utilizando el Paquete Informático MATPOWER. 2019. Available online: https://upcommons.upc.edu/handle/2117/176116 (accessed on 21 July 2023).
- Rao, R.V. Jaya: A simple and new optimization algorithm for solving constrained and unconstrained optimization problems. Int. J. Ind. Eng. Comput. 2016, 7, 19–34. [Google Scholar] [CrossRef]
- Pandey, H.M. Jaya a novel optimization algorithm: What, how and why? In Proceedings of the 2016 6th International Conference—Cloud System and Big Data Engineering (Confluence), Noida, India, 14–15 January 2016; pp. 728–730. [Google Scholar] [CrossRef]
- Alsajri, M.; Ismail, M.A.; Abdul-Baqi, S. A review on the recent application of jaya optimization algorithm. In Proceedings of the 2018 1st Annual International Conference on Information and Sciences, AiCIS, Fallujah, Iraq, 20–21 November 2018; pp. 129–132. [Google Scholar] [CrossRef]
| Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2023 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/).