Investigation of Ventilation Systems to Improve Air Quality in the Occupied Zone in Office Buildings
Abstract
:1. Introduction
2. Experimental Methodology
2.1. Office Workstations
- − displacement ventilation
- − mixed ventilation
2.2. Investigation Methods
- − In the laboratory the following parameters were measured [Figure A1] during the investigation:
- − temperature of primary air tp [°C]
- − air temperature at the measured points in the occupied zone ta [°C]
- − (1.1 m from the floor)
- − air relative humidity RH [%]
- − mean air velocity v [m∙s−1]
- − Turbulence Intensity TU [%]:
- − Draught rating DR [%]:
- − Induction ratio i [-]
- − primary air: the air coming directly from the diffuser
- − secondary air: the room air which is picked up and carried along by the primary air
- − total air: the entire stream is composed of a mixture of primary and secondary air
2.3. Numerical Model
3. Developed Air Ventilation System Element (Air-Jet Control Box)
4. Model Verification
5. Results and Discussion of Measurement for the Air-Jet Control Box
Induction Rate in the Occupied Zone Based on Simulations
6. Conclusions
- One of the most common ventilation types in offices is mixed ventilation. In this ventilation mode, the infection probability is high because of the properties of the airflow.
- At the UD, a new air-ventilation service element was developed and named as “air-jet control box”. This attachment allows for modifying the properties of the ceiling diffusers used in office buildings to suit the temporary conditions. Such properties are the airflow control, air velocity, temperature, and induction rate in the occupied zone.
- The aim was to supply as much fresh air as possible in the occupied zone with the air velocity allowed by the standards. The equipment did not cause a significant reduction in air volume, its resistance is low, therefore, it does not lead to higher energy consumption.
- It was shown that when using the air-jet control box, the induction rate was reduced, and the comfort parameters did not change significantly in the sitting position.
- Based on design software, the fresh air ratio for the standard ceiling swirl diffuser is 2.46 v% (volume percentage). Numerical models show that the fresh air ratio with the air-jet control box for the two different desk arrangements was 18.3 v% (flower layout) and 21.4 v% (island of four), respectively.
7. Future Plans and Different Fields of Application
Author Contributions
Funding
Institutional Review Board Statement
Informed Consent Statement
Data Availability Statement
Conflicts of Interest
Nomenclature
UD | University of Debrecen |
tp | temperature of primary air [°C] |
ta | air temperature at the measured points in the occupied zone [°C] |
RH | air Relative Humidity [%] |
v | mean air velocity [m∙s−1] |
TU | Turbulence Intensity [%] |
n | number of measurements |
xi | measured value |
average of measured value | |
DR | Draught rate [%] |
i | Induction ratio [-] |
vol% | volume percentage [%] |
DQJA-SR | swirl diffuser type by Schako Vertriebs GmbH |
Pil-R-Z | impulse diffuser type by Schako Vertriebs GmbH |
4-DF | ceiling diffuser type by Schako Vertriebs GmbH |
Xarto-Q6 | swirl diffuser type by TROX GmbH |
KG-215-415 | air grill type by Schako Vertriebs GmbH |
Appendix A
Instruments
Appendix B
Induction Rate: SCHAKO DQJA SR Swirl Diffuser
Appendix C
Thermal Comfort Requirements
Comfort Category | Operative Temperature [°C] | Average Air Velocity [m∙s−1] | ||
---|---|---|---|---|
Summer (Cooling) | Winter (Heating) | Summer (Cooling) | Winter (Heating) | |
A | 24.5 ± 1.0 | 22.0 ± 1.0 | 0.18 | 0.15 |
B | 24.5 ± 1.5 | 22.0 ± 2.0 | 0.22 | 0.18 |
C | 24.5 ± 2.5 | 22.0 ± 3.0 | 0.25 | 0.21 |
References
- Antoniadou, P.; Papadopoulos, A.M. Occupants’ thermal comfort: State of the art and the prospects of personalized assessment in office buildings. Energy Build. 2017, 153, 136–149. [Google Scholar] [CrossRef]
- Pérez-Lombard, L.; Ortiz, J.; Pout, C. A review on buildings energy consumption information. Energy Build. 2008, 40, 394–398. [Google Scholar] [CrossRef]
- WHO. Coronavirus Disease (COVID-19): How Is It Transmitted? Available online: www.who.int/news-room/questions-and-answers/item/coronavirus-disease-covid-19-how-is-it-transmitted (accessed on 24 February 2022).
- ASHRAE. Ashrae Position Document on Infectious Aerosols. Available online: www.ashrae.org/file%20library/about/position%20documents/pd_infectiousaerosols_2020.pdf (accessed on 24 February 2022).
- REHVA. Rehva COVID-19 Guidance. Available online: http://www.rehva.eu/fileadmin/user_upload/REHVA_COVID-19_guidance_document_ver2_20200403_1.pdf (accessed on 24 February 2022).
- Cao, S.-J.; Ren, C. Ventilation control strategy using low-dimensional linear ventilation models and artificial neural network. Build. Environ. 2018, 144, 316–333. [Google Scholar] [CrossRef]
- Luo, M.; Cao, B.; Damiens, J.; Lin, B.; Zhu, Y. Evaluating thermal comfort in mixed-mode buildings: A field study in a subtropical climate. Build. Environ. 2015, 88, 46–54. [Google Scholar] [CrossRef]
- Hummelgaard, J.; Juhl, P.; Sæbjörnsson, K.; Clausen, G.; Toftum, J.; Langkilde, G. Indoor air quality and occupant satisfaction in five mechanically and four naturally ventilated open-plan office buildings. Build. Environ. 2007, 42, 4051–4058. [Google Scholar] [CrossRef]
- Nguyen, A.T.; Singh, M.K.; Reiter, S. An adaptive thermal comfort model for hot humid South-East Asia. Build. Environ. 2012, 56, 291–300. [Google Scholar] [CrossRef] [Green Version]
- Damiati, S.A.; Zaki, S.A.; Rijal, H.B.; Wonorahardjo, S. Field study on adaptive thermal comfort in office buildings in Malaysia, Indonesia, Singapore, and Japan during hot and humid season. Build. Environ. 2016, 109, 208–223. [Google Scholar] [CrossRef]
- Pereira, P.F.; Ramos, N.M.M. The impact of mechanical ventilation operation strategies on indoor CO2 concentration and air exchange rates in residential buildings. Indoor Built Environ. 2021, 30, 1516–1530. [Google Scholar] [CrossRef]
- Persily, A.K. The relationship between indoor air quality and carbon dioxide. In Proceedings of the 7th Indoor Air Quality and Climate, Nagoya, Japan, 21–26 July 1996; pp. 961–966. [Google Scholar]
- Kalmár, T.; Kalmár, F. Investigation of natural aeration in home offices during the heating season—Case study. J. Build. Eng. 2020, 35, 102052. [Google Scholar] [CrossRef]
- Cardoso, V.E.M.; Pereira, P.F.; Ramos, N.M.M.; Almeida, R.M.S.F. The Impacts of Air Leakage Paths and Airtightness Levels on Air Change Rates. Buildings 2020, 10, 55. [Google Scholar] [CrossRef] [Green Version]
- Junghans, L.; Widerin, P. Thermal comfort and indoor air quality of the “Concept 22/26”, a new high performance building standard. Energy Build. 2017, 149, 114–122. [Google Scholar] [CrossRef]
- Valančius, R.; Jurelionis, A. Influence of indoor air temperature variation on office work performance. J. Environ. Eng. Landsc. Manag. 2012, 21, 19–25. [Google Scholar] [CrossRef]
- Kang, S.; Ou, D.; Mak, C.M. The impact of indoor environmental quality on work productivity in university open-plan research offices. Build. Environ. 2017, 124, 78–89. [Google Scholar] [CrossRef]
- Szczepanik-Scislo, N.; Schnotale, J. An Air Terminal Device with a Changing Geometry to Improve Indoor Air Quality for VAV Ventilation Systems. Energies 2020, 13, 4947. [Google Scholar] [CrossRef]
- Szczepanik-Scislo, N.; Scislo, L. Comparison of CFD and Multizone Modeling from Contaminant Migration from a Household Gas Furnace. Atmosphere 2021, 12, 79. [Google Scholar] [CrossRef]
- Liu, L.; Li, Y.; Nielsen, P.V.; Wei, J.; Jensen, R.L. Short-range airborne transmission of expiratory droplets between two people. Indoor Air 2016, 27, 452–462. [Google Scholar] [CrossRef]
- Ricciardi, P.; Buratti, C. Thermal comfort in open plan offices in northern Italy: An adaptive approach. Build. Environ. 2012, 56, 314–320. [Google Scholar] [CrossRef]
- Sun, C.; Zhai, Z. The efficacy of social distance and ventilation effectiveness in preventing COVID-19 transmission. Sustain. Cities Soc. 2020, 62, 102390. [Google Scholar] [CrossRef]
- Ren, C.; Zhu, H.-C.; Cao, S.-J. Ventilation Strategies for Mitigation of Infection Disease Transmission in an Indoor Environment: A Case Study in Office. Buildings 2022, 12, 180. [Google Scholar] [CrossRef]
- ISO 7730-1994; Moderate Thermal Environments-Determination of the PMV and PPD Indices and Specification of the Conditions for Thermal Comfort. International Organization for Standardization: Geneva, Switzerland, 1994.
- Zhao, B.; Li, X.; Yan, Q. A simplified system for indoor airflow simulation. Build. Environ. 2003, 38, 543–552. [Google Scholar] [CrossRef]
- Liu, J.; Zhu, S.; Kim, M.K.; Srebric, J. A Review of CFD Analysis Methods for Personalized Ventilation (PV) in Indoor Built Environments. Sustainability 2019, 11, 4166. [Google Scholar] [CrossRef] [Green Version]
- Szodrai, F.; Kalmár, F. Simulation of Temperature Distribution on the Face Skin in Case of Advanced Personalized Ventilation System. Energies 2019, 12, 1185. [Google Scholar] [CrossRef] [Green Version]
- Lin, H.-H. Improvement of Human Thermal Comfort by Optimizing the Airflow Induced by a Ceiling Fan. Sustainability 2019, 11, 3370. [Google Scholar] [CrossRef] [Green Version]
- Posner, J.; Buchanan, C.; Dunn-Rankin, D. Measurement and prediction of indoor air flow in a model room. Energy Build. 2002, 35, 515–526. [Google Scholar] [CrossRef]
- Mao, N.; Song, M.; Deng, S.S.; Pan, D.; Chen, S. Experimental and numerical study on air flow and moisture transport in sleeping environments with a task/ambient air conditioning (TAC) system. Energy Build. 2016, 133, 596–604. [Google Scholar] [CrossRef]
- Zhai, Z.J.; Zhang, Z.; Zhang, W.; Chen, Q.Y. Evaluation of Various Turbulence Models in Predicting Airflow and Turbulence in Enclosed Environments by CFD: Part 1—Summary of Prevalent Turbulence Models. HVAC&R Res. 2007, 13, 853–870. Available online: https://engineering.purdue.edu/~yanchen/paper/2007-8.pdf (accessed on 8 February 2022).
- Szczepanik-Scislo, N.; Antonowicz, A.; Scislo, L. PIV measurement and CFD simulations of an air terminal device with a dynamically adapting geometry. SN Appl. Sci. 2019, 1, 370. [Google Scholar] [CrossRef] [Green Version]
- ISO 7726-1998; Ergonomics of the Thermal Environment—Instruments for Measuring Physical Quantities. International Organization for Standardization: Geneva, Switzerland, 1998.
- MSZ CR 1752:2000; Ventilation for Buildings. Hungarian Standard Commitment: Budapest, Hungary, 2000.
- Ganguly, S.; Tan, L.; Date, A.; Kumar, M.S.M. Effect of Heat Loss in a Geothermal Reservoir. Energy Procedia 2017, 110, 77–82. [Google Scholar] [CrossRef]
Name | vmax [m∙s−1] | i v% |
---|---|---|
Schako-DQJA-SR | 0.14 | 40.7 2.46 |
Schako-Pil-R-Z | 0.15 | 24.5 4.08 |
Schako-4-DF | 0.18 | 16.7 5.99 |
Trox-Xarto-Q6 | 0.12 | - |
Air Supply Equipment Parameters | SCHAKO-DQJA-SR Swirl Diffuser [Figure A2] i | SCHAKO-KG215-415 Grill i |
---|---|---|
500 m3∙h−1; isotherm | 40.7 | 3.8 |
500 m3∙h−1; cooling (ΔT = 5 K) | 37.8 | 2.7 |
Island of Four Layout (ta: 23.9–24.4 °C) | |||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Empty Desktop | Desktop with Plexiglass | ||||||||||||
DQJA SR | Air-Jet Control Box | DQJA SR | Air-Jet Control Box | ||||||||||
Measure Points | V [m∙s−1] | TU [%] | DR [%] | v [m∙s−1] | TU [%] | DR [%] | v [m∙s−1] | TU [%] | DR [%] | v [m∙s−1] | TU [%] | DR [%] | |
2 | 0.03 | 66 | 0 | 0.09 | 58 | 7 | 0.03 | 67 | 0 | 0.14 | 51 | 13 | |
4 | 0.10 | 54 | 7 | 0.12 | 45 | 10 | 0.07 | 90 | 4 | 0.09 | 47 | 7 | |
7 | 0.04 | 68 | 0 | 0.07 | 72 | 5 | 0.08 | 55 | 5 | 0.07 | 54 | 3 | |
9 | 0.02 | 79 | 0 | 0.08 | 56 | 6 | 0.02 | 66 | 0 | 0.07 | 70 | 5 |
Flower Layout (ta: 23.9–24.4 °C) | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Empty Desktop | Desktop with Plexiglass | |||||||||||
DQJA SR | Air-Jet Control Box | DQJA SR | Air-Jet Control Box | |||||||||
Measure Points | v [m∙s−1] | TU [%] | DR [%] | v [m∙s−1] | TU [%] | DR [%] | v [m∙s−1] | TU [%] | DR [%] | v [m∙s−1] | TU [%] | DR [%] |
2 | 0.03 | 66 | 0 | 0.16 | 44 | 15 | 0.02 | 63 | 0 | 0.07 | 72 | 5 |
5 | 0.12 | 85 | 11 | 0.09 | 57 | 6 | 0.06 | 90 | 3 | 0.06 | 62 | 2 |
8 | 0.04 | 68 | 0 | 0.06 | 61 | 2 | 0.08 | 47 | 5 | 0.11 | 70 | 9 |
11 | 0.04 | 70 | 0 | 0.06 | 79 | 3 | 0.02 | 61 | 0 | 0.06 | 80 | 2 |
Air Supply Equipment | Type of Office Layout | Based on Estimation | Estimated Value of Induction Rate | Volume Percentage of Primary Air |
---|---|---|---|---|
SCHAKO-DQJA-SR swirl diffuser | not defined | Designer software of manufacturer | 40.7 | 2.46 |
Air-Jet Control Box | Island of four | Simulation | 4.67 | 21.41 |
Air-Jet Control Box | Flower | Simulation | 5.46 | 18.32 |
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations. |
© 2022 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/).
Share and Cite
Szekeres, S.; Kostyák, A.; Szodrai, F.; Csáky, I. Investigation of Ventilation Systems to Improve Air Quality in the Occupied Zone in Office Buildings. Buildings 2022, 12, 493. https://doi.org/10.3390/buildings12040493
Szekeres S, Kostyák A, Szodrai F, Csáky I. Investigation of Ventilation Systems to Improve Air Quality in the Occupied Zone in Office Buildings. Buildings. 2022; 12(4):493. https://doi.org/10.3390/buildings12040493
Chicago/Turabian StyleSzekeres, Szabolcs, Attila Kostyák, Ferenc Szodrai, and Imre Csáky. 2022. "Investigation of Ventilation Systems to Improve Air Quality in the Occupied Zone in Office Buildings" Buildings 12, no. 4: 493. https://doi.org/10.3390/buildings12040493
APA StyleSzekeres, S., Kostyák, A., Szodrai, F., & Csáky, I. (2022). Investigation of Ventilation Systems to Improve Air Quality in the Occupied Zone in Office Buildings. Buildings, 12(4), 493. https://doi.org/10.3390/buildings12040493